Cisco ONS 15454 SDH Troubleshooting Guide, Release 8.0
Chapter 2, Alarm Troubleshooting

Table Of Contents

Alarm Troubleshooting

2.1  Alarm Index by Default Severity

2.1.1  Critical Alarms (CR)

2.1.2  Major Alarms (MJ)

2.1.3  Minor Alarms (MN)

2.1.4  Not Alarmed Conditions (NA)

2.1.5  Not Reported Conditions (NR)

2.2  Alarms and Conditions Listed By Alphabetical Entry

2.3  Alarm Logical Objects

2.4  Alarm List by Logical Object Type

2.5  Trouble Notifications

2.5.1  Alarm Characteristics

2.5.2  Condition Characteristics

2.5.3  Severities

2.5.4  Alarm Hierarchy

2.5.5  Service Effect

2.5.6  States

2.6  Safety Summary

2.7  Alarm Procedures

2.7.1  AIS

Clear the AIS Condition

2.7.2  AIS-L

2.7.3  ALS

2.7.4  ALS-DISABLED

2.7.5  AMPLI-INIT

2.7.6  APC-CORR-SKIPPED

2.7.7  APC-DISABLED

2.7.8  APC-END

2.7.9  APC-OUT-OF-RANGE

2.7.10  APC-WRONG-GAIN

2.7.11  APSB

Clear the APSB Alarm

2.7.12  APSCDFLTK

Clear the APSCDFLTK Alarm

2.7.13  APSC-IMP

Clear the APSC-IMP Alarm

2.7.14  APSCINCON

Clear the APSCINCON Alarm on an STM-N Card in an MS-SPRing

2.7.15  APSCM

Clear the APSCM Alarm

2.7.16  APSCNMIS

Clear the APSCNMIS Alarm

2.7.17  APS-INV-PRIM

2.7.18  APS-PRIM-FAC

2.7.19  APS-PRIM-SEC-MISM

2.7.20  AS-CMD

Clear the AS-CMD Condition

2.7.21  AS-MT

Clear the AS-MT Condition

2.7.22  AS-MT-OOG

Clear the AS-MT-OOG Condition

2.7.23  AU-AIS

Clear the AU-AIS Condition

2.7.24  AUD-LOG-LOSS

Clear the AUD-LOG-LOSS Condition

2.7.25  AUD-LOG-LOW

2.7.26  AU-LOF

Clear the AU-LOF Alarm

2.7.27  AU-LOP

Clear the AU-LOP Alarm

2.7.28  AUTOLSROFF

Clear the AUTOLSROFF Alarm

2.7.29  AUTONEG-RFI

Clear the AUTONEG-RFI Alarm

2.7.30  AUTORESET

Clear the AUTORESET Alarm

2.7.31  AUTOSW-AIS-SNCP

Clear the AUTOSW-AIS-SNCP Condition

2.7.32  AUTOSW-LOP-SNCP

Clear the AUTOSW-LOP-SNCP Alarm

2.7.33  AUTOSW-SDBER-SNCP

Clear the AUTOSW-SDBER-SNCP Condition

2.7.34  AUTOSW-SFBER-SNCP

Clear the AUTOSW-SFBER-SNCP Condition

2.7.35  AUTOSW-UNEQ-SNCP (VCMON-HP)

Clear the AUTOSW-UNEQ-SNCP (VCMON-HP) Condition

2.7.36  AUTOSW-UNEQ-SNCP (VCMON-LP)

Clear the AUTOSW-UNEQ-SNCP (VCMON-LP) Condition

2.7.37  AWG-DEG

2.7.38  AWG-FAIL

2.7.39  AWG-OVERTEMP

2.7.40  AWG-WARM-UP

2.7.41  BAT-FAIL

Clear the BATFAIL Alarm

2.7.42  BKUPMEMP

Clear the BKUPMEMP Alarm

2.7.43  CARLOSS (CE100T, CE1000)

Clear the CARLOSS (CE100T, CE1000) Alarm

2.7.44  CARLOSS (E100T, E1000F)

Clear the CARLOSS (E100T, E1000F) Alarm

2.7.45  CARLOSS (EQPT)

Clear the CARLOSS (EQPT) Alarm

2.7.46  CARLOSS (FC)

2.7.47  CARLOSS (G1000)

Clear the CARLOSS (G1000) Alarm

2.7.48  CARLOSS (GE)

2.7.49  CARLOSS (ISC)

2.7.50  CARLOSS (ML100T, ML1000, MLFX)

Clear the CARLOSS (ML100T, ML1000, MLFX) Alarm

2.7.51  CARLOSS (TRUNK)

2.7.52  CASETEMP-DEG

2.7.53  CLDRESTART

Clear the CLDRESTART Condition

2.7.54  COMIOXC

Clear the COMIOXC Alarm

2.7.55  COMM-FAIL

Clear the COMM-FAIL Alarm

2.7.56  CONTBUS-A-18

Clear the CONTBUS-A-18 Alarm

2.7.57  CONTBUS-B-18

Clear the CONTBUS-B-18 Alarm

2.7.58  CONTBUS-DISABLED

Clear the CONTBUS-DISABLED Alarm

2.7.59  CONTBUS-IO-A

Clear the CONTBUS-IO-A Alarm

2.7.60  CONTBUS-IO-B

Clear the CONTBUS-IO-B Alarm

2.7.61  CPP-INCAPABLE

Clear the CPP-INCAPABLE Alarm

2.7.62  CTNEQPT-MISMATCH

Clear the CTNEQPT-MISMATCH Condition

2.7.63  CTNEQPT-PBPROT

Clear the CTNEQPT-PBPROT Alarm

2.7.64  CTNEQPT-PBWORK

Clear the CTNEQPT-PBWORK Alarm

2.7.65  DATA-CRC

Clear the DATA-CRC Alarm

2.7.66  DATAFLT

Clear the DATAFLT Alarm

2.7.67  DBOSYNC

Clear the DBOSYNC Alarm

2.7.68  DCU-LOSS-FAIL

2.7.69  DISCONNECTED

Clear the DISCONNECTED Alarm

2.7.70  DS3-MISM

Clear the DS3-MISM Condition

2.7.71  DSP-COMM-FAIL

2.7.72  DSP-FAIL

2.7.73  DUP-IPADDR

Clear the DUP-IPADDR Alarm

2.7.74  DUP-NODENAME

Clear the DUP-NODENAME Alarm

2.7.75  DUP-SHELF-ID

2.7.76  EHIBATVG

Clear the EHIBATVG Alarm

2.7.77  ELWBATVG

Clear the ELWBATVG Alarm

2.7.78  EOC

Clear the EOC Alarm

2.7.79  EOC-L

2.7.80  EQPT

Clear the EQPT Alarm

2.7.81  EQPT-DIAG

Clear the EQPT-DIAG Alarm

2.7.82  EQPT-MISS

Clear the EQPT-MISS Alarm

2.7.83  ERROR-CONFIG

Clear the ERROR-CONFIG Alarm

2.7.84  ETH-LINKLOSS

Clear the ETH-LINKLOSS Condition

2.7.85  E-W-MISMATCH

Clear the E-W-MISMATCH Alarm with a Physical Switch

Clear the E-W-MISMATCH Alarm in CTC

2.7.86  EXCCOL

Clear the EXCCOL Alarm

2.7.87  EXERCISE-RING-FAIL

Clear the EXERCISE-RING-FAIL Condition

2.7.88  EXERCISE-SPAN-FAIL

Clear the EXERCISE-SPAN-FAIL Condition

2.7.89  EXT

Clear the EXT Alarm

2.7.90  EXTRA-TRAF-PREEMPT

Clear the EXTRA-TRAF-PREEMPT Alarm

2.7.91  FAILTOSW

Clear the FAILTOSW Condition

2.7.92  FAILTOSW-HO

Clear the FAILTOSW-HO Condition

2.7.93  FAILTOSW-LO

Clear the FAILTOSW-LO Condition

2.7.94  FAILTOSWR

Clear the FAILTOSWR Condition on a Four-Fiber MS-SPRing Configuration

2.7.95  FAILTOSWS

Clear the FAILTOSWS Condition

2.7.96  FAN

Clear the FAN Alarm

2.7.97  FAPS

Clear the FAPS Alarm

2.7.98  FAPS-CONFIG-MISMATCH

2.7.99  FC-DE-NES

Clear the FC-DE-NES Alarm

2.7.100  FC-NO-CREDITS

Clear the FC-NO-CREDITS Alarm

2.7.101  FDI

2.7.102  FE-AIS

Clear the FE-AIS Condition

2.7.103  FEC-MISM

2.7.104  FE-E1-MULTLOS

Clear the FE-E1-MULTLOS Condition

2.7.105  FE-E1-NSA

Clear the FE-E1-NSA Condition

2.7.106  FE-E1-SA

Clear the FE-E1-SA Condition

2.7.107  FE-E1-SNGLLOS

Clear the FE-E1-SNGLLOS Condition

2.7.108  FE-E3-NSA

Clear the FE-E3-NSA Condition

2.7.109  FE-E3-SA

Clear the FE-E3-SA Condition

2.7.110  FE-EQPT-NSA

Clear the FE-EQPT-NSA Condition

2.7.111  FE-FRCDWKSWBK-SPAN

Clear the FE-FRCDWKSWBK-SPAN Condition

2.7.112  FE-FRCDWKSWPR-RING

Clear the FE-FRCDWKSWPR-RING Condition

2.7.113  FE-FRCDWKSWPR-SPAN

Clear the FE-FRCDWKSWPR-SPAN Condition

2.7.114  FE-IDLE

2.7.115  FE-LOCKOUTOFPR-SPAN

Clear the FE-LOCKOUTOFPR-SPAN Condition

2.7.116  FE-LOF

Clear the FE-LOF Condition

2.7.117  FE-LOS

Clear the FE-LOS Condition

2.7.118  FE-MANWKSWBK-SPAN

Clear the FE-MANWKSWBK-SPAN Condition

2.7.119  FE-MANWKSWPR-RING

Clear the FE-MANWKSWPR-RING Condition

2.7.120  FE-MANWKSWPR-SPAN

Clear the FE-MANWKSWPR-SPAN Condition

2.7.121  FEPRLF

Clear the FEPRLF Alarm on an MS-SPRing

2.7.122  FIBERTEMP-DEG

2.7.123  FORCED-REQ

Clear the FORCED-REQ Condition

2.7.124  FORCED-REQ-RING

Clear the FORCED-REQ-RING Condition

2.7.125  FORCED-REQ-SPAN

Clear the FORCED-REQ-SPAN Condition

2.7.126  FP-LINK-LOSS

Clear the FP-LINK-LOSS Condition

2.7.127  FRCDSWTOINT

2.7.128  FRCDSWTOPRI

2.7.129  FRCDSWTOSEC

2.7.130  FRCDSWTOTHIRD

2.7.131  FRNGSYNC

Clear the FRNGSYNC Condition

2.7.132  FSTSYNC

2.7.133  FTA-MISMATCH

2.7.134  FULLPASSTHR-BI

Clear the FULLPASSTHR-BI Condition

2.7.135  GAIN-HDEG

2.7.136  GAIN-HFAIL

2.7.137  GAIN-LDEG

2.7.138  GAIN-LFAIL

2.7.139  GCC-EOC

2.7.140  GE-OOSYNC

2.7.141  GFP-CSF

Clear the GFP-CSF Alarm

2.7.142  GFP-DE-MISMATCH

Clear the GFP-DE-MISMATCH Alarm

2.7.143  GFP-EX-MISMATCH

Clear the GFP-EX-MISMATCH Alarm

2.7.144  GFP-LFD

Clear the GFP-LFD Alarm

2.7.145  GFP-NO-BUFFERS

Clear the GFP-NO-BUFFERS Alarm

2.7.146  GFP-UP-MISMATCH

Clear the GFP-UP-MISMATCH Alarm

2.7.147  HELLO

Clear the HELLO Alarm

2.7.148  HI-LASERBIAS

Clear the HI-LASERBIAS Alarm

2.7.149  HI-LASERTEMP

Clear the HI-LASERTEMP Alarm

2.7.150  HI-RXPOWER

Clear the HI-RXPOWER Alarm

2.7.151  HITEMP

Clear the HITEMP Alarm

2.7.152  HI-TXPOWER

Clear the HI-TXPOWER Alarm

2.7.153  HLDOVRSYNC

Clear the HLDOVRSYNC Alarm

2.7.154  HP-DEG

Clear the HP-DEG Condition

2.7.155  HP-ENCAP-MISMATCH

Clear the HP-ENCAP-MISMATCH Alarm

2.7.156  HP-EXC

Clear the HP-EXC Condition

2.7.157  HP-RFI

Clear the HP-RFI Condition

2.7.158  HP-TIM

Clear the HP-TIM Alarm

2.7.159  HP-UNEQ

Clear the HP-UNEQ Alarm

2.7.160  I-HITEMP

Clear the I-HITEMP Alarm

2.7.161  ILK-FAIL

2.7.162  IMPROPRMVL

Clear the IMPROPRMVL Alarm

2.7.163  INC-ISD

2.7.164  INCOMPATIBLE-SW

Clear the INCOMPATIBLE-SW Alarm

2.7.165  INHSWPR

Clear the INHSWPR Condition

2.7.166  INHSWWKG

Clear the INHSWWKG Condition

2.7.167  INTRUSION-PSWD

Clear the INTRUSION-PSWD Condition

2.7.168  INVMACADR

2.7.169  IOSCFGCOPY

2.7.170  ISIS-ADJ-FAIL

Clear the ISIS-ADJ-FAIL Alarm

2.7.171  KB-PASSTHR

Clear the KB-PASSTHR Condition

2.7.172  KBYTE-APS-CHAN-FAIL

Clear the KBYTE-APS-CHAN-FAIL Alarm

2.7.173  LAN-POL-REV

Clear the LAN-POL-REV Condition

2.7.174  LASER-APR

2.7.175  LASERBIAS-DEG

2.7.176  LASERBIAS-FAIL

2.7.177  LASERTEMP-DEG

2.7.178  LCAS-CRC

Clear the LCAS-CRC Condition

2.7.179  LCAS-RX-DNU

Clear the LCAS-RX-DNU Condition

2.7.180  LCAS-RX-FAIL

Clear the LCAS-RX-FAIL Condition

2.7.181  LCAS-RX-GRP-ERR

Clear the LCAS-RX-GRP-ERR Condition

2.7.182  LCAS-TX-ADD

2.7.183  LCAS-TX-DNU

2.7.184  LINK-KEEPALIVE

Clear the LINK-KEEPALIVE Alarm

2.7.185  LKOUTPR-S

Clear the LKOUTPR-S Condition

2.7.186  LMP-FAIL

Clear the LMP-FAIL Alarm

2.7.187  LMP-SD

Clear the LMP-SD Condition

2.7.188  LMP-SF

Clear the LMP-SF Condition

2.7.189  LMP-UNALLOC

2.7.190  LOA

Clear the LOA Alarm

2.7.191  LOCKOUT-REQ

Clear the LOCKOUT-REQ Condition

2.7.192  LOF (BITS)

Clear the LOF (BITS) Alarm

2.7.193  LOF (DS1, DS3, E1, E4, STM1E, STMN)

Clear the LOF (DS1, DS3, E1, E4, STM1E, STMN) Alarm

2.7.194  LOF (TRUNK)

2.7.195  LO-LASERBIAS

Clear the LO-LASERBIAS Alarm

2.7.196  LO-LASERTEMP

Clear the LO-LASERTEMP Alarm

2.7.197  LOM

Clear the LOM Alarm

2.7.198  LO-RXPOWER

Clear the LO-RXPOWER Alarm

2.7.199  LOS (2R)

2.7.200  LOS (BITS)

Clear the LOS (BITS) Alarm

2.7.201  LOS (DS1, DS3)

Clear the LOS (DS1, DS3) Alarm

2.7.202  LOS (E1, E3, E4)

Clear the LOS (E1, E3, E4) Alarm

2.7.203  LOS (ESCON)

2.7.204  LOS (FUDC)

Clear the LOS (FUDC) Alarm

2.7.205  LOS (ISC)

2.7.206  LOS (MSUDC)

2.7.207  LOS (OTS)

2.7.208  LOS (STM1E, STMN)

Clear the LOS (STM1E, STMN) Alarm

2.7.209  LOS (TRUNK)

2.7.210  LOS-O

2.7.211  LOS-P (OCH)

2.7.212  LOS-P (OMS, OTS)

2.7.213  LOS-P (TRUNK)

2.7.214  LO-TXPOWER

2.7.215  LPBKCRS

Clear the LPBKCRS Condition

2.7.216  LPBKDS3FEAC

Clear the LPBKDS3FEAC Condition

2.7.217  LPBKDS3FEAC-CMD

2.7.218  LPBKE1FEAC

2.7.219  LPBKE3FEAC

2.7.220  LPBKFACILITY (CE100T, CE1000)

Clear the LPBKFACILITY (CE100T, CE1000) Condition

2.7.221  LPBKFACILITY (DS1, DS3)

Clear the LPBKFACILITY (DS1, DS3) Condition

2.7.222  LPBKFACILITY (E1, E3, E4)

Clear the LPBKFACILITY (E1, E3, E4) Condition

2.7.223  LPBKFACILITY (ESCON)

2.7.224  LPBKFACILITY (FC)

2.7.225  LPBKFACILITY (FCMR)

Clear the LPBKFACILITY (FCMR) Condition

2.7.226  LPBKFACILITY (G1000)

Clear the LPBKFACILITY (G1000) Condition

2.7.227  LPBKFACILITY (GE)

2.7.228  LPBKFACILITY (ISC)

Clear the LPBKFACILITY Condition

2.7.229  LPBKFACILITY (STM1E, STMN)

Clear the LPBKFACILITY (STM1E, STMN) Condition

2.7.230  LPBKFACILITY (TRUNK)

2.7.231  LPBKTERMINAL (CE100T, CE1000)

Clear the LPBKTERMINAL (CE100T, CE1000) Condition

2.7.232  LPBKTERMINAL (DS1, DS3)

Clear the LPBKTERMINAL (DS3) Condition

2.7.233  LPBKTERMINAL (E1, E3, E4)

Clear the LPBKTERMINAL (E1, E3, E4) Condition

2.7.234  LPBKTERMINAL (ESCON)

2.7.235  LPBKTERMINAL (FC)

2.7.236  LPBKTERMINAL (FCMR)

Clear the LPBKTERMINAL (FCMR) Condition

2.7.237  LPBKTERMINAL (G1000)

Clear the LPBKTERMINAL (G1000) Condition

2.7.238  LPBKTERMINAL (GE)

2.7.239  LPBKTERMINAL (ISC)

Clear the LPBKTERMINAL Condition

2.7.240  LPBKTERMINAL (STM1E, STMN)

Clear the LPBKTERMINAL (STM1E, STMN) Condition

2.7.241  LPBKTERMINAL (TRUNK)

2.7.242  LP-DEG

Clear the LP-DEG Condition

2.7.243  LP-ENCAP-MISMATCH

Clear the LP-ENCAP-MISMATCH Alarm

2.7.244  LP-EXC

Clear the LP-EXC Condition

2.7.245  LP-PLM

Clear the LP-PLM Alarm

2.7.246  LP-RFI

Clear the LP-RFI Condition

2.7.247  LP-TIM

Clear the LP-TIM Alarm

2.7.248  LP-UNEQ

Clear the LP-UNEQ Alarm

2.7.249  MAN-REQ

Clear the MAN-REQ Condition

2.7.250  MANRESET

2.7.251  MANSWTOINT

2.7.252  MANSWTOPRI

2.7.253  MANSWTOSEC

2.7.254  MANSWTOTHIRD

2.7.255  MANUAL-REQ-RING

Clear the MANUAL-REQ-RING Condition

2.7.256  MANUAL-REQ-SPAN

Clear the MANUAL-REQ-SPAN Condition

2.7.257  MAX-STATIONS

Clear the MAX-STATIONS Alarm

2.7.258  MEA (BIC)

2.7.259  MEA (EQPT)

Clear the MEA (EQPT) Alarm

2.7.260  MEA (FAN)

Clear the MEA (FAN) Alarm

2.7.261  MEA (PPM)

2.7.262  MEA (SHELF)

2.7.263  MEM-GONE

2.7.264  MEM-LOW

2.7.265  MFGMEM (AICI-AEP, AICI-AIE, PPM)

Clear the MFGMEM Alarm

2.7.266  MFGMEM (BPLANE, FAN)

Clear the MFGMEM (BPLANE, FAN) Alarm

2.7.267  MS-AIS

Clear the MS-AIS Condition

2.7.268  MS-DEG

Clear the MS-DEG Condition

2.7.269  MS-EOC

Clear the MS-EOC Alarm

2.7.270  MS-EXC

Clear the MS-EXC Condition

2.7.271  MS-RFI

Clear the MS-RFI Condition

2.7.272  MSSP-OOSYNC

Clear the MSSP-OOSYNC Alarm

2.7.273  MSSP-SW-VER-MISM

Clear the MSSP-SW-VER-MISM Alarm

2.7.274  MS-SQUELCH-HP

2.7.275  MS-SQUELCH-LP

2.7.276  NO-CONFIG

Clear the NO-CONFIG Alarm

2.7.277  NON-CISCO-PPM

Clear the NON-CISCO-PPM Condition

2.7.278  NOT-AUTHENTICATED

2.7.279  OCHNC-INC

2.7.280  OCH-TERM-INC

2.7.281  ODUK-1-AIS-PM

2.7.282  ODUK-2-AIS-PM

2.7.283  ODUK-3-AIS-PM

2.7.284  ODUK-4-AIS-PM

2.7.285  ODUK-AIS-PM

2.7.286  ODUK-BDI-PM

2.7.287  ODUK-LCK-PM

2.7.288  ODUK-OCI-PM

2.7.289  ODUK-SD-PM

2.7.290  ODUK-SF-PM

2.7.291  ODUK-TIM-PM

2.7.292  OOU-TPT

Clear the OOT-TPT Condition

2.7.293  OPTNTWMIS

Clear the OPTNTWMIS Alarm

2.7.294  OPWR-HDEG

2.7.295  OPWR-HFAIL

2.7.296  OPWR-LDEG

2.7.297  OPWR-LFAIL

2.7.298  OSRION

2.7.299  OTUK-AIS

2.7.300  OTUK-BDI

2.7.301  OTUK-IAE

2.7.302  OTUK-LOF

2.7.303  OTUK-SD

2.7.304  OTUK-SF

2.7.305  OTUK-TIM

2.7.306  OUT-OF-SYNC

2.7.307  PARAM-MISM

2.7.308  PEER-NORESPONSE

Clear the PEER-NORESPONSE Alarm

2.7.309  PLM-P

Clear the PLM-P Alarm

2.7.310  PMI

2.7.311  PORT-FAIL

2.7.312  PORT-MISMATCH

Clear the PORT-MISMATCH Alarm

2.7.313  PRC-DUPID

Clear the PRC-DUPID Alarm

2.7.314  PROTNA

Clear the PROTNA Alarm

2.7.315  PROV-MISMATCH

2.7.316  PTIM

2.7.317  PWR-FAIL-A

Clear the PWR-FAIL-A Alarm

2.7.318  PWR-FAIL-B

Clear the PWR-FAIL-B Alarm

2.7.319  PWR-FAIL-RET-A

Clear the PWR-FAIL-RET-A Alarm

2.7.320  PWR-FAIL-RET-B

Clear the PWR-FAIL-RET-A Alarm

2.7.321  RAI

Clear the RAI Condition

2.7.322  RCVR-MISS

Clear the RCVR-MISS Alarm

2.7.323  RSV-RT-EXCD-RINGLET0

Clear the RSV-RT-EXCD-RINGLET0 Alarm

2.7.324  RSV-RT-EXCD-RINGLET1

Clear the RSV-RT-EXCD-RINGLET1 Alarm

2.7.325  RFI

2.7.326  RFI-L

2.7.327  RFI-V

2.7.328  RING-ID-MIS

Clear the RING-ID-MIS Alarm

2.7.329  RING-MISMATCH

Clear the RING-MISMATCH Alarm

2.7.330  RING-SW-EAST

2.7.331  RING-SW-WEST

2.7.332  ROLL

2.7.333  ROLL-PEND

2.7.334  ROUTE-OVERFLOW

Clear the ROUTE-OVERFLOW Condition

2.7.335  RPR-PASSTHR

Clear the RPR-PASSTHR Condition

2.7.336  RPR-PEER-MISS

Clear the RPR-PEER-MISS Condition

2.7.337  RPR-PROT-ACTIVE

Clear the RPR-PROT-ACTIVE Condition

2.7.338  RPR-PROT-CONFIG-MIS

Clear the RPR-PROT-CONFIG-MISM Alarm

2.7.339  RPR-RI-FAIL

Clear the RPR-RI-FAIL Condition

2.7.340  RPR-SD

Clear the RPR-SD Condition

2.7.341  RPR-SF

Clear the RPR-SF Condition

2.7.342  RPR-SPAN-MISMATCH

Clear the RPR-SPAN-MISMATCH Alarm

2.7.343  RPRW

Clear the RPRW Condition

2.7.344  RS-EOC

Clear the RS-EOC Alarm

2.7.345  RS-TIM

Clear the RS-TIM Alarm

2.7.346  RUNCFG-SAVENEED

2.7.347  SD (DS1, DS3, E1, E3, E4, STMN)

Clear the SD (DS3, E1, E3, E4, STMN) Condition

2.7.348  SD (TRUNK)

2.7.349  SDBER-EXCEED-HO

Clear the SDBER-EXCEED-HO Condition

2.7.350  SDBER-EXCEED-LO

Clear the SDBER-EXCEED-LO Condition

2.7.351  SD-L

2.7.352  SF (DS1, DS3, E1, E3, E4, STMN)

Clear the SF (DS3, E1, E3, E4, STMN) Condition

2.7.353  SF (TRUNK)

2.7.354  SFBER-EXCEED-HO

Clear the SFBER-EXCEED-HO Condition

2.7.355  SFBER-EXCEED-LO

Clear the SFBER-EXCEED-HO Condition

2.7.356  SF-L

2.7.357  SFTWDOWN

2.7.358  SHELF-COMM-FAIL

2.7.359  SH-IL-VAR-DEG-HIGH

2.7.360  SH-IL-VAR-DEG-LOW

2.7.361  SHUTTER-OPEN

2.7.362  SIGLOSS

Clear the SIGLOSS Alarm

2.7.363  SNTP-HOST

Clear the SNTP-HOST Alarm

2.7.364  SPANLEN-OUT-OF-RANGE

2.7.365  SPAN-SW-EAST

2.7.366  SPAN-SW-WEST

2.7.367  SQUELCH

Clear the SQUELCH Condition

2.7.368  SQUELCHED

Clear the SQUELCHED Condition

2.7.369  SQM

Clear the SQM Alarm

2.7.370  SSM-DUS

2.7.371  SSM-FAIL

Clear the SSM-FAIL Alarm

2.7.372  SSM-LNC

2.7.373  SSM-OFF

2.7.374  SSM-PRC

2.7.375  SSM-PRS

2.7.376  SSM-RES

2.7.377  SSM-SDH-TN

2.7.378  SSM-SETS

2.7.379  SSM-SMC

2.7.380  SSM-ST2

2.7.381  SSM-ST3

2.7.382  SSM-ST3E

2.7.383  SSM-ST4

2.7.384  SSM-STU

Clear the SSM-STU Condition

2.7.385  SSM-TNC

2.7.386  SW-MISMATCH

2.7.387  SWMTXMOD-PROT

Clear the SWMTXMOD-PROT Alarm

2.7.388  SWMTXMOD-WORK

Clear the SWMTXMOD-WORK Alarm

2.7.389  SWTOPRI

2.7.390  SWTOSEC

2.7.391  SWTOTHIRD

2.7.392  SYNC-FREQ

Clear the SYNC-FREQ Condition

2.7.393  SYNCLOSS

Clear the SYNCLOSS Alarm

2.7.394  SYNCPRI

Clear the SYNCPRI Alarm

2.7.395  SYNCSEC

Clear the SYNCSEC Alarm

2.7.396  SYNCTHIRD

Clear the SYNCTHIRD Alarm

2.7.397  SYSBOOT

2.7.398  TEMP-MISM

Clear the TEMP-MISM Condition

2.7.399  TIM

Clear the TIM Alarm

2.7.400  TIM-MON

Clear the TIM-MON Alarm

2.7.401  TPTFAIL (CE100T, CE1000)

Clear the TPTFAIL (CE100T, CE1000) Alarm

2.7.402  TPTFAIL (FCMR)

Clear the TPTFAIL (FCMR) Alarm

2.7.403  TPTFAIL (G1000)

Clear the TPTFAIL (G1000) Alarm

2.7.404  TPTFAIL (ML100T, ML1000, MLFX)

Clear the TPTFAIL (ML100T, ML1000, MLFX) Alarm

2.7.405  TRAIL-SIGNAL-FAIL

2.7.406  TRMT

Clear the TRMT Alarm

2.7.407  TRMT-MISS

Clear the TRMT-MISS Alarm

2.7.408  TU-AIS

Clear the TU-AIS Condition

2.7.409  TU-LOP

Clear the TU-LOP Alarm

2.7.410  TX-AIS

Clear the TX-AIS Condition

2.7.411  TX-LOF

Clear the TX-LOF Condition

2.7.412  TX-RAI

Clear the TX-RAI Condition

2.7.413  UNC-WORD

2.7.414  UNQUAL-PPM

Clear the UNQUAL-PPM Condition

2.7.415  UT-COMM-FAIL

2.7.416  UT-FAIL

2.7.417  VCG-DEG

Clear the VCG-DEG Condition

2.7.418  VCG-DOWN

Clear the VCG-DOWN Condition

2.7.419  VOA-HDEG

2.7.420  VOA-HFAIL

2.7.421  VOA-LDEG

2.7.422  VOA-LFAIL

2.7.423  VOLT-MISM

Clear the VOLT-MISM Condition

2.7.424  WKSWPR

Clear the WKSWPR Condition

2.7.425  WTR

2.7.426  WVL-MISMATCH

2.8  Traffic Card LED Activity

2.8.1  Typical Traffic Card LED Activity After Insertion

2.8.2  Typical Traffic Card LED Activity During Reset

2.8.3  Typical Card LED State After Successful Reset

2.8.4  Typical Cross-Connect LED Activity During Side Switch

2.9  Frequently Used Alarm Troubleshooting Procedures

2.9.1  Node and Ring Identification, Change, Visibility, and Termination

Identify an MS-SPRing Ring Name or Node ID Number

Change an MS-SPRing Ring Name

Change an MS-SPRing Node ID Number

Verify Node Visibility for Other Nodes

2.9.2  Protection Switching, Lock Initiation, and Clearing

Initiate a 1+1 Protection Port Force Switch Command

Initiate a 1+1 Protection Port Manual Switch Command

Clear a 1+1 Protection Port Force or Manual Switch Command

Initiate a Card or Port Lock On Command

Initiate a Card or Port Lock Out Command

Clear a Card or Port Lock On or Lock Out Command

Initiate a 1:1 Card Switch Command

Initiate a Force Switch for All Circuits on an SNCP Span

Initiate a Manual Switch for All Circuits on an SNCP Span

Initiate a Lock-Out-of-Protect Switch for All Circuits on an SNCP Span

Clear an SNCP Span External Switching Command

Initiate a Force Ring Switch on an MS-SPRing

Initiate a Force Span Switch on a Four-Fiber MS-SPRing

Initiate a Manual Ring Switch on an MS-SPRing

Initiate a Lockout on an MS-SPRing Protect Span

Initiate an Exercise Ring Switch on an MS-SPRing

Initiate an Exercise Ring Switch on a Four Fiber MS-SPRing

Clear an MS-SPRing External Switching Command

2.9.3  CTC Card Resetting and Switching

Reset a Traffic Card in CTC

Reset an ActiveTCC2/TCC2P Card and Activate the Standby Card

Reset the Standby TCC2/TCC2P Card

Side Switch the Active and Standby Cross-Connect Cards

2.9.4  Physical Card Reseating, Resetting, and Replacement

Remove and Reinsert (Reseat) the Standby TCC2/TCC2P Card

Remove and Reinsert (Reseat) Any Card

Physically Replace a Traffic Card

Physically Replace an In-Service Cross-Connect Card

2.9.5  Generic Signal and Circuit Procedures

Verify the Signal BER Threshold Level

Delete a Circuit

Verify or Create Node RS-DCC Terminations

Clear an STM-N Card Facility or Terminal Loopback Circuit

Clear an STM-N Card XC Loopback Circuit

Clear a Non-STM Card Facility or Terminal Loopback Circuit

2.9.6  Air Filter and Fan Procedures

Inspect, Clean, and Replace the Reusable Air Filter

Remove and Reinsert a Fan-Tray Assembly

Replace the Fan-Tray Assembly


Alarm Troubleshooting


This chapter gives a description, severity, and troubleshooting procedure for each commonly encountered Cisco ONS 15454 SDH alarm and condition. Tables 2-1 through 2-5 provide lists of ONS 15454 SDH alarms organized by severity. Table 2-6 provides a list of alarms organized alphabetically. Table 2-7 gives definitions of all ONS 15454 SDH alarm logical objects, which are the basis of the alarm profile list in Table 2-8. For a comprehensive list of all conditions, refer to the Cisco ONS 15454 SDH and Cisco ONS 15600 SDH TL1 Reference Guide. For instructions on using Transaction Language One (TL1) commands, refer to the Cisco ONS 15454 SDH and Cisco ONS 15600 SDH TL1 Command Guide.

An alarm's troubleshooting procedure applies to both the Cisco Transport Controller (CTC) and TL1 version of that alarm. If the troubleshooting procedure does not clear the alarm log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.

More information about alarm profile information modification and downloads is located in the "Manage Alarms" chapter of the Cisco ONS 15454 SDH Procedure Guide.

2.1  Alarm Index by Default Severity

The following tables group alarms and conditions by their default severities in the ONS 15454 SDH system. These severities are reported in the CTC Alarms window severity (SEV) column.


Note The CTC default alarm profile contains some alarms or conditions that are not currently implemented but are reserved for future use.


The following tables group alarms and conditions by the severity displayed in the CTC Alarms window in the severity (SEV) column. All severities listed in this manual are the default profile settings. Alarm severities can be altered from default settings for individual alarms or groups of alarms by creating a nondefault alarm profile and applying it on a port, card, or shelf basis. All settings (default or user-defined) that are Critical (CR) or Major (MJ) are demoted to Minor (MN) in situations that do not affect service.


Note The CTC default alarm profile in some cases contains two severities for one alarm (for example, MJ/MN). The ONS 15454 SDH platform default severity comes first (in this example, MJ), but the alarm can be demoted to the second severity in the presence of a higher-ranking alarm.


2.1.1  Critical Alarms (CR)

Table 2-1 alphabetically lists ONS 15454 SDH Critical (CR) alarms.

Table 2-1 ONS 15454 SDH Critical Alarm List 

I-HITEMP (NE)

MEA (PPM)

ILK-FAIL (TRUNK)

MFGMEM (AICI-AEP)

AU-LOF (VCTRM-HP)

IMPROPRMVL (EQPT)

MFGMEM (AICI-AIE)

AU-LOP (VCMON-HP)

IMPROPRMVL (PPM)

MFGMEM (BPLANE)

AU-LOP (VCTRM-HP)

LINK-KEEPALIVE (ML1000)

MFGMEM (FAN)

AUTOLSROFF (STMN)

LINK-KEEPALIVE (ML100T)

MFGMEM (PPM)

AWG-FAIL (OTS)

LINK-KEEPALIVE (MLFX)

OPWR-HFAIL (AOTS)

AWG-OVERTEMP (OTS)

LINK-KEEPALIVE (MLMR)

OPWR-HFAIL (OCH)

BKUPMEMP (EQPT)

LOA (VCG)

OPWR-HFAIL (OMS)

COMIOXC (EQPT)

LOF (DS3)

OPWR-HFAIL (OTS)

CONTBUS-DISABLED (EQPT)

LOF (E4)

OPWR-LFAIL (AOTS)

CTNEQPT-PBPROT (EQPT)

LOF (STM1E)

OPWR-LFAIL (OCH-TERM)

CTNEQPT-PBWORK (EQPT)

LOF (STMN)

OPWR-LFAIL (OCH)

EQPT (AICI-AEP)

LOF (TRUNK)

OPWR-LFAIL (OMS)

EQPT (AICI-AIE)

LOM (TRUNK)

OPWR-LFAIL (OTS)

EQPT (EQPT)

LOM (VCMON-HP)

OTUK-LOF (TRUNK)

EQPT (PPM)

LOS (2R)

OTUK-TIM (TRUNK)

EQPT-DIAG (EQPT)

LOS (DS3)

PORT-FAIL (OCH)

EQPT-MISS (FAN)

LOS (E3)

PLM-P (STSMON)

FAN (FAN)

LOS (E4)

PLM-P (STSTRM)

GAIN-HFAIL (AOTS)

LOS (ESCON)

RS-TIM (STMN)

GAIN-LFAIL (AOTS)

LOS (ISC)

SQM (VCTRM-HP)

GE-OOSYNC (FC)

LOS (OTS)

SWMTXMOD-PROT (EQPT)

GE-OOSYNC (GE)

LOS (STM1E)

SWMTXMOD-WORK (EQPT)

GE-OOSYNC (ISC)

LOS (STMN)

TIM (STMN)

GE-OOSYNC (TRUNK)

LOS (TRUNK)

TIM (TRUNK)

HITEMP (NE)

LOS-P (OCH)

VOA-HFAIL (AOTS)

HP-ENCAP-MISMATCH (VCTRM-HP)

LOS-P (OMS)

VOA-HFAIL (OCH)

HP-PLM (VCMON-HP)

LOS-P (OTS)

VOA-HFAIL (OMS)

HP-PLM (VCTRM-HP)

LOS-P (TRUNK)

VOA-HFAIL (OTS)

HP-TIM (VCTRM-HP)

LP-ENCAP-MISMATCH (VCTRM-LP)

VOA-LFAIL (AOTS)

HP-UNEQ (VCMON-HP)

MEA (BIC)

VOA-LFAIL (OCH)

HP-UNEQ (VCTRM-HP)

MEA (EQPT)

VOA-LFAIL (OMS)

MEA (FAN)

VOA-LFAIL (OTS)


2.1.2  Major Alarms (MJ)

Table 2-2 alphabetically lists ONS 15454 SDH Major (MJ) alarms.

Table 2-2 ONS 15454 SDH Major Alarm List 

APSCM (STMN)

GFP-EX-MISMATCH (FCMR)

RCVR-MISS (DS1)

APSCNMIS (STMN)

GFP-EX-MISMATCH (GFP-FAC)

RCVR-MISS (E1)

AUTONEG-RFI (ML1000)

GFP-LFD (CE1000)

RSV-RT-EXCD-RINGLET0 (RPRIF)

BAT-FAIL (PWR)

GFP-LFD (CE100T)

RSV-RT-EXCD-RINGLET1 (RPRIF)

CARLOSS (CE1000)

GFP-LFD (CEMR)

RING-ID-MIS (OSC-RING)

CARLOSS (CE100T)

GFP-LFD (FCMR)

RING-ID-MIS (STMN)

CARLOSS (CEMR)

GFP-LFD (GFP-FAC)

RING-MISMATCH (STMN)

CARLOSS (E1000F)

GFP-LFD (ML1000)

RPR-PEER-MISS (RPRIF)

CARLOSS (E100T)

GFP-LFD (ML100T)

RPR-PROT-CONFIG-MISM (RPRIF)

CARLOSS (EQPT)

GFP-LFD (MLFX)

RPR-RI-FAIL (RPRIF)

CARLOSS (FC)

GFP-LFD (MLMR)

RPR-SPAN-MISMATCH (ML1000)

CARLOSS (G1000)

GFP-NO-BUFFERS (FCMR)

RPR-SPAN-MISMATCH (ML100T)

CARLOSS (GE)

GFP-NO-BUFFERS (GFP-FAC)

RPR-SPAN-MISMATCH (MLFX)

CARLOSS (ISC)

GFP-UP-MISMATCH (CE1000)

RPR-SPAN-MISMATCH (MLMR)

CARLOSS (ML1000)

GFP-UP-MISMATCH (CE100T)

SHELF-COMM-FAIL (SHELF)

CARLOSS (ML100T)

GFP-UP-MISMATCH (CEMR)

SIGLOSS (ESCON)

CARLOSS (MLFX)

GFP-UP-MISMATCH (FCMR)

SIGLOSS (FC)

CARLOSS (MLMR)

GFP-UP-MISMATCH (GFP-FAC)

SIGLOSS (FCMR)

CARLOSS (TRUNK)

GFP-UP-MISMATCH (ML1000)

SIGLOSS (GE)

DATA-CRC (CE100T)

GFP-UP-MISMATCH (ML100T)

SIGLOSS (ISC)

DATA-CRC (ML1000)

GFP-UP-MISMATCH (MLFX)

SIGLOSS (TRUNK)

DATA-CRC (ML100T)

GFP-UP-MISMATCH (MLMR)

SQM (VCTRM-LP)

DATA-CRC (MLFX)

INVMACADR (BPLANE)

SYNCLOSS (FC)

DBOSYNC (NE)

LASERBIAS-FAIL (AOTS)

SYNCLOSS (FCMR)

DSP-COMM-FAIL (TRUNK)

LOF (DS1)

SYNCLOSS (GE)

DSP-FAIL (TRUNK)

LOF (E1)

SYNCLOSS (ISC)

DUP-SHELF-ID (SHELF)

LOM (VCTRM-HP)

SYNCLOSS (TRUNK)

EHIBATVG (PWR)

LOM (VCTRM-LP)

SYNCPRI (NE-SREF)

ELWBATVG (PWR)

LOS (DS1)

SYSBOOT (NE)

E-W-MISMATCH (STMN)

LOS (E1)

TIM (STM1E)

EXTRA-TRAF-PREEMPT (STMN)

LP-PLM (VCMON-LP)

TPTFAIL (CE1000)

FC-DE-NES (FC)

LP-PLM (VCTRM-LP)

TPTFAIL (CE100T)

FC-DE-NES (FCMR)

LP-TIM (VCMON-LP)

TPTFAIL (CEMR)

FC-DE-NES (TRUNK)

LP-TIM (VCTRM-LP)

TPTFAIL (FCMR)

FC-NO-CREDITS (FC)

LP-UNEQ (VCMON-LP)

TPTFAIL (G1000)

FC-NO-CREDITS (FCMR)

LP-UNEQ (VCTRM-LP)

TPTFAIL (ML1000)

FC-NO-CREDITS (TRUNK)

MAX-STATIONS (RPRIF)

TPTFAIL (ML100T)

FEC-MISM (TRUNK)

MEA (SHELF)

TPTFAIL (MLFX)

GFP-CSF (CE1000)

MEM-GONE (EQPT)

TPTFAIL (MLMR)

GFP-CSF (CE100T)

MSSP-OOSYNC (STMN)

TRMT (DS1)

GFP-CSF (CEMR)

ODUK-TIM-PM (TRUNK)

TRMT (E1)

GFP-CSF (FCMR)

OUT-OF-SYNC (FC)

TRMT-MISS (DS1)

GFP-CSF (GFP-FAC)

OUT-OF-SYNC (GE)

TRMT-MISS (E1)

GFP-CSF (ML1000)

OUT-OF-SYNC (TRUNK)

TU-LOP (VCMON-LP)

GFP-CSF (ML100T)

PEER-NORESPONSE (EQPT)

TU-LOP (VCTRM-LP)

GFP-CSF (MLFX)

PORT-MISMATCH (CEMR)

UT-COMM-FAIL (TRUNK)

GFP-CSF (MLMR)

PORT-MISMATCH (MLMR)

UT-FAIL (TRUNK)

GFP-DE-MISMATCH (FCMR)

PRC-DUPID (STMN)

WVL-MISMATCH (TRUNK)

GFP-DE-MISMATCH (GFP-FAC)

PROV-MISMATCH (TRUNK)

GFP-EX-MISMATCH (CE1000)

PTIM (TRUNK)


2.1.3  Minor Alarms (MN)

Table 2-3 alphabetically lists ONS 15454 SDH Minor (MN) alarms.

Table 2-3 ONS 15454 SDH Minor Alarm List 

HI-RXPOWER (2R)

LO-TXPOWER (GE)

HI-RXPOWER (ESCON)

LO-TXPOWER (ISC)

APC-CORR-SKIPPED (AOTS)

HI-RXPOWER (FC)

LO-TXPOWER (PPM)

APC-CORR-SKIPPED (OCH)

HI-RXPOWER (GE)

LO-TXPOWER (STMN)

APC-CORR-SKIPPED (OMS)

HI-RXPOWER (ISC)

LO-TXPOWER (TRUNK)

APC-CORR-SKIPPED (OTS)

HI-RXPOWER (STMN)

MEM-LOW (EQPT)

APC-OUT-OF-RANGE (AOTS)

HI-RXPOWER (TRUNK)

MS-EOC (STMN)

APC-OUT-OF-RANGE (OCH)

HITEMP (EQPT)

MSSP-SW-VER-MISM (STMN)

APC-OUT-OF-RANGE (OMS)

HI-TXPOWER (2R)

NON-CISCO-PPM (PPM)

APC-OUT-OF-RANGE (OTS)

HI-TXPOWER (EQPT)

OPWR-HDEG (AOTS)

APSB (STMN)

HI-TXPOWER (ESCON)

OPWR-HDEG (OCH-TERM)

APSCDFLTK (STMN)

HI-TXPOWER (FC)

OPWR-HDEG (OCH)

APSC-IMP (STMN)

HI-TXPOWER (GE)

OPWR-HDEG (OMS)

APSCINCON (STMN)

HI-TXPOWER (ISC)

OPWR-HDEG (OTS)

APSIMP (STMN)

HI-TXPOWER (PPM)

OPWR-LDEG (AOTS)

APS-INV-PRIM (STMN)

HI-TXPOWER (STMN)

OPWR-LDEG (OCH-TERM)

APS-PRIM-SEC-MISM (STMN)

HI-TXPOWER (TRUNK)

OPWR-LDEG (OCH)

AUTORESET (EQPT)

HP-TIM (VCMON-HP)

OPWR-LDEG (OMS)

AWG-DEG (OTS)

ISIS-ADJ-FAIL (STMN)

OPWR-LDEG (OTS)

CASETEMP-DEG (AOTS)

ISIS-ADJ-FAIL (TRUNK)

OTUK-IAE (TRUNK)

COMM-FAIL (EQPT)

KBYTE-APS-CHAN-FAIL (STMN)

PROTNA (EQPT)

CONTBUS-A-18 (EQPT)

LASERBIAS-DEG (AOTS)

PROV-MISMATCH (PPM)

CONTBUS-B-18 (EQPT)

LASERBIAS-DEG (OTS)

PWR-FAIL-A (EQPT)

CONTBUS-IO-A (EQPT)

LASERTEMP-DEG (AOTS)

PWR-FAIL-B (EQPT)

CONTBUS-IO-B (EQPT)

LMP-FAIL (CTRL)

PWR-FAIL-RET-A (EQPT)

DATAFLT (NE)

LMP-FAIL (GE)

PWR-FAIL-RET-B (EQPT)

DCU-LOSS-FAIL (OTS)

LMP-FAIL (STMN)

ROUTE-OVERFLOW (NSA)

DUP-IPADDR (NE)

LMP-FAIL (TLINK)

RS-EOC (STMN)

DUP-NODENAME (NE)

LMP-SD (GE)

SFTWDOWN (EQPT)

EOC (TRUNK)

LMP-SD (STMN)

SH-IL-VAR-DEG-HIGH (OTS)

EOC-L (TRUNK)

LMP-SF (GE)

SH-IL-VAR-DEG-LOW (OTS)

ERROR-CONFIG (EQPT)

LMP-SF (STMN)

SNTP-HOST (NE)

EXCCOL (EQPT)

LOF (BITS)

SPANLEN-OUT-OF-RANGE (OTS)

EXT (ENVALRM)

LO-LASERBIAS (EQPT)

SSM-FAIL (BITS)

FAPS-CONFIG-MISMATCH (EQPT)

LO-LASERBIAS (PPM)

SSM-FAIL (E1)

FEPRLF (STMN)

LO-LASERBIAS (STMN)

SSM-FAIL (STMN)

FE-SDPRLF (STMN)

LO-LASERTEMP (EQPT)

SSM-FAIL (TRUNK)

FIBERTEMP-DEG (AOTS)

LO-LASERTEMP (PPM)

SYNCPRI (EXT-SREF)

FP-LINK-LOSS (EQPT)

LO-LASERTEMP (STMN)

SYNCSEC (EXT-SREF)

GAIN-HDEG (AOTS)

LO-RXPOWER (2R)

SYNCSEC (NE-SREF)

GAIN-LDEG (AOTS)

LO-RXPOWER (ESCON)

SYNCTHIRD (EXT-SREF)

GCC-EOC (TRUNK)

LO-RXPOWER (FC)

SYNCTHIRD (NE-SREF)

HELLO (STMN)

LO-RXPOWER (GE)

TIM-MON (STMN)

HELLO (TRUNK)

LO-RXPOWER (ISC)

TIM-MON (TRUNK)

HI-LASERBIAS (2R)

LO-RXPOWER (STMN)

UNQUAL-PPM (PPM)

HI-LASERBIAS (EQPT)

LO-RXPOWER (TRUNK)

VOA-HDEG (AOTS)

HI-LASERBIAS (ESCON)

LOS (BITS)

VOA-HDEG (OCH)

HI-LASERBIAS (FC)

LOS (FUDC)

VOA-HDEG (OMS)

HI-LASERBIAS (GE)

LOS (MSUDC)

VOA-HDEG (OTS)

HI-LASERBIAS (ISC)

LOS-O (OCH)

VOA-LDEG (AOTS)

HI-LASERBIAS (PPM)

LOS-O (OMS)

VOA-LDEG (OCH)

HI-LASERBIAS (STMN)

LOS-O (OTS)

VOA-LDEG (OMS)

HI-LASERBIAS (TRUNK)

LO-TXPOWER (2R)

VOA-LDEG (OTS)

HI-LASERTEMP (EQPT)

LO-TXPOWER (EQPT)

HI-LASERTEMP (PPM)

LO-TXPOWER (ESCON)

HI-LASERTEMP (STMN)

LO-TXPOWER (FC)


2.1.4  Not Alarmed Conditions (NA)

Table 2-4 alphabetically lists ONS 15454 SDH Not Alarmed (NA) conditions.

Table 2-4 ONS 15454 SDH Not Alarmed Conditions List 

ALS (2R)

FORCED-REQ-SPAN (ESCON)

PARAM-MISM (AOTS)

ALS (AOTS)

FORCED-REQ-SPAN (FC)

PARAM-MISM (OCH-TERM)

ALS (ESCON)

FORCED-REQ-SPAN (GE)

PARAM-MISM (OCH)

ALS (FC)

FORCED-REQ-SPAN (ISC)

PARAM-MISM (OMS)

ALS (GE)

FORCED-REQ-SPAN (STMN)

PARAM-MISM (OTS)

ALS (ISC)

FORCED-REQ-SPAN (TRUNK)

PMI (OMS)

ALS (STMN)

FRCDSWTOINT (NE-SREF)

PMI (OTS)

ALS (TRUNK)

FRCDSWTOPRI (EXT-SREF)

PORT-MISMATCH (FCMR)

ALS-DISABLED (EQPT)

FRCDSWTOPRI (NE-SREF)

RAI (DS1)

AMPLI-INIT (AOTS)

FRCDSWTOSEC (EXT-SREF)

RAI (DS3)

APC-DISABLED (AOTS)

FRCDSWTOSEC (NE-SREF)

RAI (E1)

APC-DISABLED (EQPT)

FRCDSWTOTHIRD (EXT-SREF)

RING-SW-EAST (STMN)

APC-DISABLED (NE)

FRCDSWTOTHIRD (NE-SREF)

RING-SW-WEST (STMN)

APC-DISABLED (OCH)

FRNGSYNC (NE-SREF)

ROLL (VCMON-HP)

APC-DISABLED (OMS)

FSTSYNC (NE-SREF)

ROLL (VCMON-LP)

APC-DISABLED (OTS)

FTA-MISMATCH (EQPT)

ROLL (VCTRM-HP)

APC-DISABLED (SHELF)

FULLPASSTHR-BI (STMN)

ROLL (VCTRM-LP)

APC-END (NE)

HLDOVRSYNC (NE-SREF)

ROLL-PEND (VCMON-HP)

APC-WRONG-GAIN (AOTS)

HP-DEG (VCMON-HP)

ROLL-PEND (VCMON-LP)

APS-PRIM-FAC (STMN)

HP-DEG (VCTRM-HP)

ROLL-PEND (VCTRM-LP)

AS-CMD (2R)

HP-EXC (VCMON-HP)

RPR-PASSTHR (RPRIF)

AS-CMD (AOTS)

HP-EXC (VCTRM-HP)

RPR-PROT-ACTIVE (RPRIF)

AS-CMD (BPLANE)

IDLE (DS1)

RPR-SD (ML1000)

AS-CMD (CE1000)

INC-ISD (DS3)

RPR-SD (ML100T)

AS-CMD (CE100T)

INC-ISD (E3)

RPR-SD (MLFX)

AS-CMD (CEMR)

INHSWPR (EQPT)

RPR-SD (MLMR)

AS-CMD (DS1)

INHSWWKG (EQPT)

RPR-SF (ML1000)

AS-CMD (DS3)

INTRUSION-PSWD (NE)

RPR-SF (ML100T)

AS-CMD (E1000F)

IOSCFGCOPY (EQPT)

RPR-SF (MLFX)

AS-CMD (E100T)

KB-PASSTHR (STMN)

RPR-SF (MLMR)

AS-CMD (E1)

LAN-POL-REV (NE)

RPRW (ML1000)

AS-CMD (E3)

LASER-APR (AOTS)

RPRW (ML100T)

AS-CMD (E4)

LCAS-CRC (VCTRM-HP)

RPRW (MLFX)

AS-CMD (EQPT)

LCAS-CRC (VCTRM-LP)

RUNCFG-SAVENEED (EQPT)

AS-CMD (ESCON)

LCAS-RX-DNU (VCTRM-HP)

SD (DS1)

AS-CMD (FC)

LCAS-RX-DNU (VCTRM-LP)

SD (DS3)

AS-CMD (FCMR)

LCAS-RX-FAIL (VCTRM-HP)

SD (STM1E)

AS-CMD (G1000)

LCAS-RX-FAIL (VCTRM-LP)

SD (TRUNK)

AS-CMD (GE)

LCAS-RX-GRP-ERR (VCTRM-HP)

SD-L (TRUNK)

AS-CMD (GFP-FAC)

LCAS-RX-GRP-ERR (VCTRM-LP)

SF (DS1)

AS-CMD (ISC)

LCAS-TX-ADD (VCTRM-HP)

SF (DS3)

AS-CMD (ML1000)

LCAS-TX-ADD (VCTRM-LP)

SF (TRUNK)

AS-CMD (ML100T)

LCAS-TX-DNU (VCTRM-HP)

SF-L (TRUNK)

AS-CMD (MLFX)

LCAS-TX-DNU (VCTRM-LP)

SHUTTER-OPEN (OTS)

AS-CMD (MLMR)

LKOUTPR-S (STMN)

SPAN-NOT-MEASURED (OTS)

AS-CMD (NE)

LMP-UNALLOC (GE)

SPAN-SW-EAST (STMN)

AS-CMD (OCH)

LMP-UNALLOC (STMN)

SPAN-SW-WEST (STMN)

AS-CMD (OMS)

LOCKOUT-REQ (2R)

SQUELCH (STMN)

AS-CMD (OTS)

LOCKOUT-REQ (EQPT)

SQUELCHED (2R)

AS-CMD (PPM)

LOCKOUT-REQ (ESCON)

SQUELCHED (ESCON)

AS-CMD (PWR)

LOCKOUT-REQ (FC)

SQUELCHED (FC)

AS-CMD (SHELF)

LOCKOUT-REQ (GE)

SQUELCHED (GE)

AS-CMD (STM1E)

LOCKOUT-REQ (ISC)

SQUELCHED (ISC)

AS-CMD (STMN)

LOCKOUT-REQ (STMN)

SQUELCHED (STMN)

AS-CMD (TRUNK)

LOCKOUT-REQ (TRUNK)

SQUELCHED (TRUNK)

AS-MT (2R)

LOCKOUT-REQ (VCMON-HP)

SSM-DUS (BITS)

AS-MT (AOTS)

LOCKOUT-REQ (VCMON-LP)

SSM-DUS (DS1)

AS-MT (CE1000)

LPBKCRS (VCMON-HP)

SSM-DUS (E1)

AS-MT (CE100T)

LPBKCRS (VCTRM-HP)

SSM-DUS (STMN)

AS-MT (CEMR)

LPBKDS1FE-CMD (DS1)

SSM-DUS (TRUNK)

AS-MT (DS1)

LPBKDS3FEAC (DS3)

SSM-LNC (BITS)

AS-MT (DS3)

LPBKDS3FEAC-CMD (DS3)

SSM-LNC (NE-SREF)

AS-MT (E1)

LPBKDS3FEAC-CMD (E3)

SSM-LNC (STMN)

AS-MT (E3)

LPBKE1FEAC (E3)

SSM-LNC (TRUNK)

AS-MT (E4)

LPBKE3FEAC (E3)

SSM-OFF (BITS)

AS-MT (EQPT)

LPBKFACILITY (CE1000)

SSM-OFF (DS1)

AS-MT (ESCON)

LPBKFACILITY (CE100T)

SSM-OFF (E1)

AS-MT (FC)

LPBKFACILITY (CEMR)

SSM-OFF (STMN)

AS-MT (FCMR)

LPBKFACILITY (DS1)

SSM-OFF (TRUNK)

AS-MT (G1000)

LPBKFACILITY (DS3)

SSM-PRC (BITS)

AS-MT (GE)

LPBKFACILITY (E1)

SSM-PRC (NE-SREF)

AS-MT (GFP-FAC)

LPBKFACILITY (E3)

SSM-PRC (STMN)

AS-MT (ISC)

LPBKFACILITY (E4)

SSM-PRC (TRUNK)

AS-MT (ML1000)

LPBKFACILITY (ESCON)

SSM-PRS (E1)

AS-MT (ML100T)

LPBKFACILITY (FC)

SSM-PRS (TRUNK)

AS-MT (MLFX)

LPBKFACILITY (FCMR)

SSM-RES (DS1)

AS-MT (MLMR)

LPBKFACILITY (G1000)

SSM-RES (E1)

AS-MT (OCH)

LPBKFACILITY (GE)

SSM-RES (TRUNK)

AS-MT (OMS)

LPBKFACILITY (ISC)

SSM-SDH-TN (BITS)

AS-MT (OTS)

LPBKFACILITY (MLMR)

SSM-SDH-TN (NE-SREF)

AS-MT (PPM)

LPBKFACILITY (STM1E)

SSM-SDH-TN (STMN)

AS-MT (SHELF)

LPBKFACILITY (STMN)

SSM-SDH-TN (TRUNK)

AS-MT (STM1E)

LPBKFACILITY (TRUNK)

SSM-SETS (BITS)

AS-MT (STMN)

LPBKTERMINAL (CE1000)

SSM-SETS (NE-SREF)

AS-MT (TRUNK)

LPBKTERMINAL (CE100T)

SSM-SETS (STMN)

AS-MT-OOG (VCTRM-HP)

LPBKTERMINAL (CEMR)

SSM-SETS (TRUNK)

AS-MT-OOG (VCTRM-LP)

LPBKTERMINAL (DS1)

SSM-SMC (E1)

AUD-LOG-LOSS (NE)

LPBKTERMINAL (DS3)

SSM-SMC (TRUNK)

AUD-LOG-LOW (NE)

LPBKTERMINAL (E1)

SSM-ST2 (E1)

AUTOSW-LOP-SNCP (VCMON-HP)

LPBKTERMINAL (E3)

SSM-ST2 (TRUNK)

AUTOSW-LOP-SNCP (VCMON-LP)

LPBKTERMINAL (E4)

SSM-ST3 (E1)

LPBKTERMINAL (ESCON)

SSM-ST3 (TRUNK)

LPBKTERMINAL (FC)

SSM-ST3E (E1)

AUTOSW-SDBER-SNCP (VCMON-HP)

LPBKTERMINAL (FCMR)

SSM-ST3E (TRUNK)

AUTOSW-SDBER-SNCP (VCMON-LP)

LPBKTERMINAL (G1000)

SSM-ST4 (DS1)

AUTOSW-SFBER-SNCP (VCMON-HP)

LPBKTERMINAL (GE)

SSM-ST4 (E1)

AUTOSW-SFBER-SNCP (VCMON-LP)

LPBKTERMINAL (ISC)

SSM-ST4 (STMN)

AUTOSW-UNEQ-SNCP (VCMON-HP)

LPBKTERMINAL (MLMR)

SSM-ST4 (TRUNK)

AUTOSW-UNEQ-SNCP (VCMON-LP)

LPBKTERMINAL (STM1E)

SSM-STU (BITS)

AWG-WARM-UP (OTS)

LPBKTERMINAL (STMN)

SSM-STU (E1)

CLDRESTART (EQPT)

LPBKTERMINAL (TRUNK)

SSM-STU (NE-SREF)

CPP-INCAPABLE (EQPT)

LP-DEG (VCMON-LP)

SSM-STU (STMN)

CTNEQPT-MISMATCH (EQPT)

LP-DEG (VCTRM-LP)

SSM-STU (TRUNK)

DS3-MISM (DS3)

LP-EXC (VCMON-LP)

SSM-TNC (NE-SREF)

ETH-LINKLOSS (NE)

LP-EXC (VCTRM-LP)

SSM-TNC (STMN)

EXERCISE-RING-FAIL (STMN)

MAN-REQ (EQPT)

SSM-TNC (TRUNK)

EXERCISE-SPAN-FAIL (STMN)

MAN-REQ (ML1000)

SW-MISMATCH (EQPT)

FAILTOSW (2R)

MAN-REQ (ML100T)

SWTOPRI (EXT-SREF)

FAILTOSW (EQPT)

MAN-REQ (MLFX)

SWTOPRI (NE-SREF)

FAILTOSW (ESCON)

MAN-REQ (MLMR)

SWTOSEC (EXT-SREF)

FAILTOSW (FC)

MAN-REQ (VCMON-HP)

SWTOSEC (NE-SREF)

FAILTOSW (GE)

MAN-REQ (VCMON-LP)

SWTOTHIRD (EXT-SREF)

FAILTOSW (ISC)

MANRESET (EQPT)

SWTOTHIRD (NE-SREF)

FAILTOSW (STMN)

MANSWTOINT (NE-SREF)

SYNC-FREQ (DS1)

FAILTOSW (TRUNK)

MANSWTOPRI (EXT-SREF)

SYNC-FREQ (E1)

FAILTOSW-PATH (VCMON-HP)

MANSWTOPRI (NE-SREF)

SYNC-FREQ (STMN)

FAILTOSW-PATH (VCMON-LP)

MANSWTOSEC (EXT-SREF)

SYNC-FREQ (TRUNK)

FAILTOSWR (STMN)

MANSWTOSEC (NE-SREF)

TEMP-MISM (NE)

FAILTOSWS (STMN)

MANSWTOTHIRD (EXT-SREF)

TRAIL-SIGNAL-FAIL (OCH)

FAPS (FCMR)

MANSWTOTHIRD (NE-SREF)

TRAIL-SIGNAL-FAIL (TRUNK)

FAPS (TRUNK)

MANUAL-REQ-RING (STMN)

TX-IDLE (DS1)

FDI (OCH-TERM)

MANUAL-REQ-SPAN (2R)

TX-RAI (DS1)

FDI (OCH)

MANUAL-REQ-SPAN (ESCON)

TX-RAI (E1)

FE-AIS (E3)

MANUAL-REQ-SPAN (FC)

TX-RAI (E3)

FE-E1-MULTLOS (E3)

MANUAL-REQ-SPAN (GE)

UNC-WORD (TRUNK)

FE-E1-NSA (E3)

MANUAL-REQ-SPAN (ISC)

VCG-DEG (VCG)

FE-E1-SA (E3)

MANUAL-REQ-SPAN (STMN)

VCG-DOWN (VCG)

FE-E1-SNGLLOS (E3)

MANUAL-REQ-SPAN (TRUNK)

VOLT-MISM (PWR)

FE-E3-NSA (E3)

MS-DEG (E1)

WKSWPR (2R)

FE-E3-SA (E3)

MS-DEG (E3)

WKSWPR (EQPT)

FE-EQPT-NSA (E3)

MS-DEG (E4)

WKSWPR (ESCON)

FE-FRCDWKSWBK-SPAN (STMN)

MS-DEG (STM1E)

WKSWPR (FC)

FE-FRCDWKSWPR-RING (STMN)

MS-DEG (STMN)

WKSWPR (GE)

FE-FRCDWKSWPR-SPAN (STMN)

MS-EXC (E1)

WKSWPR (ISC)

FE-IDLE (E3)

MS-EXC (E3)

WKSWPR (STMN)

FE-LOCKOUTOFPR-SPAN (STMN)

MS-EXC (E4)

WKSWPR (VCMON-HP)

FE-LOF (E3)

MS-EXC (STM1E)

WKSWPR (VCMON-LP)

FE-LOS (E3)

MS-EXC (STMN)

WTR (2R)

FE-MANWKSWBK-SPAN (STMN)

MS-SQUELCH-HP (STMN)

WTR (EQPT)

FE-MANWKSWPR-RING (STMN)

MS-SQUELCH-LP (STMN)

WTR (ESCON)

FE-MANWKSWPR-SPAN (STMN)

MT-OCHNC (OTS)

WTR (FC)

FE-SD-SPAN (STMN)

NO-CONFIG (EQPT)

WTR (GE)

FE-SF-RING (STMN)

OCHNC-INC (OCHNC-CONN)

WTR (ISC)

FE-SF-SPAN (STMN)

OCHTERM-INC (OCH-TERM)

WTR (ML1000)

FORCED-REQ (EQPT)

ODUK-SD-PM (TRUNK)

WTR (ML100T)

FORCED-REQ (ML1000)

ODUK-SF-PM (TRUNK)

WTR (MLFX)

FORCED-REQ (ML100T)

OOU-TPT (VCTRM-HP)

WTR (MLMR)

FORCED-REQ (MLFX)

OOU-TPT (VCTRM-LP)

WTR (STMN)

FORCED-REQ (MLMR)

OSRION (AOTS)

WTR (TRUNK)

FORCED-REQ (VCMON-HP)

OSRION (OTS)

WTR (VCMON-HP)

FORCED-REQ (VCMON-LP)

OTUK-SD (TRUNK)

WTR (VCMON-LP)

FORCED-REQ-RING (STMN)

OTUK-SF (TRUNK)

FORCED-REQ-SPAN (2R)

OUT-OF-SYNC (ISC)


2.1.5  Not Reported Conditions (NR)

Table 2-5 alphabetically lists ONS 15454 SDH Not Reported (NR) conditions.

Table 2-5 ONS 15454 SDH Not Reported Conditions List 

AIS (BITS)

HP-RFI (VCTRM-HP)

ODUK-OCI-PM (TRUNK)

AIS (DS1)

LP-RFI (VCMON-LP)

OTUK-AIS (TRUNK)

AIS (DS3)

LP-RFI (VCTRM-LP)

OTUK-BDI (TRUNK)

AIS (E1)

MS-AIS (STM1E)

RFI (TRUNK)

AIS (E3)

MS-AIS (STMN)

RFI-L (TRUNK)

AIS (E4)

MS-RFI (STM1E)

ROLL-PEND (VCTRM-HP)

AIS (FUDC)

MS-RFI (STMN)

TU-AIS (VCMON-LP)

AIS (MSUDC)

ODUK-1-AIS-PM (TRUNK)

TU-AIS (VCTRM-LP)

AIS (TRUNK)

ODUK-2-AIS-PM (TRUNK)

TX-AIS (DS1)

AIS-L (TRUNK)

ODUK-3-AIS-PM (TRUNK)

TX-AIS (DS3)

AU-AIS (VCMON-HP)

ODUK-4-AIS-PM (TRUNK)

TX-AIS (E1)

AU-AIS (VCTRM-HP)

ODUK-AIS-PM (TRUNK)

TX-AIS (E3)

AUTOSW-AIS-SNCP (VCMON-HP)

ODUK-BDI-PM (TRUNK)

TX-LOF (DS1)

AUTOSW-AIS-SNCP (VCMON-LP)

ODUK-LCK-PM (TRUNK)

TX-LOF (E1)

HP-RFI (VCMON-HP)


2.2  Alarms and Conditions Listed By Alphabetical Entry

Table 2-6 alphabetically lists all ONS 15454 SDH alarms and conditions.

Table 2-6 ONS 15454 SDH Alarm and Condition Alphabetical List 

GFP-LFD (CE100T)

ODUK-OCI-PM (TRUNK)

GFP-LFD (CEMR)

ODUK-SD-PM (TRUNK)

GFP-LFD (FCMR)

ODUK-SF-PM (TRUNK)

GFP-LFD (GFP-FAC)

ODUK-TIM-PM (TRUNK)

AIS (BITS)

GFP-LFD (ML1000)

OOU-TPT (VCTRM-HP)

AIS (DS1)

GFP-LFD (ML100T)

OOU-TPT (VCTRM-LP)

AIS (DS3)

GFP-LFD (MLFX)

OPWR-HDEG (AOTS)

AIS (E1)

GFP-LFD (MLMR)

OPWR-HDEG (OCH)

AIS (E3)

GFP-NO-BUFFERS (FCMR)

OPWR-HDEG (OCH-TERM)

AIS (E4)

GFP-NO-BUFFERS (GFP-FAC)

OPWR-HDEG (OMS)

AIS (FUDC)

GFP-UP-MISMATCH (CE1000)

OPWR-HDEG (OTS)

AIS (MSUDC)

GFP-UP-MISMATCH (CE100T)

OPWR-HFAIL (AOTS)

AIS (TRUNK)

GFP-UP-MISMATCH (CEMR)

OPWR-HFAIL (OCH)

AIS-L (TRUNK)

GFP-UP-MISMATCH (FCMR)

OPWR-HFAIL (OMS)

ALS (2R)

GFP-UP-MISMATCH (GFP-FAC)

OPWR-HFAIL (OTS)

ALS (AOTS)

GFP-UP-MISMATCH (ML1000)

OPWR-LDEG (AOTS)

ALS (ESCON)

GFP-UP-MISMATCH (ML100T)

OPWR-LDEG (OCH)

ALS (FC)

GFP-UP-MISMATCH (MLFX)

OPWR-LDEG (OCH-TERM)

ALS (GE)

GFP-UP-MISMATCH (MLMR)

OPWR-LDEG (OMS)

ALS (ISC)

HELLO (STMN)

OPWR-LDEG (OTS)

ALS (STMN)

HELLO (TRUNK)

OPWR-LFAIL (AOTS)

ALS (TRUNK)

HI-LASERBIAS (2R)

OPWR-LFAIL (OCH)

ALS-DISABLED (EQPT)

HI-LASERBIAS (EQPT)

OPWR-LFAIL (OCH-TERM)

AMPLI-INIT (AOTS)

HI-LASERBIAS (ESCON)

OPWR-LFAIL (OMS)

APC-CORR-SKIPPED (AOTS)

HI-LASERBIAS (FC)

OPWR-LFAIL (OTS)

APC-CORR-SKIPPED (OCH)

HI-LASERBIAS (GE)

OSRION (AOTS)

APC-CORR-SKIPPED (OMS)

HI-LASERBIAS (ISC)

OSRION (OTS)

APC-CORR-SKIPPED (OTS)

HI-LASERBIAS (PPM)

OTUK-AIS (TRUNK)

APC-DISABLED (AOTS)

HI-LASERBIAS (STMN)

OTUK-BDI (TRUNK)

APC-DISABLED (EQPT)

HI-LASERBIAS (TRUNK)

OTUK-IAE (TRUNK)

APC-DISABLED (NE)

HI-LASERTEMP (EQPT)

OTUK-LOF (TRUNK)

APC-DISABLED (OCH)

HI-LASERTEMP (PPM)

OTUK-SD (TRUNK)

APC-DISABLED (OMS)

HI-LASERTEMP (STMN)

OTUK-SF (TRUNK)

APC-DISABLED (OTS)

HI-RXPOWER (2R)

OTUK-TIM (TRUNK)

APC-DISABLED (SHELF)

HI-RXPOWER (ESCON)

OUT-OF-SYNC (FC)

APC-END (NE)

HI-RXPOWER (FC)

OUT-OF-SYNC (GE)

APC-OUT-OF-RANGE (AOTS)

HI-RXPOWER (GE)

OUT-OF-SYNC (ISC)

APC-OUT-OF-RANGE (OCH)

HI-RXPOWER (ISC)

OUT-OF-SYNC (TRUNK)

APC-OUT-OF-RANGE (OMS)

HI-RXPOWER (STMN)

PARAM-MISM (AOTS)

APC-OUT-OF-RANGE (OTS)

HI-RXPOWER (TRUNK)

PARAM-MISM (OCH)

APC-WRONG-GAIN (AOTS)

HITEMP (EQPT)

PARAM-MISM (OCH-TERM)

APSB (STMN)

HITEMP (NE)

PARAM-MISM (OMS)

APSCDFLTK (STMN)

HI-TXPOWER (2R)

PARAM-MISM (OTS)

APSC-IMP (STMN)

HI-TXPOWER (EQPT)

PEER-NORESPONSE (EQPT)

APSCINCON (STMN)

HI-TXPOWER (ESCON)

PLM-P (STSMON)

APSCM (STMN)

HI-TXPOWER (FC)

PLM-P (STSTRM)

APSCNMIS (STMN)

HI-TXPOWER (GE)

PMI (OMS)

APSIMP (STMN)

HI-TXPOWER (ISC)

PMI (OTS)

APS-INV-PRIM (STMN)

HI-TXPOWER (PPM)

PORT-FAIL (OCH)

APS-PRIM-FAC (STMN)

HI-TXPOWER (STMN)

PORT-MISMATCH (CEMR)

APS-PRIM-SEC-MISM (STMN)

HI-TXPOWER (TRUNK)

PORT-MISMATCH (FCMR)

AS-CMD (2R)

HLDOVRSYNC (NE-SREF)

PORT-MISMATCH (MLMR)

AS-CMD (AOTS)

HP-DEG (VCMON-HP)

PRC-DUPID (STMN)

AS-CMD (BPLANE)

HP-DEG (VCTRM-HP)

PROTNA (EQPT)

AS-CMD (CE1000)

HP-ENCAP-MISMATCH (VCTRM-HP)

PROV-MISMATCH (PPM)

AS-CMD (CE100T)

HP-EXC (VCMON-HP)

PROV-MISMATCH (TRUNK)

AS-CMD (CEMR)

HP-EXC (VCTRM-HP)

PTIM (TRUNK)

AS-CMD (DS1)

HP-PLM (VCMON-HP)

PWR-FAIL-A (EQPT)

AS-CMD (DS3)

HP-PLM (VCTRM-HP)

PWR-FAIL-B (EQPT)

AS-CMD (E1)

HP-RFI (VCMON-HP)

PWR-FAIL-RET-A (EQPT)

AS-CMD (E1000F)

HP-RFI (VCTRM-HP)

PWR-FAIL-RET-B (EQPT)

AS-CMD (E100T)

HP-TIM (VCMON-HP)

RAI (DS1)

AS-CMD (E3)

HP-TIM (VCTRM-HP)

RAI (DS3)

AS-CMD (E4)

HP-UNEQ (VCMON-HP)

RAI (E1)

AS-CMD (EQPT)

HP-UNEQ (VCTRM-HP)

RCVR-MISS (DS1)

AS-CMD (ESCON)

IDLE (DS1)

RCVR-MISS (E1)

AS-CMD (FC)

I-HITEMP (NE)

RSV-RT-EXCD-RINGLET0 (RPRIF)

AS-CMD (FCMR)

ILK-FAIL (TRUNK)

RSV-RT-EXCD-RINGLET1 (RPRIF)

AS-CMD (G1000)

IMPROPRMVL (EQPT)

RFI (TRUNK)

AS-CMD (GE)

IMPROPRMVL (PPM)

RFI-L (TRUNK)

AS-CMD (GFP-FAC)

INC-ISD (DS3)

RING-ID-MIS (OSC-RING)

AS-CMD (ISC)

INC-ISD (E3)

RING-ID-MIS (STMN)

AS-CMD (ML1000)

INHSWPR (EQPT)

RING-MISMATCH (STMN)

AS-CMD (ML100T)

INHSWWKG (EQPT)

RING-SW-EAST (STMN)

AS-CMD (MLFX)

INTRUSION-PSWD (NE)

RING-SW-WEST (STMN)

AS-CMD (MLMR)

INVMACADR (BPLANE)

ROLL (VCMON-HP)

AS-CMD (NE)

IOSCFGCOPY (EQPT)

ROLL (VCMON-LP)

AS-CMD (OCH)

ISIS-ADJ-FAIL (STMN)

ROLL (VCTRM-HP)

AS-CMD (OMS)

ISIS-ADJ-FAIL (TRUNK)

ROLL (VCTRM-LP)

AS-CMD (OTS)

KB-PASSTHR (STMN)

ROLL-PEND (VCMON-HP)

AS-CMD (PPM)

KBYTE-APS-CHAN-FAIL (STMN)

ROLL-PEND (VCMON-LP)

AS-CMD (PWR)

LAN-POL-REV (NE)

ROLL-PEND (VCTRM-HP)

AS-CMD (SHELF)

LASER-APR (AOTS)

ROLL-PEND (VCTRM-LP)

AS-CMD (STM1E)

LASERBIAS-DEG (AOTS)

RPR-PASSTHR (RPRIF)

AS-CMD (STMN)

LASERBIAS-DEG (OTS)

RPR-PEER-MISS (RPRIF)

AS-CMD (TRUNK)

LASERBIAS-FAIL (AOTS)

RPR-PROT-ACTIVE (RPRIF)

AS-MT (2R)

LASERTEMP-DEG (AOTS)

RPR-PROT-CONFIG-MISM (RPRIF)

AS-MT (AOTS)

LCAS-CRC (VCTRM-HP)

RPR-RI-FAIL (RPRIF)

AS-MT (CE1000)

LCAS-CRC (VCTRM-LP)

RPR-SD (ML1000)

AS-MT (CE100T)

LCAS-RX-DNU (VCTRM-HP)

RPR-SD (ML100T)

AS-MT (CEMR)

LCAS-RX-DNU (VCTRM-LP)

RPR-SD (MLFX)

AS-MT (DS1)

LCAS-RX-FAIL (VCTRM-HP)

RPR-SD (MLMR)

AS-MT (DS3)

LCAS-RX-FAIL (VCTRM-LP)

RPR-SF (ML1000)

AS-MT (E1)

LCAS-RX-GRP-ERR (VCTRM-HP)

RPR-SF (ML100T)

AS-MT (E3)

LCAS-RX-GRP-ERR (VCTRM-LP)

RPR-SF (MLFX)

AS-MT (E4)

LCAS-TX-ADD (VCTRM-HP)

RPR-SF (MLMR)

AS-MT (EQPT)

LCAS-TX-ADD (VCTRM-LP)

RPR-SPAN-MISMATCH (ML1000)

AS-MT (ESCON)

LCAS-TX-DNU (VCTRM-HP)

RPR-SPAN-MISMATCH (ML100T)

AS-MT (FC)

LCAS-TX-DNU (VCTRM-LP)

RPR-SPAN-MISMATCH (MLFX)

AS-MT (FCMR)

LINK-KEEPALIVE (ML1000)

RPR-SPAN-MISMATCH (MLMR)

AS-MT (G1000)

LINK-KEEPALIVE (ML100T)

RPRW (ML1000)

AS-MT (GE)

LINK-KEEPALIVE (MLFX)

RPRW (ML100T)

AS-MT (GFP-FAC)

LINK-KEEPALIVE (MLMR)

RPRW (MLFX)

AS-MT (ISC)

LKOUTPR-S (STMN)

RS-EOC (STMN)

AS-MT (ML1000)

LMP-FAIL (CTRL)

RS-TIM (STMN)

AS-MT (ML100T)

LMP-FAIL (GE)

RUNCFG-SAVENEED (EQPT)

AS-MT (MLFX)

LMP-FAIL (STMN)

SD (DS1)

AS-MT (MLMR)

LMP-FAIL (TLINK)

SD (DS3)

AS-MT (OCH)

LMP-SD (GE)

SD (STM1E)

AS-MT (OMS)

LMP-SD (STMN)

SD (TRUNK)

AS-MT (OTS)

LMP-SF (GE)

SD-L (TRUNK)

AS-MT (PPM)

LMP-SF (STMN)

SF (DS1)

AS-MT (SHELF)

LMP-UNALLOC (GE)

SF (DS3)

AS-MT (STM1E)

LMP-UNALLOC (STMN)

SF (TRUNK)

AS-MT (STMN)

LOA (VCG)

SF-L (TRUNK)

AS-MT (TRUNK)

LOCKOUT-REQ (2R)

SFTWDOWN (EQPT)

AS-MT-OOG (VCTRM-HP)

LOCKOUT-REQ (EQPT)

SHELF-COMM-FAIL (SHELF)

AS-MT-OOG (VCTRM-LP)

LOCKOUT-REQ (ESCON)

SH-IL-VAR-DEG-HIGH (OTS)

AU-AIS (VCMON-HP)

LOCKOUT-REQ (FC)

SH-IL-VAR-DEG-LOW (OTS)

AU-AIS (VCTRM-HP)

LOCKOUT-REQ (GE)

SHUTTER-OPEN (OTS)

AUD-LOG-LOSS (NE)

LOCKOUT-REQ (ISC)

SIGLOSS (ESCON)

AUD-LOG-LOW (NE)

LOCKOUT-REQ (STMN)

SIGLOSS (FC)

AU-LOF (VCTRM-HP)

LOCKOUT-REQ (TRUNK)

SIGLOSS (FCMR)

AU-LOP (VCMON-HP)

LOCKOUT-REQ (VCMON-HP)

SIGLOSS (GE)

AU-LOP (VCTRM-HP)

LOCKOUT-REQ (VCMON-LP)

SIGLOSS (ISC)

AUTOLSROFF (STMN)

LOF (BITS)

SIGLOSS (TRUNK)

AUTONEG-RFI (ML1000)

LOF (DS1)

SNTP-HOST (NE)

AUTORESET (EQPT)

LOF (DS3)

SPANLEN-OUT-OF-RANGE (OTS)

AUTOSW-AIS-SNCP (VCMON-HP)

LOF (E1)

SPAN-NOT-MEASURED (OTS)

AUTOSW-AIS-SNCP (VCMON-LP)

LOF (E4)

SPAN-SW-EAST (STMN)

AUTOSW-LOP-SNCP (VCMON-HP)

LOF (STM1E)

SPAN-SW-WEST (STMN)

AUTOSW-LOP-SNCP (VCMON-LP)

LOF (STMN)

SQM (VCTRM-HP)

LOF (TRUNK)

SQM (VCTRM-LP)

LO-LASERBIAS (EQPT)

SQUELCH (STMN)

AUTOSW-SDBER-SNCP (VCMON-HP)

LO-LASERBIAS (PPM)

SQUELCHED (2R)

AUTOSW-SDBER-SNCP (VCMON-LP)

LO-LASERBIAS (STMN)

SQUELCHED (ESCON)

AUTOSW-SFBER-SNCP (VCMON-HP)

LO-LASERTEMP (EQPT)

SQUELCHED (FC)

AUTOSW-SFBER-SNCP (VCMON-LP)

LO-LASERTEMP (PPM)

SQUELCHED (GE)

AUTOSW-UNEQ-SNCP (VCMON-HP)

LO-LASERTEMP (STMN)

SQUELCHED (ISC)

AUTOSW-UNEQ-SNCP (VCMON-LP)

LOM (TRUNK)

SQUELCHED (STMN)

AWG-DEG (OTS)

LOM (VCMON-HP)

SQUELCHED (TRUNK)

AWG-FAIL (OTS)

LOM (VCTRM-HP)

SSM-DUS (BITS)

AWG-OVERTEMP (OTS)

LOM (VCTRM-LP)

SSM-DUS (DS1)

AWG-WARM-UP (OTS)

LO-RXPOWER (2R)

SSM-DUS (E1)

BAT-FAIL (PWR)

LO-RXPOWER (ESCON)

SSM-DUS (STMN)

BKUPMEMP (EQPT)

LO-RXPOWER (FC)

SSM-DUS (TRUNK)

CARLOSS (CE1000)

LO-RXPOWER (GE)

SSM-FAIL (BITS)

CARLOSS (CE100T)

LO-RXPOWER (ISC)

SSM-FAIL (E1)

CARLOSS (CEMR)

LO-RXPOWER (STMN)

SSM-FAIL (STMN)

CARLOSS (E1000F)

LO-RXPOWER (TRUNK)

SSM-FAIL (TRUNK)

CARLOSS (E100T)

LOS (2R)

SSM-LNC (BITS)

CARLOSS (EQPT)

LOS (BITS)

SSM-LNC (NE-SREF)

CARLOSS (FC)

LOS (DS1)

SSM-LNC (STMN)

CARLOSS (G1000)

LOS (DS3)

SSM-LNC (TRUNK)

CARLOSS (GE)

LOS (E1)

SSM-OFF (BITS)

CARLOSS (ISC)

LOS (E3)

SSM-OFF (DS1)

CARLOSS (ML1000)

LOS (E4)

SSM-OFF (E1)

CARLOSS (ML100T)

LOS (ESCON)

SSM-OFF (STMN)

CARLOSS (MLFX)

LOS (FUDC)

SSM-OFF (TRUNK)

CARLOSS (MLMR)

LOS (ISC)

SSM-PRC (BITS)

CARLOSS (TRUNK)

LOS (MSUDC)

SSM-PRC (NE-SREF)

CASETEMP-DEG (AOTS)

LOS (OTS)

SSM-PRC (STMN)

CLDRESTART (EQPT)

LOS (STM1E)

SSM-PRC (TRUNK)

COMIOXC (EQPT)

LOS (STMN)

SSM-PRS (E1)

COMM-FAIL (EQPT)

LOS (TRUNK)

SSM-PRS (TRUNK)

CONTBUS-A-18 (EQPT)

LOS-O (OCH)

SSM-RES (DS1)

CONTBUS-B-18 (EQPT)

LOS-O (OMS)

SSM-RES (E1)

CONTBUS-DISABLED (EQPT)

LOS-O (OTS)

SSM-RES (TRUNK)

CONTBUS-IO-A (EQPT)

LOS-P (OCH)

SSM-SDH-TN (BITS)

CONTBUS-IO-B (EQPT)

LOS-P (OMS)

SSM-SDH-TN (NE-SREF)

CPP-INCAPABLE (EQPT)

LOS-P (OTS)

SSM-SDH-TN (STMN)

CTNEQPT-MISMATCH (EQPT)

LOS-P (TRUNK)

SSM-SDH-TN (TRUNK)

CTNEQPT-PBPROT (EQPT)

LO-TXPOWER (2R)

SSM-SETS (BITS)

CTNEQPT-PBWORK (EQPT)

LO-TXPOWER (EQPT)

SSM-SETS (NE-SREF)

DATA-CRC (CE100T)

LO-TXPOWER (ESCON)

SSM-SETS (STMN)

DATA-CRC (ML1000)

LO-TXPOWER (FC)

SSM-SETS (TRUNK)

DATA-CRC (ML100T)

LO-TXPOWER (GE)

SSM-SMC (E1)

DATA-CRC (MLFX)

LO-TXPOWER (ISC)

SSM-SMC (TRUNK)

DATAFLT (NE)

LO-TXPOWER (PPM)

SSM-ST2 (E1)

DBOSYNC (NE)

LO-TXPOWER (STMN)

SSM-ST2 (TRUNK)

DCU-LOSS-FAIL (OTS)

LO-TXPOWER (TRUNK)

SSM-ST3 (E1)

DS3-MISM (DS3)

LPBKCRS (VCMON-HP)

SSM-ST3 (TRUNK)

DSP-COMM-FAIL (TRUNK)

LPBKCRS (VCTRM-HP)

SSM-ST3E (E1)

DSP-FAIL (TRUNK)

LPBKDS1FE-CMD (DS1)

SSM-ST3E (TRUNK)

DUP-IPADDR (NE)

LPBKDS3FEAC (DS3)

SSM-ST4 (DS1)

DUP-NODENAME (NE)

LPBKDS3FEAC-CMD (DS3)

SSM-ST4 (E1)

DUP-SHELF-ID (SHELF)

LPBKDS3FEAC-CMD (E3)

SSM-ST4 (STMN)

EHIBATVG (PWR)

LPBKE1FEAC (E3)

SSM-ST4 (TRUNK)

ELWBATVG (PWR)

LPBKE3FEAC (E3)

SSM-STU (BITS)

EOC (TRUNK)

LPBKFACILITY (CE1000)

SSM-STU (E1)

EOC-L (TRUNK)

LPBKFACILITY (CE100T)

SSM-STU (NE-SREF)

EQPT (AICI-AEP)

LPBKFACILITY (CEMR)

SSM-STU (STMN)

EQPT (AICI-AIE)

LPBKFACILITY (DS1)

SSM-STU (TRUNK)

EQPT (EQPT)

LPBKFACILITY (DS3)

SSM-TNC (NE-SREF)

EQPT (PPM)

LPBKFACILITY (E1)

SSM-TNC (STMN)

EQPT-DIAG (EQPT)

LPBKFACILITY (E3)

SSM-TNC (TRUNK)

EQPT-MISS (FAN)

LPBKFACILITY (E4)

SW-MISMATCH (EQPT)

ERROR-CONFIG (EQPT)

LPBKFACILITY (ESCON)

SWMTXMOD-PROT (EQPT)

ETH-LINKLOSS (NE)

LPBKFACILITY (FC)

SWMTXMOD-WORK (EQPT)

E-W-MISMATCH (STMN)

LPBKFACILITY (FCMR)

SWTOPRI (EXT-SREF)

EXCCOL (EQPT)

LPBKFACILITY (G1000)

SWTOPRI (NE-SREF)

EXERCISE-RING-FAIL (STMN)

LPBKFACILITY (GE)

SWTOSEC (EXT-SREF)

EXERCISE-SPAN-FAIL (STMN)

LPBKFACILITY (ISC)

SWTOSEC (NE-SREF)

EXT (ENVALRM)

LPBKFACILITY (MLMR)

SWTOTHIRD (EXT-SREF)

EXTRA-TRAF-PREEMPT (STMN)

LPBKFACILITY (STM1E)

SWTOTHIRD (NE-SREF)

FAILTOSW (2R)

LPBKFACILITY (STMN)

SYNC-FREQ (DS1)

FAILTOSW (EQPT)

LPBKFACILITY (TRUNK)

SYNC-FREQ (E1)

FAILTOSW (ESCON)

LPBKTERMINAL (CE1000)

SYNC-FREQ (STMN)

FAILTOSW (FC)

LPBKTERMINAL (CE100T)

SYNC-FREQ (TRUNK)

FAILTOSW (GE)

LPBKTERMINAL (CEMR)

SYNCLOSS (FC)

FAILTOSW (ISC)

LPBKTERMINAL (DS1)

SYNCLOSS (FCMR)

FAILTOSW (STMN)

LPBKTERMINAL (DS3)

SYNCLOSS (GE)

FAILTOSW (TRUNK)

LPBKTERMINAL (E1)

SYNCLOSS (ISC)

FAILTOSW-PATH (VCMON-HP)

LPBKTERMINAL (E3)

SYNCLOSS (TRUNK)

FAILTOSW-PATH (VCMON-LP)

LPBKTERMINAL (E4)

SYNCPRI (EXT-SREF)

FAILTOSWR (STMN)

LPBKTERMINAL (ESCON)

SYNCPRI (NE-SREF)

FAILTOSWS (STMN)

LPBKTERMINAL (FC)

SYNCSEC (EXT-SREF)

FAN (FAN)

LPBKTERMINAL (FCMR)

SYNCSEC (NE-SREF)

FAPS (FCMR)

LPBKTERMINAL (G1000)

SYNCTHIRD (EXT-SREF)

FAPS (TRUNK)

LPBKTERMINAL (GE)

SYNCTHIRD (NE-SREF)

FAPS-CONFIG-MISMATCH (EQPT)

LPBKTERMINAL (ISC)

SYSBOOT (NE)

FC-DE-NES (FC)

LPBKTERMINAL (MLMR)

TEMP-MISM (NE)

FC-DE-NES (FCMR)

LPBKTERMINAL (STM1E)

TIM (STM1E)

FC-DE-NES (TRUNK)

LPBKTERMINAL (STMN)

TIM (STMN)

FC-NO-CREDITS (FC)

LPBKTERMINAL (TRUNK)

TIM (TRUNK)

FC-NO-CREDITS (FCMR)

LP-DEG (VCMON-LP)

TIM-MON (STMN)

FC-NO-CREDITS (TRUNK)

LP-DEG (VCTRM-LP)

TIM-MON (TRUNK)

FDI (OCH)

LP-ENCAP-MISMATCH (VCTRM-LP)

TPTFAIL (CE1000)

FDI (OCH-TERM)

LP-EXC (VCMON-LP)

TPTFAIL (CE100T)

FE-AIS (E3)

LP-EXC (VCTRM-LP)

TPTFAIL (CEMR)

FEC-MISM (TRUNK)

LP-PLM (VCMON-LP)

TPTFAIL (FCMR)

FE-E1-MULTLOS (E3)

LP-PLM (VCTRM-LP)

TPTFAIL (G1000)

FE-E1-NSA (E3)

LP-RFI (VCMON-LP)

TPTFAIL (ML1000)

FE-E1-SA (E3)

LP-RFI (VCTRM-LP)

TPTFAIL (ML100T)

FE-E1-SNGLLOS (E3)

LP-TIM (VCMON-LP)

TPTFAIL (MLFX)

FE-E3-NSA (E3)

LP-TIM (VCTRM-LP)

TPTFAIL (MLMR)

FE-E3-SA (E3)

LP-UNEQ (VCMON-LP)

TRAIL-SIGNAL-FAIL (OCH)

FE-EQPT-NSA (E3)

LP-UNEQ (VCTRM-LP)

TRAIL-SIGNAL-FAIL (TRUNK)

FE-FRCDWKSWBK-SPAN (STMN)

MAN-REQ (EQPT)

TRMT (DS1)

FE-FRCDWKSWPR-RING (STMN)

MAN-REQ (ML1000)

TRMT (E1)

FE-FRCDWKSWPR-SPAN (STMN)

MAN-REQ (ML100T)

TRMT-MISS (DS1)

FE-IDLE (E3)

MAN-REQ (MLFX)

TRMT-MISS (E1)

FE-LOCKOUTOFPR-SPAN (STMN)

MAN-REQ (MLMR)

TU-AIS (VCMON-LP)

FE-LOF (E3)

MAN-REQ (VCMON-HP)

TU-AIS (VCTRM-LP)

FE-LOS (E3)

MAN-REQ (VCMON-LP)

TU-LOP (VCMON-LP)

FE-MANWKSWBK-SPAN (STMN)

MANRESET (EQPT)

TU-LOP (VCTRM-LP)

FE-MANWKSWPR-RING (STMN)

MANSWTOINT (NE-SREF)

TX-AIS (DS1)

FE-MANWKSWPR-SPAN (STMN)

MANSWTOPRI (EXT-SREF)

TX-AIS (DS3)

FEPRLF (STMN)

MANSWTOPRI (NE-SREF)

TX-AIS (E1)

FE-SDPRLF (STMN)

MANSWTOSEC (EXT-SREF)

TX-AIS (E3)

FE-SD-SPAN (STMN)

MANSWTOSEC (NE-SREF)

TX-IDLE (DS1)

FE-SF-RING (STMN)

MANSWTOTHIRD (EXT-SREF)

TX-LOF (DS1)

FE-SF-SPAN (STMN)

MANSWTOTHIRD (NE-SREF)

TX-LOF (E1)

FIBERTEMP-DEG (AOTS)

MANUAL-REQ-RING (STMN)

TX-RAI (DS1)

FORCED-REQ (EQPT)

MANUAL-REQ-SPAN (2R)

TX-RAI (E1)

FORCED-REQ (ML1000)

MANUAL-REQ-SPAN (ESCON)

TX-RAI (E3)

FORCED-REQ (ML100T)

MANUAL-REQ-SPAN (FC)

UNC-WORD (TRUNK)

FORCED-REQ (MLFX)

MANUAL-REQ-SPAN (GE)

UNQUAL-PPM (PPM)

FORCED-REQ (MLMR)

MANUAL-REQ-SPAN (ISC)

UT-COMM-FAIL (TRUNK)

FORCED-REQ (VCMON-HP)

MANUAL-REQ-SPAN (STMN)

UT-FAIL (TRUNK)

FORCED-REQ (VCMON-LP)

MANUAL-REQ-SPAN (TRUNK)

VCG-DEG (VCG)

FORCED-REQ-RING (STMN)

MAX-STATIONS (RPRIF)

VCG-DOWN (VCG)

FORCED-REQ-SPAN (2R)

MEA (BIC)

VOA-HDEG (AOTS)

FORCED-REQ-SPAN (ESCON)

MEA (EQPT)

VOA-HDEG (OCH)

FORCED-REQ-SPAN (FC)

MEA (FAN)

VOA-HDEG (OMS)

FORCED-REQ-SPAN (GE)

MEA (PPM)

VOA-HDEG (OTS)

FORCED-REQ-SPAN (ISC)

MEA (SHELF)

VOA-HFAIL (AOTS)

FORCED-REQ-SPAN (STMN)

MEM-GONE (EQPT)

VOA-HFAIL (OCH)

FORCED-REQ-SPAN (TRUNK)

MEM-LOW (EQPT)

VOA-HFAIL (OMS)

FP-LINK-LOSS (EQPT)

MFGMEM (AICI-AEP)

VOA-HFAIL (OTS)

FRCDSWTOINT (NE-SREF)

MFGMEM (AICI-AIE)

VOA-LDEG (AOTS)

FRCDSWTOPRI (EXT-SREF)

MFGMEM (BPLANE)

VOA-LDEG (OCH)

FRCDSWTOPRI (NE-SREF)

MFGMEM (FAN)

VOA-LDEG (OMS)

FRCDSWTOSEC (EXT-SREF)

MFGMEM (PPM)

VOA-LDEG (OTS)

FRCDSWTOSEC (NE-SREF)

MS-AIS (STM1E)

VOA-LFAIL (AOTS)

FRCDSWTOTHIRD (EXT-SREF)

MS-AIS (STMN)

VOA-LFAIL (OCH)

FRCDSWTOTHIRD (NE-SREF)

MS-DEG (E1)

VOA-LFAIL (OMS)

FRNGSYNC (NE-SREF)

MS-DEG (E3)

VOA-LFAIL (OTS)

FSTSYNC (NE-SREF)

MS-DEG (E4)

VOLT-MISM (PWR)

FTA-MISMATCH (EQPT)

MS-DEG (STM1E)

WKSWPR (2R)

FULLPASSTHR-BI (STMN)

MS-DEG (STMN)

WKSWPR (EQPT)

GAIN-HDEG (AOTS)

MS-EOC (STMN)

WKSWPR (ESCON)

GAIN-HFAIL (AOTS)

MS-EXC (E1)

WKSWPR (FC)

GAIN-LDEG (AOTS)

MS-EXC (E3)

WKSWPR (GE)

GAIN-LFAIL (AOTS)

MS-EXC (E4)

WKSWPR (ISC)

GCC-EOC (TRUNK)

MS-EXC (STM1E)

WKSWPR (STMN)

GE-OOSYNC (FC)

MS-EXC (STMN)

WKSWPR (VCMON-HP)

GE-OOSYNC (GE)

MS-RFI (STM1E)

WKSWPR (VCMON-LP)

GE-OOSYNC (ISC)

MS-RFI (STMN)

WTR (2R)

GE-OOSYNC (TRUNK)

MSSP-OOSYNC (STMN)

WTR (EQPT)

GFP-CSF (CE1000)

MSSP-SW-VER-MISM (STMN)

WTR (ESCON)

GFP-CSF (CE100T)

MS-SQUELCH-HP (STMN)

WTR (FC)

GFP-CSF (CEMR)

MS-SQUELCH-LP (STMN)

WTR (GE)

GFP-CSF (FCMR)

MT-OCHNC (OTS)

WTR (ISC)

GFP-CSF (GFP-FAC)

NO-CONFIG (EQPT)

WTR (ML1000)

GFP-CSF (ML1000)

NON-CISCO-PPM (PPM)

WTR (ML100T)

GFP-CSF (ML100T)

OCHNC-INC (OCHNC-CONN)

WTR (MLFX)

GFP-CSF (MLFX)

OCHTERM-INC (OCH-TERM)

WTR (MLMR)

GFP-CSF (MLMR)

ODUK-1-AIS-PM (TRUNK)

WTR (STMN)

GFP-DE-MISMATCH (FCMR)

ODUK-2-AIS-PM (TRUNK)

WTR (TRUNK)

GFP-DE-MISMATCH (GFP-FAC)

ODUK-3-AIS-PM (TRUNK)

WTR (VCMON-HP)

GFP-EX-MISMATCH (CE1000)

ODUK-4-AIS-PM (TRUNK)

WTR (VCMON-LP)

GFP-EX-MISMATCH (FCMR)

ODUK-AIS-PM (TRUNK)

WVL-MISMATCH (TRUNK)

GFP-EX-MISMATCH (GFP-FAC)

ODUK-BDI-PM (TRUNK)

GFP-LFD (CE1000)

ODUK-LCK-PM (TRUNK)


2.3  Alarm Logical Objects

The CTC alarm profile list organizes all alarms and conditions according to the logical objects they are raised against. These logical objects represent physical objects such as cards, logical objects such as circuits, or transport and signal monitoring entities such as the SDH or ITU-T G.709 optical overhead bits. One alarm can appear in multiple entries. It can be raised against multiple objects. For example, the loss of signal (LOS) alarm can be raised against the optical signal (STM-N) or the optical transport layer overhead (OTN) as well as other objects. Therefore, both STM-N: LOS and OTN: LOS appear in the list (as well as the other objects).

Alarm profile list objects are defined in Table 2-7.


Note Alarm logical object names can appear as abbreviated versions of standard terms used in the system and the documentation. For example, the "STMN" logical object refers to the STM-N signal. Logical object names or industry-standard terms are used within the entries as appropriate.


Table 2-7 Alarm Logical Object Type Definitions 

Object Type
Definition
2R

Reshape and retransmit (used for transponder [TXP] cards). For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

AICI-AEP

Alarm Interface Controller-International—Alarm expansion panel.

AICI-AIE

Alarm Interface Controller-International/Alarm Interface Extension. A combination term that refers to this platform's AIC-I card.

AIP

Alarm Interface Panel.

AOTS

Amplified optical transport section. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

BIC

Backplane interface connector.

BITS

Building integrated timing supply incoming references (BITS-1, BITS-2).

BPLANE

The backplane.

CE1000

CE-1000-4 card.

CE100T

CE-100T-8 card.

CEMR

CE-MR-10 card.

CTRL

Control channel.

DS1

A DS-1 line on a DS-1 or DS-3 electrical card (DS1-14, DS3N-12E, DS3XM-6, DS3XM-12).

DS3

A DS-3 signal on a DS3i-N-12 card.

E1

E1-42 card.

E3

E3-12 card.

E4

Line type supported by the STM1E card.

E1000F

An E1000-2-G card.

E100T

An E100T-G card.

ENVALRM

An environmental alarm port.

EQPT

A card, its physical objects, and logical objects as they are located in any of the
eight noncommon card slots. The EQPT object is used for alarms that refer to the
card itself and all other objects on the card including ports, lines, STM, and VC.

ESCON

Enterprise System Connection fiber optic technology, referring to the following TXP cards: TXP_MR_2.5G, TXPP_MR_2.5G. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

EXT-SREF

BITS outgoing references (SYNC-BITS1, SYNC-BITS2).

FAN

Fan-tray assembly.

FC

Fibre Channel data transfer architecture, referring to the following muxponder (MXP) or TXP cards: MXP_MR_2.5G, MXPP_MR_2.5G, TXP_MR_2.5G, TXPP_MR_2.5G, TXP_MR_10E.  For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

FCMR

An FC_MR-4 Fibre Channel card. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

FUDC

SDH F1 byte user data channel for ONS 15454 SDH ML-Series Ethernet cards.

G1000

The ONS 15454 SDH G-Series card.

GE

Gigabit Ethernet, referring to the following MXP or TXP cards: MXP_MR_2.5G, MXPP_MR_2.5G, TXP_MR_2.5G, TXPP_MR_2.5G, TXP_MR_10E, TXP_MR_10G. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

GFP-FAC

Generic framing procedure facility port, referring to all MXP and TXP cards. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

ISC

Inter-service channel referring to MXP and TXP cards. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

ML1000

The ONS 15454 SDH ML1000-2 card.

ML100T

The ONS 15454 SDH ML100T-2 or ML100T-8 card.

MLFX

An MLFX Ethernet card.

MLMR

ML-MR-10 Ethernet card.

MSUDC

Multiplex section user data channel.

NE

The entire network element.

NE-SREF

The timing status of the NE.

OCH

The optical channel, referring to dense wavelength division multiplexing (DWDM) cards. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

OCH-TERM

The optical channel termination node, referring to DWDM cards. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

OCHNC-CONN

The optical channel network connection, referring to DWDM cards. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

OMS

Optical multiplex section. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

OSC-RING

Optical service channel ring. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

OTS

Optical transport section. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

PWR

Power equipment.

PPM

Pluggable port module (PPM), referring to all MXP and TXP cards, MRC-12 cards, and OC192-XFP/STM64-XFP cards. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

RPRIF

Resilient Packet Ring (RPR) Interface.

SHELF

The shelf assembly. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

STM1E

Synchronous transfer mode 1 (speed) electrical interface

STMN

An STM-N line on an STM-N card.

TLINK

Traffic engineering (TE) link correlation.

VCTRM-HP

VT alarm detection at termination (downstream from the cross-connect).

TRUNK

The optical or DWDM card carrying the high-speed signal; referring to MXP, TXP, or ML-Series cards. For more information about most of the alarms on this object, refer to the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

UCP-CKT

Unified control plane circuit.

UCP-IPCC

Unified control plane IP control channel.

UCP-NBR

Unified control plane neighbor.

VCG

ONS 15454 SDH virtual concatenation group of virtual tributaries (VT).

VCMON-HP

High-order path virtual concatenation monitoring.

VCMON-LP

VT1 alarm detection at the monitor point (upstream from the cross-connect).

VCTRM-HP

High-order path concatenation termination monitoring.

VCTRM-LP

VC alarm detection at termination (downstream from the cross-connect).


2.4  Alarm List by Logical Object Type

Table 2-8 lists all ONS 15454 SDH Release 8.0 alarms and logical objects as they are given in the system alarm profile. The list entries are organized by logical object name and then by alarm or condition name. Where appropriate, the alarm entries also contain troubleshooting procedures.


Note In a mixed network containing different types of nodes (such as ONS 15310-CL, ONS 15454 SDH, and ONS 15600), the initially displayed alarm list in the Provisioning > Alarm Profiles > Alarm Profile Editor tab lists all conditions that are applicable to all nodes in the network. However, when you load the default severity profile from a node, only applicable alarms will display severity levels. Nonapplicable alarms can display "use default" or "unset."



Note In some cases this list does not follow alphabetical order, but it does reflect the order shown in CTC.


Table 2-8 Alarm List by Logical Object Type in Alarm Profile 

2R: ALS (NA)

FC: HI-TXPOWER (MN)

RPRIF: RPR-PASSTHR (NA)

2R: AS-CMD (NA)

FC: LO-RXPOWER (MN)

RPRIF: RPR-PEER-MISS (MJ)

2R: AS-MT (NA)

FC: LO-TXPOWER (MN)

RPRIF: RPR-PROT-ACTIVE (NA)

2R: FAILTOSW (NA)

FC: LOCKOUT-REQ (NA)

RPRIF: RPR-PROT-CONFIG-MISM (MJ)

2R: FORCED-REQ-SPAN (NA)

FC: LPBKFACILITY (NA)

RPRIF: RPR-RI-FAIL (MJ)

2R: HI-LASERBIAS (MN)

FC: LPBKTERMINAL (NA)

SHELF: APC-DISABLED (NA)

2R: HI-RXPOWER (MN)

FC: MANUAL-REQ-SPAN (NA)

SHELF: AS-CMD (NA)

2R: HI-TXPOWER (MN)

FC: OUT-OF-SYNC (MJ)

SHELF: AS-MT (NA)

2R: LO-RXPOWER (MN)

FC: SIGLOSS (MJ)

SHELF: DUP-SHELF-ID (MJ)

2R: LO-TXPOWER (MN)

FC: SQUELCHED (NA)

SHELF: MEA (MJ)

2R: LOCKOUT-REQ (NA)

FC: SYNCLOSS (MJ)

SHELF: SHELF-COMM-FAIL (MJ)

2R: LOS (CR)

FC: WKSWPR (NA)

STM1E: AS-CMD (NA)

2R: MANUAL-REQ-SPAN (NA)

FC: WTR (NA)

STM1E: AS-MT (NA)

2R: SQUELCHED (NA)

FCMR: AS-CMD (NA)

STM1E: LOF (CR)

2R: WKSWPR (NA)

FCMR: AS-MT (NA)

STM1E: LOS (CR)

2R: WTR (NA)

FCMR: FAPS (NA)

STM1E: LPBKFACILITY (NA)

AICI-AEP: EQPT (CR)

FCMR: FC-DE-NES (MJ)

STM1E: LPBKTERMINAL (NA)

AICI-AEP: MFGMEM (CR)

FCMR: FC-NO-CREDITS (MJ)

STM1E: MS-AIS (NR)

AICI-AIE: EQPT (CR)

FCMR: GFP-CSF (MJ)

STM1E: MS-DEG (NA)

AICI-AIE: MFGMEM (CR)

FCMR: GFP-DE-MISMATCH (MJ)

STM1E: MS-EXC (NA)

AOTS: ALS (NA)

FCMR: GFP-EX-MISMATCH (MJ)

STM1E: MS-RFI (NR)

AOTS: AMPLI-INIT (NA)

FCMR: GFP-LFD (MJ)

STM1E: SD (NA)

AOTS: APC-DISABLED (NA)

FCMR: GFP-NO-BUFFERS (MJ)

STM1E: TIM (MJ)

AOTS: APC-CORR-SKIPPED (MN)

FCMR: GFP-UP-MISMATCH (MJ)

STMN: ALS (NA)

AOTS: APC-OUT-OF-RANGE (MN)

FCMR: LPBKFACILITY (NA)

STMN: APS-INV-PRIM (MN)

AOTS: APC-WRONG-GAIN (NA)

FCMR: LPBKTERMINAL (NA)

STMN: APS-PRIM-FAC (NA)

AOTS: AS-CMD (NA)

FCMR: PORT-MISMATCH (NA)

STMN: APS-PRIM-SEC-MISM (MN)

AOTS: AS-MT (NA)

FCMR: SIGLOSS (MJ)

STMN: APSB (MN)

AOTS: CASETEMP-DEG (MN)

FCMR: SYNCLOSS (MJ)

STMN: APSC-IMP (MN)

AOTS: FIBERTEMP-DEG (MN)

FCMR: TPTFAIL (MJ)

STMN: APSCDFLTK (MN)

AOTS: GAIN-HDEG (MN)

FUDC: AIS (NR)

STMN: APSCINCON (MN)

AOTS: GAIN-HFAIL (CR)

FUDC: LOS (MN)

STMN: APSCM (MJ)

AOTS: GAIN-LDEG (MN)

G1000: AS-CMD (NA)

STMN: APSCNMIS (MJ)

AOTS: GAIN-LFAIL (CR)

G1000: AS-MT (NA)

STMN: APSIMP (MN)

AOTS: LASER-APR (NA)

G1000: CARLOSS (MJ)

STMN: AS-CMD (NA)

AOTS: LASERBIAS-DEG (MN)

G1000: LPBKFACILITY (NA)

STMN: AS-MT (NA)

AOTS: LASERBIAS-FAIL (MJ)

G1000: LPBKTERMINAL (NA)

STMN: AUTOLSROFF (CR)

AOTS: LASERTEMP-DEG (MN)

G1000: TPTFAIL (MJ)

STMN: E-W-MISMATCH (MJ)

AOTS: OPWR-HDEG (MN)

GE: ALS (NA)

STMN: EXERCISE-RING-FAIL (NA)

AOTS: OPWR-HFAIL (CR)

GE: AS-CMD (NA)

STMN: EXERCISE-SPAN-FAIL (NA)

AOTS: OPWR-LDEG (MN)

GE: AS-MT (NA)

STMN: EXTRA-TRAF-PREEMPT (MJ)

AOTS: OPWR-LFAIL (CR)

GE: CARLOSS (MJ)

STMN: FAILTOSW (NA)

AOTS: OSRION (NA)

GE: FAILTOSW (NA)

STMN: FAILTOSWR (NA)

AOTS: PARAM-MISM (NA)

GE: FORCED-REQ-SPAN (NA)

STMN: FAILTOSWS (NA)

AOTS: VOA-HDEG (MN)

GE: GE-OOSYNC (CR)

STMN: FE-FRCDWKSWBK-SPAN (NA)

AOTS: VOA-HFAIL (CR)

GE: HI-LASERBIAS (MN)

STMN: FE-FRCDWKSWPR-RING (NA)

AOTS: VOA-LDEG (MN)

GE: HI-RXPOWER (MN)

STMN: FE-FRCDWKSWPR-SPAN (NA)

AOTS: VOA-LFAIL (CR)

GE: HI-TXPOWER (MN)

STMN: FE-LOCKOUTOFPR-SPAN (NA)

BIC: MEA (CR)

GE: LMP-FAIL (MN)

STMN: FE-MANWKSWBK-SPAN (NA)

BITS: AIS (NR)

GE: LMP-SD (MN)

STMN: FE-MANWKSWPR-RING (NA)

BITS: LOF (MN)

GE: LMP-SF (MN)

STMN: FE-MANWKSWPR-SPAN (NA)

BITS: LOS (MN)

GE: LMP-UNALLOC (NA)

STMN: FE-SD-SPAN (NA)

BITS: SSM-DUS (NA)

GE: LO-RXPOWER (MN)

STMN: FE-SDPRLF (MN)

BITS: SSM-FAIL (MN)

GE: LO-TXPOWER (MN)

STMN: FE-SF-RING (NA)

BITS: SSM-LNC (NA)

GE: LOCKOUT-REQ (NA)

STMN: FE-SF-SPAN (NA)

BITS: SSM-OFF (NA)

GE: LPBKFACILITY (NA)

STMN: FEPRLF (MN)

BITS: SSM-PRC (NA)

GE: LPBKTERMINAL (NA)

STMN: FORCED-REQ-RING (NA)

BITS: SSM-SDH-TN (NA)

GE: MANUAL-REQ-SPAN (NA)

STMN: FORCED-REQ-SPAN (NA)

BITS: SSM-SETS (NA)

GE: OUT-OF-SYNC (MJ)

STMN: FULLPASSTHR-BI (NA)

BITS: SSM-STU (NA)

GE: SIGLOSS (MJ)

STMN: HELLO (MN)

BPLANE: AS-CMD (NA)

GE: SQUELCHED (NA)

STMN: HI-LASERBIAS (MN)

BPLANE: INVMACADR (MJ)

GE: SYNCLOSS (MJ)

STMN: HI-LASERTEMP (MN)

BPLANE: MFGMEM (CR)

GE: WKSWPR (NA)

STMN: HI-RXPOWER (MN)

CE1000: AS-CMD (NA)

GE: WTR (NA)

STMN: HI-TXPOWER (MN)

CE1000: AS-MT (NA)

GFP-FAC: AS-CMD (NA)

STMN: ISIS-ADJ-FAIL (MN)

CE1000: CARLOSS (MJ)

GFP-FAC: AS-MT (NA)

STMN: KB-PASSTHR (NA)

CE1000: GFP-CSF (MJ)

GFP-FAC: GFP-CSF (MJ)

STMN: KBYTE-APS-CHAN-FAIL (MN)

CE1000: GFP-EX-MISMATCH (MJ)

GFP-FAC: GFP-DE-MISMATCH (MJ)

STMN: LKOUTPR-S (NA)

CE1000: GFP-LFD (MJ)

GFP-FAC: GFP-EX-MISMATCH (MJ)

STMN: LMP-FAIL (MN)

CE1000: GFP-UP-MISMATCH (MJ)

GFP-FAC: GFP-LFD (MJ)

STMN: LMP-SD (MN)

CE1000: LPBKFACILITY (NA)

GFP-FAC: GFP-NO-BUFFERS (MJ)

STMN: LMP-SF (MN)

CE1000: LPBKTERMINAL (NA)

GFP-FAC: GFP-UP-MISMATCH (MJ)

STMN: LMP-UNALLOC (NA)

CE1000: TPTFAIL (MJ)

ISC: ALS (NA)

STMN: LO-LASERBIAS (MN)

CE100T: AS-CMD (NA)

ISC: AS-CMD (NA)

STMN: LO-LASERTEMP (MN)

CE100T: AS-MT (NA)

ISC: AS-MT (NA)

STMN: LO-RXPOWER (MN)

CE100T: CARLOSS (MJ)

ISC: CARLOSS (MJ)

STMN: LO-TXPOWER (MN)

CE100T: DATA-CRC (MJ)

ISC: FAILTOSW (NA)

STMN: LOCKOUT-REQ (NA)

CE100T: GFP-CSF (MJ)

ISC: FORCED-REQ-SPAN (NA)

STMN: LOF (CR)

CE100T: GFP-LFD (MJ)

ISC: GE-OOSYNC (CR)

STMN: LOS (CR)

CE100T: GFP-UP-MISMATCH (MJ)

ISC: HI-LASERBIAS (MN)

STMN: LPBKFACILITY (NA)

CE100T: LPBKFACILITY (NA)

ISC: HI-RXPOWER (MN)

STMN: LPBKTERMINAL (NA)

CE100T: LPBKTERMINAL (NA)

ISC: HI-TXPOWER (MN)

STMN: MANUAL-REQ-RING (NA)

CE100T: TPTFAIL (MJ)

ISC: LO-RXPOWER (MN)

STMN: MANUAL-REQ-SPAN (NA)

CEMR: AS-CMD (NA)

ISC: LO-TXPOWER (MN)

STMN: MS-AIS (NR)

CEMR: AS-MT (NA)

ISC: LOCKOUT-REQ (NA)

STMN: MS-DEG (NA)

CEMR: CARLOSS (MJ)

ISC: LOS (CR)

STMN: MS-EOC (MN)

CEMR: GFP-CSF (MJ)

ISC: LPBKFACILITY (NA)

STMN: MS-EXC (NA)

CEMR: GFP-LFD (MJ)

ISC: LPBKTERMINAL (NA)

STMN: MS-RFI (NR)

CEMR: GFP-UP-MISMATCH (MJ)

ISC: MANUAL-REQ-SPAN (NA)

STMN: MS-SQUELCH-HP (NA)

CEMR: LPBKFACILITY (NA)

ISC: OUT-OF-SYNC (NA)

STMN: MS-SQUELCH-LP (NA)

CEMR: LPBKTERMINAL (NA)

ISC: SIGLOSS (MJ)

STMN: MSSP-OOSYNC (MJ)

CEMR: PORT-MISMATCH (MJ)

ISC: SQUELCHED (NA)

STMN: MSSP-SW-VER-MISM (MN)

CEMR: TPTFAIL (MJ)

ISC: SYNCLOSS (MJ)

STMN: PRC-DUPID (MJ)

CTRL: LMP-FAIL (MN)

ISC: WKSWPR (NA)

STMN: RING-ID-MIS (MJ)

DS1: AIS (NR)

ISC: WTR (NA)

STMN: RING-MISMATCH (MJ)

DS1: AS-CMD (NA)

ML1000: AS-CMD (NA)

STMN: RING-SW-EAST (NA)

DS1: AS-MT (NA)

ML1000: AS-MT (NA)

STMN: RING-SW-WEST (NA)

DS1: IDLE (NA)

ML1000: AUTONEG-RFI (MJ)

STMN: RS-EOC (MN)

DS1: LOF (MJ)

ML1000: CARLOSS (MJ)

STMN: RS-TIM (CR)

DS1: LOS (MJ)

ML1000: DATA-CRC (MJ)

STMN: SPAN-SW-EAST (NA)

DS1: LPBKDS1FE-CMD (NA)

ML1000: FORCED-REQ (NA)

STMN: SPAN-SW-WEST (NA)

DS1: LPBKFACILITY (NA)

ML1000: GFP-CSF (MJ)

STMN: SQUELCH (NA)

DS1: LPBKTERMINAL (NA)

ML1000: GFP-LFD (MJ)

STMN: SQUELCHED (NA)

DS1: RAI (NA)

ML1000: GFP-UP-MISMATCH (MJ)

STMN: SSM-DUS (NA)

DS1: RCVR-MISS (MJ)

ML1000: LINK-KEEPALIVE (CR)

STMN: SSM-FAIL (MN)

DS1: SD (NA)

ML1000: MAN-REQ (NA)

STMN: SSM-LNC (NA)

DS1: SF (NA)

ML1000: RPR-SD (NA)

STMN: SSM-OFF (NA)

DS1: SSM-DUS (NA)

ML1000: RPR-SF (NA)

STMN: SSM-PRC (NA)

DS1: SSM-OFF (NA)

ML1000: RPR-SPAN-MISMATCH (MJ)

STMN: SSM-SDH-TN (NA)

DS1: SSM-RES (NA)

ML1000: RPRW (NA)

STMN: SSM-SETS (NA)

DS1: SSM-ST4 (NA)

ML1000: TPTFAIL (MJ)

STMN: SSM-ST4 (NA)

DS1: SYNC-FREQ (NA)

ML1000: WTR (NA)

STMN: SSM-STU (NA)

DS1: TRMT (MJ)

ML100T: AS-CMD (NA)

STMN: SSM-TNC (NA)

DS1: TRMT-MISS (MJ)

ML100T: AS-MT (NA)

STMN: SYNC-FREQ (NA)

DS1: TX-AIS (NR)

ML100T: CARLOSS (MJ)

STMN: TIM (CR)

DS1: TX-IDLE (NA)

ML100T: DATA-CRC (MJ)

STMN: TIM-MON (MN)

DS1: TX-LOF (NR)

ML100T: FORCED-REQ (NA)

STMN: WKSWPR (NA)

DS1: TX-RAI (NA)

ML100T: GFP-CSF (MJ)

STMN: WTR (NA)

DS3: AIS (NR)

ML100T: GFP-LFD (MJ)

STSMON: PLM-P )CR)

DS3: AS-CMD (NA)

ML100T: GFP-UP-MISMATCH (MJ)

STSTRM: PLM-P (CR)

DS3: AS-MT (NA)

ML100T: LINK-KEEPALIVE (CR)

TLINK: LMP-FAIL (MN)

DS3: DS3-MISM (NA)

ML100T: MAN-REQ (NA)

TRUNK: AIS (NR)

DS3: INC-ISD (NA)

ML100T: RPR-SD (NA)

TRUNK: AIS-L (NR)

DS3: LOF (CR)

ML100T: RPR-SF (NA)

TRUNK: ALS (NA)

DS3: LOS (CR)

ML100T: RPR-SPAN-MISMATCH (MJ)

TRUNK: AS-CMD (NA)

DS3: LPBKDS3FEAC (NA)

ML100T: RPRW (NA)

TRUNK: AS-MT (NA)

DS3: LPBKDS3FEAC-CMD (NA)

ML100T: TPTFAIL (MJ)

TRUNK: CARLOSS (MJ)

DS3: LPBKFACILITY (NA)

ML100T: WTR (NA)

TRUNK: DSP-COMM-FAIL (MJ)

DS3: LPBKTERMINAL (NA)

MLFX: AS-CMD (NA)

TRUNK: DSP-FAIL (MJ)

DS3: RAI (NA)

MLFX: AS-MT (NA)

TRUNK: EOC (MN)

DS3: SD (NA)

MLFX: CARLOSS (MJ)

TRUNK: EOC-L (MN)

DS3: SF (NA)

MLFX: DATA-CRC (MJ)

TRUNK: FAILTOSW (NA)

DS3: TX-AIS (NR)

MLFX: FORCED-REQ (NA)

TRUNK: FAPS (NA)

E1000F: AS-CMD (NA)

MLFX: GFP-CSF (MJ)

TRUNK: FC-DE-NES (MJ)

E1000F: CARLOSS (MJ)

MLFX: GFP-LFD (MJ)

TRUNK: FC-NO-CREDITS (MJ)

E100T: AS-CMD (NA)

MLFX: GFP-UP-MISMATCH (MJ)

TRUNK: FEC-MISM (MJ)

E100T: CARLOSS (MJ)

MLFX: LINK-KEEPALIVE (CR)

TRUNK: FORCED-REQ-SPAN (NA)

E1: AIS (NR)

MLFX: MAN-REQ (NA)

TRUNK: GCC-EOC (MN)

E1: AS-CMD (NA)

MLFX: RPR-SD (NA)

TRUNK: GE-OOSYNC (CR)

E1: AS-MT (NA)

MLFX: RPR-SF (NA)

TRUNK: HELLO (MN)

E1: LOF (MJ)

MLFX: RPR-SPAN-MISMATCH (MJ)

TRUNK: HI-LASERBIAS (MN)

E1: LOS (MJ)

MLFX: RPRW (NA)

TRUNK: HI-RXPOWER (MN)

E1: LPBKFACILITY (NA)

MLFX: TPTFAIL (MJ)

TRUNK: HI-TXPOWER (MN)

E1: LPBKTERMINAL (NA)

MLFX: WTR (NA)

TRUNK: ILK-FAIL (CR)

E1: MS-DEG (NA)

MLMR: AS-CMD (NA)

TRUNK: ISIS-ADJ-FAIL (MN)

E1: MS-EXC (NA)

MLMR: AS-MT (NA)

TRUNK: LO-RXPOWER (MN)

E1: RAI (NA)

MLMR: CARLOSS (MJ)

TRUNK: LO-TXPOWER (MN)

E1: RCVR-MISS (MJ)

MLMR: FORCED-REQ (NA)

TRUNK: LOCKOUT-REQ (NA)

E1: SSM-DUS (NA)

MLMR: GFP-CSF (MJ)

TRUNK: LOF (CR)

E1: SSM-FAIL (MN)

MLMR: GFP-LFD (MJ)

TRUNK: LOM (CR)

E1: SSM-OFF (NA)

MLMR: GFP-UP-MISMATCH (MJ)

TRUNK: LOS (CR)

E1: SSM-PRS (NA)

MLMR: LINK-KEEPALIVE (CR)

TRUNK: LOS-P (CR)

E1: SSM-RES (NA)

MLMR: LPBKFACILITY (NA)

TRUNK: LPBKFACILITY (NA)

E1: SSM-SMC (NA)

MLMR: LPBKTERMINAL (NA)

TRUNK: LPBKTERMINAL (NA)

E1: SSM-ST2 (NA)

MLMR: MAN-REQ (NA)

TRUNK: MANUAL-REQ-SPAN (NA)

E1: SSM-ST3 (NA)

MLMR: PORT-MISMATCH (MJ)

TRUNK: ODUK-1-AIS-PM (NR)

E1: SSM-ST3E (NA)

MLMR: RPR-SD (NA)

TRUNK: ODUK-2-AIS-PM (NR)

E1: SSM-ST4 (NA)

MLMR: RPR-SF (NA)

TRUNK: ODUK-3-AIS-PM (NR)

E1: SSM-STU (NA)

MLMR: RPR-SPAN-MISMATCH (MJ)

TRUNK: ODUK-4-AIS-PM (NR)

E1: SYNC-FREQ (NA)

MLMR: TPTFAIL (MJ)

TRUNK: ODUK-AIS-PM (NR)

E1: TRMT (MJ)

MLMR: WTR (NA)

TRUNK: ODUK-BDI-PM (NR)

E1: TRMT-MISS (MJ)

MSUDC: AIS (NR)

TRUNK: ODUK-LCK-PM (NR)

E1: TX-AIS (NR)

MSUDC: LOS (MN)

TRUNK: ODUK-OCI-PM (NR)

E1: TX-LOF (NR)

NE-SREF: FRCDSWTOINT (NA)

TRUNK: ODUK-SD-PM (NA)

E1: TX-RAI (NA)

NE-SREF: FRCDSWTOPRI (NA)

TRUNK: ODUK-SF-PM (NA)

E3: AIS (NR)

NE-SREF: FRCDSWTOSEC (NA)

TRUNK: ODUK-TIM-PM (MJ)

E3: AS-CMD (NA)

NE-SREF: FRCDSWTOTHIRD (NA)

TRUNK: OTUK-AIS (NR)

E3: AS-MT (NA)

NE-SREF: FRNGSYNC (NA)

TRUNK: OTUK-BDI (NR)

E3: FE-AIS (NA)

NE-SREF: FSTSYNC (NA)

TRUNK: OTUK-IAE (MN)

E3: FE-E1-MULTLOS (NA)

NE-SREF: HLDOVRSYNC (NA)

TRUNK: OTUK-LOF (CR)

E3: FE-E1-NSA (NA)

NE-SREF: MANSWTOINT (NA)

TRUNK: OTUK-SD (NA)

E3: FE-E1-SA (NA)

NE-SREF: MANSWTOPRI (NA)

TRUNK: OTUK-SF (NA)

E3: FE-E1-SNGLLOS (NA)

NE-SREF: MANSWTOSEC (NA)

TRUNK: OTUK-TIM (CR)

E3: FE-E3-NSA (NA)

NE-SREF: MANSWTOTHIRD (NA)

TRUNK: OUT-OF-SYNC (MJ)

E3: FE-E3-SA (NA)

NE-SREF: SSM-LNC (NA)

TRUNK: PROV-MISMATCH (MJ)

E3: FE-EQPT-NSA (NA)

NE-SREF: SSM-PRC (NA)

TRUNK: PTIM (MJ)

E3: FE-IDLE (NA)

NE-SREF: SSM-SDH-TN (NA)

TRUNK: RFI (NR)

E3: FE-LOF (NA)

NE-SREF: SSM-SETS (NA)

TRUNK: RFI-L (NR)

E3: FE-LOS (NA)

NE-SREF: SSM-STU (NA)

TRUNK: SD (NA)

E3: INC-ISD (NA)

NE-SREF: SSM-TNC (NA)

TRUNK: SD-L (NA)

E3: LOS (CR)

NE-SREF: SWTOPRI (NA)

TRUNK: SF (NA)

E3: LPBKDS3FEAC-CMD (NA)

NE-SREF: SWTOSEC (NA)

TRUNK: SF-L (NA)

E3: LPBKE1FEAC (NA)

NE-SREF: SWTOTHIRD (NA)

TRUNK: SIGLOSS (MJ)

E3: LPBKE3FEAC (NA)

NE-SREF: SYNCPRI (MJ)

TRUNK: SQUELCHED (NA)

E3: LPBKFACILITY (NA)

NE-SREF: SYNCSEC (MN)

TRUNK: SSM-DUS (NA)

E3: LPBKTERMINAL (NA)

NE-SREF: SYNCTHIRD (MN)

TRUNK: SSM-FAIL (MN)

E3: MS-DEG (NA)

NE: APC-DISABLED (NA)

TRUNK: SSM-LNC (NA)

E3: MS-EXC (NA)

NE: APC-END (NA)

TRUNK: SSM-OFF (NA)

E3: TX-AIS (NR)

NE: AS-CMD (NA)

TRUNK: SSM-PRC (NA)

E3: TX-RAI (NA)

NE: AUD-LOG-LOSS (NA)

TRUNK: SSM-PRS (NA)

E4: AIS (NR)

NE: AUD-LOG-LOW (NA)

TRUNK: SSM-RES (NA)

E4: AS-CMD (NA)

NE: DATAFLT (MN)

TRUNK: SSM-SDH-TN (NA)

E4: AS-MT (NA)

NE: DBOSYNC (MJ)

TRUNK: SSM-SETS (NA)

E4: LOF (CR)

NE: DUP-IPADDR (MN)

TRUNK: SSM-SMC (NA)

E4: LOS (CR)

NE: DUP-NODENAME (MN)

TRUNK: SSM-ST2 (NA)

E4: LPBKFACILITY (NA)

NE: ETH-LINKLOSS (NA)

TRUNK: SSM-ST3 (NA)

E4: LPBKTERMINAL (NA)

NE: HITEMP (CR)

TRUNK: SSM-ST3E (NA)

E4: MS-DEG (NA)

NE: I-HITEMP (CR)

TRUNK: SSM-ST4 (NA)

E4: MS-EXC (NA)

NE: INTRUSION-PSWD (NA)

TRUNK: SSM-STU (NA)

ENVALRM: EXT (MN)

NE: LAN-POL-REV (NA)

TRUNK: SSM-TNC (NA)

EQPT: ALS-DISABLED (NA)

NE: SNTP-HOST (MN)

TRUNK: SYNC-FREQ (NA)

EQPT: APC-DISABLED (NA)

NE: SYSBOOT (MJ)

TRUNK: SYNCLOSS (MJ)

EQPT: AS-CMD (NA)

NE: TEMP-MISM (NA)

TRUNK: TIM (CR)

EQPT: AS-MT (NA)

OCH-TERM: FDI (NA)

TRUNK: TIM-MON (MN)

EQPT: AUTORESET (MN)

OCH-TERM: OCHTERM-INC (NA)

TRUNK: TRAIL-SIGNAL-FAIL (NA)

EQPT: BKUPMEMP (CR)

OCH-TERM: OPWR-HDEG (MN)

TRUNK: UNC-WORD (NA)

EQPT: CARLOSS (MJ)

OCH-TERM: OPWR-LDEG (MN)

TRUNK: UT-COMM-FAIL (MJ)

EQPT: CLDRESTART (NA)

OCH-TERM: OPWR-LFAIL (CR)

TRUNK: UT-FAIL (MJ)

EQPT: COMIOXC (CR)

OCH-TERM: PARAM-MISM (NA)

TRUNK: WTR (NA)

EQPT: COMM-FAIL (MN)

TRUNK: WVL-MISMATCH (MJ)

EQPT: CONTBUS-A-18 (MN)

VCG: LOA (CR)

EQPT: CONTBUS-B-18 (MN)

VCG: VCG-DEG (NA)

EQPT: CONTBUS-DISABLED (CR)

VCG: VCG-DOWN (NA)

EQPT: CONTBUS-IO-A (MN)

OCH: APC-CORR-SKIPPED (MN)

VCMON-HP: AU-AIS (NR)

EQPT: CONTBUS-IO-B (MN)

OCH: APC-DISABLED (NA)

VCMON-HP: AU-LOP (CR)

EQPT: CPP-INCAPABLE (NA)

OCH: APC-OUT-OF-RANGE (MN)

VCMON-HP: AUTOSW-AIS-SNCP (NR)

EQPT: CTNEQPT-MISMATCH (NA)

OCH: AS-CMD (NA)

VCMON-HP: AUTOSW-LOP-SNCP (NA)

EQPT: CTNEQPT-PBPROT (CR)

OCH: AS-MT (NA)

EQPT: CTNEQPT-PBWORK (CR)

OCH: FDI (NA)

VCMON-HP: AUTOSW-SDBER-SNCP (NA)

EQPT: EQPT (CR)

OCH: LOS-O (MN)

VCMON-HP: AUTOSW-SFBER-SNCP (NA)

EQPT: EQPT-DIAG (CR)

OCH: LOS-P (CR)

VCMON-HP: AUTOSW-UNEQ-SNCP (NA)

EQPT: ERROR-CONFIG (MN)

OCH: OPWR-HDEG (MN)

VCMON-HP: FAILTOSW-PATH (NA)

EQPT: EXCCOL (MN)

OCH: OPWR-HFAIL (CR)

VCMON-HP: FORCED-REQ (NA)

EQPT: FAILTOSW (NA)

OCH: OPWR-LDEG (MN)

VCMON-HP: HP-DEG (NA)

EQPT: FAPS-CONFIG-MISMATCH (MN)

OCH: OPWR-LFAIL (CR)

VCMON-HP: HP-EXC (NA)

EQPT: FORCED-REQ (NA)

OCH: PARAM-MISM (NA)

VCMON-HP: HP-PLM (CR)

EQPT: FP-LINK-LOSS (MN)

OCH: PORT-FAIL (CR)

VCMON-HP: HP-RFI (NR)

EQPT: FTA-MISMATCH (NA)

OCH: TRAIL-SIGNAL-FAIL (NA)

VCMON-HP: HP-TIM (MN)

EQPT: HI-LASERBIAS (MN)

OCH: VOA-HDEG (MN)

VCMON-HP: HP-UNEQ (CR)

EQPT: HI-LASERTEMP (MN)

OCH: VOA-HFAIL (CR)

VCMON-HP: LOCKOUT-REQ (NA)

EQPT: HI-TXPOWER (MN)

OCH: VOA-LDEG (MN)

VCMON-HP: LOM (CR)

EQPT: HITEMP (MN)

OCH: VOA-LFAIL (CR)

VCMON-HP: LPBKCRS (NA)

EQPT: IMPROPRMVL (CR)

OCHNC-CONN: OCHNC-INC (NA)

VCMON-HP: MAN-REQ (NA)

EQPT: INHSWPR (NA)

OMS: APC-CORR-SKIPPED (MN)

VCMON-HP: ROLL (NA)

EQPT: INHSWWKG (NA)

OMS: APC-DISABLED (NA)

VCMON-HP: ROLL-PEND (NA)

EQPT: IOSCFGCOPY (NA)

OMS: APC-OUT-OF-RANGE (MN)

VCMON-HP: WKSWPR (NA)

EQPT: LO-LASERBIAS (MN)

OMS: AS-CMD (NA)

VCMON-HP: WTR (NA)

EQPT: LO-LASERTEMP (MN)

OMS: AS-MT (NA)

VCMON-LP: AUTOSW-AIS-SNCP (NR)

EQPT: LO-TXPOWER (MN)

OMS: LOS-O (MN)

VCMON-LP: AUTOSW-LOP-SNCP (NA)

EQPT: LOCKOUT-REQ (NA)

OMS: LOS-P (CR)

EQPT: MAN-REQ (NA)

OMS: OPWR-HDEG (MN)

VCMON-LP: AUTOSW-SDBER-SNCP (NA)

EQPT: MANRESET (NA)

OMS: OPWR-HFAIL (CR)

VCMON-LP: AUTOSW-SFBER-SNCP (NA)

EQPT: MEA (CR)

OMS: OPWR-LDEG (MN)

VCMON-LP: AUTOSW-UNEQ-SNCP (NA)

EQPT: MEM-GONE (MJ)

OMS: OPWR-LFAIL (CR)

VCMON-LP: FAILTOSW-PATH (NA)

EQPT: MEM-LOW (MN)

OMS: PARAM-MISM (NA)

VCMON-LP: FORCED-REQ (NA)

EQPT: NO-CONFIG (NA)

OMS: PMI (NA)

VCMON-LP: LOCKOUT-REQ (NA)

EQPT: PEER-NORESPONSE (MJ)

OMS: VOA-HDEG (MN)

VCMON-LP: LP-DEG (NA)

EQPT: PROTNA (MN)

OMS: VOA-HFAIL (CR)

VCMON-LP: LP-EXC (NA)

EQPT: PWR-FAIL-A (MN)

OMS: VOA-LDEG (MN)

VCMON-LP: LP-PLM (MJ)

EQPT: PWR-FAIL-B (MN)

OMS: VOA-LFAIL (CR)

VCMON-LP: LP-RFI (NR)

EQPT: PWR-FAIL-RET-A (MN)

OSC-RING: RING-ID-MIS (MJ)

VCMON-LP: LP-TIM (MJ)

EQPT: PWR-FAIL-RET-B (MN)

OTS: APC-CORR-SKIPPED (MN)

VCMON-LP: LP-UNEQ (MJ)

EQPT: RUNCFG-SAVENEED (NA)

OTS: APC-DISABLED (NA)

VCMON-LP: MAN-REQ (NA)

EQPT: SFTWDOWN (MN)

OTS: APC-OUT-OF-RANGE (MN)

VCMON-LP: ROLL (NA)

EQPT: SW-MISMATCH (NA)

OTS: AS-CMD (NA)

VCMON-LP: ROLL-PEND (NA)

EQPT: SWMTXMOD-PROT (CR)

OTS: AS-MT (NA)

VCMON-LP: TU-AIS (NR)

EQPT: SWMTXMOD-WORK (CR)

OTS: AWG-DEG (MN)

VCMON-LP: TU-LOP (MJ)

EQPT: WKSWPR (NA)

OTS: AWG-FAIL (CR)

VCMON-LP: WKSWPR (NA)

EQPT: WTR (NA)

OTS: AWG-OVERTEMP (CR)

VCMON-LP: WTR (NA)

ESCON: ALS (NA)

OTS: AWG-WARM-UP (NA)

VCTRM-HP: AS-MT-OOG (NA)

ESCON: AS-CMD (NA)

OTS: DCU-LOSS-FAIL (MN)

VCTRM-HP: AU-AIS (NR)

ESCON: AS-MT (NA)

OTS: LASERBIAS-DEG (MN)

VCTRM-HP: AU-LOF (CR)

ESCON: FAILTOSW (NA)

OTS: LOS (CR)

VCTRM-HP: AU-LOP (CR)

ESCON: FORCED-REQ-SPAN (NA)

OTS: LOS-O (MN)

VCTRM-HP: HP-DEG (NA)

ESCON: HI-LASERBIAS (MN)

OTS: LOS-P (CR)

VCTRM-HP: HP-ENCAP-MISMATCH (CR)

ESCON: HI-RXPOWER (MN)

OTS: MT-OCHNC (NA)

VCTRM-HP: HP-EXC (NA)

ESCON: HI-TXPOWER (MN)

OTS: OPWR-HDEG (MN)

VCTRM-HP: HP-PLM (CR)

ESCON: LO-RXPOWER (MN)

OTS: OPWR-HFAIL (CR)

VCTRM-HP: HP-RFI (NR)

ESCON: LO-TXPOWER (MN)

OTS: OPWR-LDEG (MN)

VCTRM-HP: HP-TIM (CR)

ESCON: LOCKOUT-REQ (NA)

OTS: OPWR-LFAIL (CR)

VCTRM-HP: HP-UNEQ (CR)

ESCON: LOS (CR)

OTS: OSRION (NA)

VCTRM-HP: LCAS-CRC (NA)

ESCON: LPBKFACILITY (NA)

OTS: PARAM-MISM (NA)

VCTRM-HP: LCAS-RX-DNU (NA)

ESCON: LPBKTERMINAL (NA)

OTS: PMI (NA)

VCTRM-HP: LCAS-RX-FAIL (NA)

ESCON: MANUAL-REQ-SPAN (NA)

OTS: SH-IL-VAR-DEG-HIGH (MN)

VCTRM-HP: LCAS-RX-GRP-ERR (NA)

ESCON: SIGLOSS (MJ)

OTS: SH-IL-VAR-DEG-LOW (MN)

VCTRM-HP: LCAS-TX-ADD (NA)

ESCON: SQUELCHED (NA)

OTS: SHUTTER-OPEN (NA)

VCTRM-HP: LCAS-TX-DNU (NA)

ESCON: WKSWPR (NA)

OTS: SPAN-NOT-MEASURED (NA)

VCTRM-HP: LOM (MJ)

ESCON: WTR (NA)

OTS: SPANLEN-OUT-OF-RANGE (MN)

VCTRM-HP: LPBKCRS (NA)

EXT-SREF: FRCDSWTOPRI (NA)

OTS: VOA-HDEG (MN)

VCTRM-HP: OOU-TPT (NA)

EXT-SREF: FRCDSWTOSEC (NA)

OTS: VOA-HFAIL (CR)

VCTRM-HP: ROLL (NA)

EXT-SREF: FRCDSWTOTHIRD (NA)

OTS: VOA-LDEG (MN)

VCTRM-HP: ROLL-PEND (NR)

EXT-SREF: MANSWTOPRI (NA)

OTS: VOA-LFAIL (CR)

VCTRM-HP: SQM (CR)

EXT-SREF: MANSWTOSEC (NA)

PPM: AS-CMD (NA)

VCTRM-LP: AS-MT-OOG (NA)

EXT-SREF: MANSWTOTHIRD (NA)

PPM: AS-MT (NA)

VCTRM-LP: LCAS-CRC (NA)

EXT-SREF: SWTOPRI (NA)

PPM: EQPT (CR)

VCTRM-LP: LCAS-RX-DNU (NA)

EXT-SREF: SWTOSEC (NA)

PPM: HI-LASERBIAS (MN)

VCTRM-LP: LCAS-RX-FAIL (NA)

EXT-SREF: SWTOTHIRD (NA)

PPM: HI-LASERTEMP (MN)

VCTRM-LP: LCAS-RX-GRP-ERR (NA)

EXT-SREF: SYNCPRI (MN)

PPM: HI-TXPOWER (MN)

VCTRM-LP: LCAS-TX-ADD (NA)

EXT-SREF: SYNCSEC (MN)

PPM: IMPROPRMVL (CR)

VCTRM-LP: LCAS-TX-DNU (NA)

EXT-SREF: SYNCTHIRD (MN)

PPM: LO-LASERBIAS (MN)

VCTRM-LP: LOM (MJ)

FAN: EQPT-MISS (CR)

PPM: LO-LASERTEMP (MN)

VCTRM-LP: LP-DEG (NA)

FAN: FAN (CR)

PPM: LO-TXPOWER (MN)

VCTRM-LP: LP-ENCAP-MISMATCH (CR)

FAN: MEA (CR)

PPM: MEA (CR)

VCTRM-LP: LP-EXC (NA)

FAN: MFGMEM (CR)

PPM: MFGMEM (CR)

VCTRM-LP: LP-PLM (MJ)

FC: ALS (NA)

PPM: NON-CISCO-PPM (MN)

VCTRM-LP: LP-RFI (NR)

FC: AS-CMD (NA)

PPM: PROV-MISMATCH (MN)

VCTRM-LP: LP-TIM (MJ)

FC: AS-MT (NA)

PPM: UNQUAL-PPM (MN)

VCTRM-LP: LP-UNEQ (MJ)

FC: CARLOSS (MJ)

PWR: AS-CMD (NA)

VCTRM-LP: OOU-TPT (NA)

FC: FAILTOSW (NA)

PWR: BAT-FAIL (MJ)

VCTRM-LP: ROLL (NA)

FC: FC-DE-NES (MJ)

PWR: EHIBATVG (MJ)

VCTRM-LP: ROLL-PEND (NA)

FC: FC-NO-CREDITS (MJ)

PWR: ELWBATVG (MJ)

VCTRM-LP: SQM (MJ)

FC: FORCED-REQ-SPAN (NA)

PWR: VOLT-MISM (NA)

VCTRM-LP: TU-AIS (NR)

FC: GE-OOSYNC (CR)

RPRIF: MAX-STATIONS (MJ)

VCTRM-LP: TU-LOP (MJ)

FC: HI-LASERBIAS (MN)

RPRIF: RSV-RT-EXCD-RINGLET0 (MJ)

FC: HI-RXPOWER (MN)

RPRIF: RSV-RT-EXCD-RINGLET1 (MJ)


2.5  Trouble Notifications

The ONS 15454 SDH system reports trouble by utilizing standard alarm and condition characteristics, and standard severities following the rules in ITU-T x.733, and graphical user interface (GUI) state indicators. These notifications are described in the following paragraphs.

The ONS 15454 SDH uses standard categories to characterize levels of trouble. The system reports trouble notifications as alarms and status or descriptive notifications (if configured to do so) as conditions in the CTC Alarms window. Alarms typically signify a problem that the user needs to address, such as a loss of signal. Conditions do not necessarily require troubleshooting.

2.5.1  Alarm Characteristics

The ONS 15454 SDH uses standard alarm entities to identify what is causing trouble. All alarms stem from hardware, software, environment, or operator-originated problems whether or not they affect service. Current alarms for the network, CTC session, node, or card are listed in the Alarms tab. (In addition, cleared alarms are also found in the History tab.)

2.5.2  Condition Characteristics

Conditions include any problem detected on an ONS 15454 SDH shelf. They could include standing or transient notifications. A snapshot of all current raised, standing conditions on the network, node, or card can be retrieved in the CTC Conditions window or using TL1's set of RTRV-COND commands. (In addition, some but not all cleared conditions are also found in the History tab.)

For more information about transient conditions, see Chapter 3, "Transient Conditions."


Note ONS 15454 SDH condition reporting is not ITU-compliant.


2.5.3  Severities

The ONS 15454 SDH uses ITU-devised standard severities for alarms and conditions: Critical (CR), Major (MJ), Minor (MN), Not Alarmed (NA), and Not Reported (NR). These are described below:

A Critical (CR) alarm generally indicates severe, Service-Affecting (SA) trouble that needs immediate correction, such as an LOS on a trunk port or STM signal.

A Major (MJ) alarm is a serious alarm, but the trouble has less impact on the network. For example, an automatic protection switching (APS) channel mismatch (APSCNMIS) alarm occurs when working and protect channels have been inadvertently switched so that a working channel is expected at the receive end, but a protect channel is received instead.

Minor (MN) alarms generally are those that do not affect service. For example, the APS byte failure (APSB) alarm indicates that line terminating equipment (LTE) detects a byte failure on the signal that could prevent traffic from properly executing a traffic switch.

Not Alarmed (NA) conditions are information indicators, such as for a free-running synchronization (FRNGSYNC) state or a forced-switch to primary timing (FRCSWTOPRI) event. They could or could not require troubleshooting, as indicated in the entries.

Not Reported (NR) conditions occur as a secondary result of another event. For example, the alarm indication signal (MS-AIS), with severity NR, is inserted by a downstream node when an LOS (CR or MJ) alarm occurs upstream. These conditions do not in themselves require troubleshooting, but are to be expected in the presence of primary alarms.

Severities can be customized for an entire network or for single nodes, from the network level down to the port level by changing or downloading customized alarm profiles. These custom severities are subject to the standard severity-demoting rules given in Telcordia GR-474-CORE and shown in the "Alarm Hierarchy" section. Procedures for customizing alarm severities are located in the "Manage Alarms" chapter of the Cisco ONS 15454 SDH Procedure Guide.

2.5.4  Alarm Hierarchy

All alarm, condition, and unreported event severities listed in this manual are default profile settings. However in situations when traffic is not lost, such as when the alarm occurs on protected ports or circuits, alarms having Critical (CR) or Major (MJ) default severities can be demoted to lower severities such as Minor (MN) or Non-Service-Affecting (NSA) as defined in Telcordia GR-474-CORE.

A path alarm can be demoted if a higher-ranking alarm is raised for the same object. For example, If an high-order path trace identifier mismatch (HP-TIM) is raised on a circuit path and then an administrative unit (AU) loss of pointer (LOP) is raised on it, the AU-LOP alarm stands and the HP-TIM closes. The path alarm hierarchy used in the ONS 15454 SDH system is shown in Table 2-9.

Table 2-9 Path Alarm Hierarchy

Priority
Condition Type

Highest

AU-AIS

AU-LOP

HP-UNEQ

Lowest

HP-TIM


Facility (port) alarms also follow a hierarchy, which means that lower-ranking alarms are closed by higher-ranking alarms. The facility alarm hierarchy used in the ONS 15454 SDH system is shown in Table 2-10.

Table 2-10 Facility Alarm Hierarchy

Priority
Condition Type

Highest

LOS

LOF

MS-AIS

MS-EXC1

MS-DEG1

MS-RDI1

RS-TIM

AU-AIS

AU-LOP

HP-EXC1

HP-DEG1

HP-UNEQ

HP-TIM

HP-PLM1

Lowest

PLM-P

1 This alarm is not currently used in the platform.


Near-end failures and far-end failures follow different hierarchies. Near-end failures stand according to whether they are for the entire signal (LOS, LOF), facility (MS-AIS), path (AU-AIS, etc.) or VT (TU-AIS, etc.). The full hierarchy for near-end failures is shown in Table 2-11. This table is taken from Telcordia GR-253-CORE.

Table 2-11 Near-End Alarm Hierarchy

Priority
Condition Type

Highest

LOS

LOF

MS-AIS

AU-AIS1

AU-LOP2

HP-UNEQ

HP-TIM

PLM-P

HP-PLM

TU-AIS1

TU-LOP2

LP-UNEQ3

LP-PLM3

Lowest

DS-N AIS (if reported for outgoing DS-N signals)

1 Although it is not defined as a defect or failure, all-ones VT pointer relay is also higher priority than AU-LOP. Similarly, all-ones VC pointer relay is higher priority than TU-LOP.

2 AU-LOP is also higher priority than the far-end failure MS-RFI, which does not affect the detection of any near-end failures. Similarly, TU-LOP is higher priority than LP-RF.

3 This alarm is not used in this platform in this release.


The far-end failure alarm hierarchy is shown in Table 2-12, as given in Telcordia GR-253-CORE.

Table 2-12 Far-End Alarm Hierarchy

Priority
Condition Type

Highest

MS-RDI1

HP-RFI

Lowest

LP-RFI1

1 This condition is not used in this platform in this release.


2.5.5  Service Effect

The ITU also provides service effect standards. Service-Affecting (SA) alarms—those that interrupt service—could be Critical (CR), Major (MJ), or Minor (MN) severity alarms. Non-Service-Affecting (NSA) alarms always have a Minor (MN) default severity.

2.5.6  States

The Alarms and History tab State (ST) column indicate the disposition of the alarm or condition as follows:

A raised (R) event is one that is active.

A cleared (C) event is one that is no longer active.

A transient (T) event is one that is automatically raised and cleared in CTC during system changes such as user login, logout, loss of connection to node view, etc. Transient events do not require user action. These are listed in Chapter 3, "Transient Conditions."

2.6  Safety Summary

This section covers safety considerations designed to ensure safe operation of the ONS 15454 SDH. Do not perform any procedures in this chapter unless you understand all safety precautions, practices, and warnings for the system equipment. Some troubleshooting procedures require installation or removal of cards; in these instances pay close attention to the following caution.


Caution Hazardous voltage or energy could be present on the backplane when the system is operating. Use caution when removing or installing cards.

Some troubleshooting procedures require installation or removal of STM-64 cards. In these instances, pay close attention to the following warnings.


Warning On the OC192 LR/STM64 LH 1550 card, the laser is on when the card is booted and the safety key is in the on position (labeled 1). The port does not have to be in service for the laser to be on. The laser is off when the safety key is off (labeled 0). Statement 293



Warning Invisible laser radiation could be emitted from the end of the unterminated fiber cable or connector. Do not stare into the beam directly with optical instruments. Viewing the laser output with certain optical instruments (for example, eye loupes, magnifiers, and microscopes) within a distance of 100 mm could pose an eye hazard. Statement 1056



Warning Use of controls, adjustments, or performing procedures other than those specified could result in hazardous radiation exposure. Statement 1057



Warning Class 1 laser product. Statement 1008



Warning Class 1M laser radiation when open. Do not view directly with optical instruments. Statement 1053



Warning Do not reach into a vacant slot or chassis while you install or remove a module or a fan. Exposed circuitry could constitute an energy hazard. Statement 206



Warning The power supply circuitry for the equipment can constitute an energy hazard. Before you install or replace the equipment, remove all jewelry (including rings, necklaces, and watches). Metal objects can come into contact with exposed power supply wiring or circuitry inside the DSLAM equipment. This could cause the metal objects to heat up and cause serious burns or weld the metal object to the equipment. Statement 207


2.7  Alarm Procedures

This section list alarms alphabetically and includes some conditions commonly encountered when troubleshooting alarms. The severity, description, and troubleshooting procedure accompany each alarm and condition.


Note When you check the status of alarms for cards, ensure that the alarm filter icon in the lower right corner of the GUI is not indented. If it is, click it to turn it off. When you're done checking for alarms, click the alarm filter icon again to turn filtering back on. For more information about alarm filtering, refer to the "Manage Alarms" chapter of the Cisco ONS 15454 SDH Procedure Guide.



Note When checking alarms, ensure that alarm suppression is not enabled on the card or port. For more information about alarm suppression, refer to the "Manage Alarms" chapter in the Cisco ONS 15454 SDH Procedure Guide.



Note When an entity is put in the Locked,maintenance administrative state, the ONS 15454 SDH suppresses all standing alarms on that entity and alarms and events appear on the Conditions tab. You can change this behavior for the LPBKFACILITY and LPBKTERMINAL alarms. To display these alarms on the Alarms tab, set the NODE.general.ReportLoopbackConditionsOnPortsInLocked,Maintenance to TRUE on the NE Defaults tab. For more information about changing NE defaults, refer to the "Maintain the Node" chapter in the Cisco ONS 15454 SDH Procedure Guide.


2.7.1  AIS

Default Severity: Not Reported (NR), Non-Service-Affecting (NSA)

SDH Logical Objects: BITS, DS1, DS3, E1, E3, E4, FUDC, MSUDC

DWDM Logical Object: TRUNK

The Alarm Indication Signal (AIS) condition indicates that this node is detecting an alarm indication signal in the incoming signal SDH overhead.

Generally, any AIS is a special SDH signal that communicates to the receiving node when the transmit node does not send a valid signal. AIS is not considered an error. It is raised by the receiving node on each input when it detects the AIS instead of a real signal. In most cases when this condition is raised, an upstream node is raising an alarm to indicate a signal failure; all nodes downstream from it only raise some type of AIS. This condition clears when you resolved the problem on the upstream node.


Note DS3i-N-12 card DS3 facility and terminal loopbacks do not transmit DS3 AIS in the direction away from the loopback. Instead of DS3 AIS, a continuance of the signal transmitted to the loopback is provided.


Clear the AIS Condition


Step 1 Determine whether there are alarms on the upstream nodes and equipment, especially the "LOS (STM1E, STMN)" alarm on page 2-161, or if there are locked (Locked,maintenance or Locked,disabled) ports.

Step 2 Clear the upstream alarms using the applicable procedures in this chapter.

Step 3 If the condition does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.2  AIS-L

The AIS-L condition is not used in this platform in this release. It is reserved for development.

2.7.3  ALS

For information about this alarm or condition, refer to the "Alarm Troubleshooting" chapter in the Cisco ONS 15454 DWDM Troubleshooting Guide. This guide discusses all DWDM alarms.

2.7.4  ALS-DISABLED

For information about this alarm or condition, refer to the "Alarm Troubleshooting" chapter in the Cisco ONS 15454 DWDM Troubleshooting Guide. This guide discusses all DWDM alarms.

2.7.5  AMPLI-INIT

For information about this alarm or condition, refer to the "Alarm Troubleshooting" chapter in the Cisco ONS 15454 DWDM Troubleshooting Guide. This guide discusses all DWDM alarms.

2.7.6  APC-CORR-SKIPPED

For information about this alarm or condition, refer to the "Alarm Troubleshooting" chapter in the Cisco ONS 15454 DWDM Troubleshooting Guide. This guide discusses all DWDM alarms.

2.7.7  APC-DISABLED

For information about this alarm or condition, refer to the "Alarm Troubleshooting" chapter in the Cisco ONS 15454 DWDM Troubleshooting Guide. This guide discusses all DWDM alarms.

2.7.8  APC-END

For information about this alarm or condition, refer to the "Alarm Troubleshooting" chapter in the Cisco ONS 15454 DWDM Troubleshooting Guide. This guide discusses all DWDM alarms.

2.7.9  APC-OUT-OF-RANGE

For information about this alarm or condition, refer to the "Alarm Troubleshooting" chapter in the Cisco ONS 15454 DWDM Troubleshooting Guide. This guide discusses all DWDM alarms.

2.7.10  APC-WRONG-GAIN

For information about this alarm or condition, refer to the "Alarm Troubleshooting" chapter in the Cisco ONS 15454 DWDM Troubleshooting Guide. This guide discusses all DWDM alarms.

2.7.11  APSB

Default Severity: Minor (MN), Non-Service-Affecting (NSA)

SDH Logical Object: STMN

The APS Channel Byte Failure alarm occurs when LTE detects protection switching byte failure or an invalid switching code in the incoming APS signal. Some older SDH nodes not manufactured by Cisco send invalid APS codes if they are configured in a 1+1 protection group with newer SDH nodes, such as the ONS 15454 SDH. These invalid codes cause an APSB alarm on an ONS 15454 SDH node.

Clear the APSB Alarm


Step 1 Use an optical test set to examine the incoming SDH overhead to confirm inconsistent or invalid K bytes. For specific procedures to use the test set equipment, consult the manufacturer. If corrupted K bytes are confirmed and the upstream equipment is functioning properly, the upstream equipment might not interoperate effectively with the ONS 15454 SDH.

Step 2 If the alarm does not clear and the overhead shows inconsistent or invalid K bytes, you could need to replace the upstream cards for protection switching to operate properly. Complete the "Physically Replace a Traffic Card" procedure.


Caution For the ONS 15454 SDH, removing a card that currently carries traffic on one or more ports can cause a traffic hit. To avoid this, perform an external switch if a switch has not already occurred. See the "Protection Switching, Lock Initiation, and Clearing" section for commonly used alarm troubleshooting procedures.


Note When you replace a card with the identical type of card, you do not need to make any changes to the database.


Step 3 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.12  APSCDFLTK

Default Severity: Minor (MN), Non-Service-Affecting (NSA)

SDH Logical Object: STMN

The APS Default K Byte Received alarm occurs when a multiplex section-shared protection ring (MS-SPRing) is not properly configured—for example, when a four-node MS-SPRing has one node configured as a subnetwork connection protection (SNCP) ring. When this misconfiguration occurs, a node in an SNCP ring or 1+1 configuration does not send the two valid K1/K2 APS bytes anticipated by a system configured for MS-SPRing. One of the bytes sent is considered invalid by the MS-SPRing configuration. The K1/K2 byte is monitored by receiving equipment for link-recovery information.

Troubleshooting for APSCDFLTK is often similar to troubleshooting for the "MSSP-OOSYNC" alarm on page 2-191.

Clear the APSCDFLTK Alarm


Step 1 Complete the "Identify an MS-SPRing Ring Name or Node ID Number" procedure to verify that each node has a unique node ID number.

Step 2 Repeat Step 1 for all nodes in the ring.

Step 3 If two nodes have the same node ID number, complete the "Change an MS-SPRing Node ID Number" procedure to change one node ID number so that each node ID is unique.

Step 4 If the alarm does not clear, verify correct configuration of east port and west port optical fibers. (See the "EXCCOL" alarm on page 2-91.) West port fibers must connect to east port fibers and east port fibers must connect to west port fibers. The "Install Cards and Fiber-Optic Cable" chapter in the Cisco ONS 15454 SDH Procedure Guide provides a procedure for fibering MS-SPRings.

Step 5 If the alarm does not clear and if the network is a four-fiber MS-SPRing, ensure that each protect fiber is connected to another protect fiber and each working fiber is connected to another working fiber. The software does not report any alarm if a working fiber is incorrectly attached to a protect fiber.

Step 6 If the alarm does not clear, complete the "Verify Node Visibility for Other Nodes" procedure.

Step 7 If nodes are not visible, complete the "Verify or Create Node RS-DCC Terminations" procedure to ensure that regenerator section data communications channel (RS-DCC) terminations exist on each node.

Step 8 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.13  APSC-IMP

Default Severity: Minor (MN), Non-Service-Affecting (NSA)

SDH Logical Object: STMN

An Improper SDH APS Code alarm indicates bad or invalid K bytes. The APSC-IMP alarm occurs on STM-N cards in a MS-SPRing configuration and can occur during MS-SPRing configuration.

The receiving equipment monitors K bytes or K1 and K2 APS bytes for an indication to switch from the working card to the protect card or from the protect card to the working one. K1/K2 bytes also contain bits that tell the receiving equipment whether the K byte is valid. The alarm clears when the node receives valid K bytes.


Note This alarm can occur on a VC_LO_PATH_TUNNEL tunnel when it does not have lower order circuits provisioned on it. It can also occur when the exercise command or a lockout is applied to a span. An externally switched span does not raise this alarm because the traffic is preempted.



Note The APSC-IMP alarm may be raised on a BLSR or MS-SPRing when a drop connection is part of a cross-connect loopback.



Note The APSC-IMP alarm may be momentarily raised on BLSR spans during PCA circuit creation or deletion across multiple nodes using CTC.



Warning Invisible laser radiation could be emitted from the end of the unterminated fiber cable or connector. Do not stare into the beam directly with optical instruments. Viewing the laser output with certain optical instruments (for example, eye loupes, magnifiers, and microscopes) within a distance of 100 mm could pose an eye hazard. Statement 1056



Warning Use of controls, adjustments, or performing procedures other than those specified could result in hazardous radiation exposure. Statement 1057


Clear the APSC-IMP Alarm


Step 1 Use an optical test set to determine the validity of the K byte signal by examining the received signal. For specific procedures to use the test set equipment, consult the manufacturer.


Caution Always use the supplied electrostatic discharge wristband when working with a powered ONS 15454 SDH. Plug the wristband cable into the ESD jack located on the on the middle-right outside edge of the shelf assembly.

If the K byte is invalid, the problem lies with upstream equipment and not with the reporting ONS 15454 SDH. Troubleshoot the upstream equipment using the procedures in this chapter, as applicable. If the upstream nodes are not ONS 15454 SDHs, consult the appropriate user documentation.

Step 2 If the K byte is valid, verify that each node has a ring name that matches the other node ring names. Complete the "Identify an MS-SPRing Ring Name or Node ID Number" procedure.

Step 3 Repeat Step 2 for all nodes in the ring.

Step 4 If a node has a ring name that does not match the other nodes, make that node's ring name identical to the other nodes. Complete the "Change an MS-SPRing Ring Name" procedure.

Step 5 If the condition does not clear, log into the Cisco Technical Support website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.14  APSCINCON

Default Severity: Minor (MN), Non-Service-Affecting (NSA)

SDH Logical Object: STMN

An Inconsistent APS Code alarm indicates that the APS code contained in the SDH overhead is inconsistent. The SDH overhead contains K1/K2 APS bytes that notify receiving equipment, such as the ONS 15454 SDH, to switch the SDH signal from a working to a protect path when necessary. An inconsistent APS code occurs when three consecutive frames contain nonidentical APS bytes, which in turn give the receiving equipment conflicting commands about switching.

Clear the APSCINCON Alarm on an STM-N Card in an MS-SPRing


Step 1 Look for other alarms, especially the "LOS (STM1E, STMN)" alarm on page 2-161, the "LOF (DS1, DS3, E1, E4, STM1E, STMN)" alarm on page 2-152, or the "APSB" alarm on page 2-38. Clearing these alarms clears the APSCINCON alarm.

Step 2 If an APSINCON alarm occurs with no other alarms, log into the Cisco Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.15  APSCM

Default Severity: Major (MJ), Service-Affecting (SA) for STMN

SDH Logical Object: STMN

An Improper SDH APS Code alarm indicates three consecutive, identical frames containing:

Unused code in bits 6 through 8 of byte K2.

Codes that are irrelevant to the specific protection switching operation being requested.

Requests that are irrelevant to the ring state of the ring (such as a span protection switch request in a two-fiber ring NE).

ET code in K2 bits 6 through 8 received on the incoming span, but not sourced from the outgoing span.


Warning On the OC192 LR/STM64 LH 1550 card, the laser is on when the card is booted and the safety key is in the on position (labeled 1). The port does not have to be in service for the laser to be on. The laser is off when the safety key is off (labeled 0). Statement 293



Warning Invisible laser radiation could be emitted from the end of the unterminated fiber cable or connector. Do not stare into the beam directly with optical instruments. Viewing the laser output with certain optical instruments (for example, eye loupes, magnifiers, and microscopes) within a distance of 100 mm could pose an eye hazard. Statement 1056



Warning Use of controls, adjustments, or performing procedures other than those specified could result in hazardous radiation exposure. Statement 1057


Clear the APSCM Alarm


Step 1 Verify that the working-card channel fibers are physically connected directly to the adjoining node's working-card channel fibers.


Caution Always use the supplied electrostatic discharge wristband when working with a powered ONS 15454 SDH. Plug the wristband cable into the ESD jack located on the middle-right outside edge of the shelf assembly.

Step 2 If the alarm does not clear, verify that the protection-card channel fibers are physically connected directly to the adjoining node's protection-card channel fibers.

Step 3 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country in order to report a Service-Affecting (SA) problem.


2.7.16  APSCNMIS

Default Severity: Major (MJ), Service-Affecting (SA)

SDH Logical Object: STMN

The APS Node ID Mismatch alarm occurs when the source node ID contained in the incoming APS channel K2 byte is not present in the ring map. APSCNMIS could occur and clear when an MS-SPRing is being provisioned. If so, the user can disregard the temporary occurrence. If the APSCNMIS occurs and stays, the alarm clears when a K byte with a valid source node ID is received.

Clear the APSCNMIS Alarm


Step 1 Complete the "Identify an MS-SPRing Ring Name or Node ID Number" procedure for each node to verify that each node has a unique node ID number.

Step 2 If the Node ID column contains any two nodes with the same node ID listed, record the repeated node ID.

Step 3 Click Close in the Ring Map dialog box.

Step 4 If two nodes have the same node ID number, complete the "Change an MS-SPRing Node ID Number" procedure to change one node ID number so that each node ID is unique.


Note If the node names shown in the network view do not correlate with the node IDs, log into each node and click the Provisioning > MS-SPRing tabs. The MS-SPRing window shows the node ID of the login node.



Note Applying and removing a lockout on a span causes the ONS node to generate a new K byte. The APSCNMIS alarm clears when the node receives a K byte containing the correct node ID.


Step 5 If the alarm does not clear, use the "Initiate a Lockout on an MS-SPRing Protect Span" procedure to lock out the span.

Step 6 Complete the "Clear an MS-SPRing External Switching Command" procedure to clear the lockout.

Step 7 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country in order to report a Service-Affecting (SA) problem.


2.7.17  APS-INV-PRIM

The APS-INV-PRIM alarm is not used in this platform in this release. It is reserved for development.

2.7.18  APS-PRIM-FAC

The APS-PRIM-FAC condition is not used in this platform in this release. It is reserved for development.

2.7.19  APS-PRIM-SEC-MISM

The APS-PRIM-SEC-MISM condition is not used in this platform in this release. It is reserved for development.

2.7.20  AS-CMD

Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)

SDH Logical Objects: BPLANE, CE100T, CE1000, DS1, DS3, E1, E100T, E1000F, E3, E4, EQPT, FCMR, G1000 GFP-FAC, ML100T, ML1000, MLFX, NE, PWR, STM1E, STMN

DWDM Logical Objects: 2R, AOTS, ESCON, FC, GE, ISC, OCH, OMS, OTS, PPM, SHELF, TRUNK

The Alarms Suppressed by User Command condition applies to the network element (NE object), backplane, a single card, or a port on a card. It occurs when alarms are suppressed for that object and its subordinate objects; For example, suppressing alarms on a card also suppresses alarms on its ports.


Note For more information about suppressing alarms, refer to the "Manage Alarms" chapter in the Cisco ONS 15454 SDH Procedure Guide.


Clear the AS-CMD Condition


Step 1 For all nodes, in node view, click the Conditions tab.

Step 2 Click Retrieve. If you have already retrieved conditions, look under the Object column and Eqpt Type column and note what entity the condition is reported against—such as a port, slot, or shelf.

If the condition is reported against an STM-N card and slot, alarms were either suppressed for the entire card or for one of the ports. Note the slot number and continue with Step 3.

If the condition is reported against the backplane, go to Step 8.

If the condition is reported against the NE object, go to Step 9.

Step 3 If the AS-CMD condition is reported for an STM-N card, determine whether alarms are suppressed for a port and if so, raise the suppressed alarms by completing the following steps:

a. Double-click the card to display the card view.

b. Click the Provisioning > Alarm Profiles > Alarm Behavior tabs an d complete one of the following substeps:

If the Suppress Alarms column check box is checked for a port row, deselect it and click Apply.

If the Suppress Alarms column check box is not checked for a port row, click View > Go to Previous View.

Step 4 If the AS-CMD condition is reported for an amplifier, combiner, or other DWDM card, determine whether alarms are suppressed for a port and if so, raise the suppressed alarms by completing the following steps:

a. Double-click the card to display the card view.

b. Click the Provisioning > Optical Line > Alarm Profiles tabs and complete one of the following substeps:

If the Suppress Alarms column check box is checked for a port row, deselect it and click Apply.

If the Suppress Alarms column check box is not checked for a port row, click View > Go to Previous View.

Step 5 In node view, if the AS-CMD condition is reported for a card and not an individual port, click the Provisioning > Alarm Profiles > Alarm Behavior tabs.

Step 6 Locate the row for the reported card slot.

Step 7 Click the Suppress Alarms column check box to deselect the option for the card row.

Step 8 If the condition is reported for the backplane, the alarms are suppressed for cards such as the AIP that are not in the optical or electrical slots. To clear the alarm, complete the following steps:

a. In node view, click the Provisioning > Alarm Profiles > Alarm Behavior tabs.

b. In the backplane row, uncheck the Suppress Alarms column check box.

c. Click Apply.

Step 9 If the condition is reported for the shelf, cards and other equipment are affected. To clear the alarm, complete the following steps:

a. In node view, click the Provisioning > Alarm Profiles > Alarm Behavior tabs.

b. Click the Suppress Alarms check box located at the bottom of the window to deselect the option.

c. Click Apply.

Step 10 If the condition does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.21  AS-MT

Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)

SDH Logical Objects: CE100T, CE1000, DS1, DS3, E1, E3, E4, EQPT, FCMR, G1000, GFP-FAC, ML100T, ML1000, MLFX, STM1E, STMN

DWDM Logical Objects: 2R, AOTS, ESCON, FC, GE, ISC, OCH, OMS, OTS, PPM, SHELF, TRUNK

The Alarms Suppressed for Maintenance Command condition applies to STM-N, electrical cards, and Ethernet cards, and occurs when a port is placed in the Locked-Enabled, loopback & maintenance service state for loopback testing operations.

Clear the AS-MT Condition


Step 1 Complete the "Clear an STM-N Card Facility or Terminal Loopback Circuit" procedure.

Step 2 If the condition does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.22  AS-MT-OOG

Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)

SDH Logical Objects: VCTRM-HP, VCTRM-LP

The Alarms Suppressed on an Out-Of-Group VCAT Member condition is raised on a VC whenever the member is in the IDLE (AS-MT-OOG) admin state. This condition can be raised when a member is initially added to a group. In IDLE (AS-MT-OOG) state, all other alarms for the VC are suppressed.

Clear the AS-MT-OOG Condition


Step 1 The AS-MT-OOG condition clears when a VC member transitions to a different state from IDLE (AS-MT-OOG) or when it is removed completely from the group. It does not require troubleshooting unless it does not clear.

Step 2 If the condition does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.23  AU-AIS

Default Severity: Not Reported (NR), Non-Service-Affecting (NSA)

SDH Logical Objects: VCMON-HP, VCTRM-HP

An AU AIS condition applies to the administration unit, which consists of the virtual container (VC) capacity and pointer bytes (H1, H2, and H3) in the SDH frame.

Generally, any AIS is a special SDH signal that communicates to the receiving node when the transmit node does not send a valid signal. AIS is not considered an error. It is raised by the receiving node on each input when it detects the AIS instead of a real signal. In most cases when this condition is raised, an upstream node is raising an alarm to indicate a signal failure; all nodes downstream from it only raise some type of AIS. This condition clears when you resolved the problem on the upstream node.

Clear the AU-AIS Condition


Step 1 Complete the "Clear the AIS Condition" procedure.

Step 2 If the condition does not clear, complete the "Clear the APSB Alarm" procedure.

Step 3 If the condition does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.24  AUD-LOG-LOSS

Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)

SDH Logical Object: NE

The Audit Trail Log Loss condition occurs when the log is 100 percent full and that the oldest entries are being replaced as new entries are generated. The log capacity is 640 entries. You must off-load (save) the log to make room for more entries.

Clear the AUD-LOG-LOSS Condition


Step 1 In node view, click the Maintenance > Audit tabs.

Step 2 Click Retrieve.

Step 3 Click Archive.

Step 4 In the Archive Audit Trail dialog box, navigate to the directory (local or network) where you want to save the file.

Step 5 Enter a name in the File Name field.

You do not need to assign an extension to the file. The file is readable in any application that supports text files, such as WordPad, Microsoft Word (imported), etc.

Step 6 Click Save.

The 640 entries are saved in this file. New entries continue with the next number in the sequence, rather than starting over.

Step 7 If the condition does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.25  AUD-LOG-LOW

Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)

SDH Logical Object: NE

The Audit Trail Log Low condition occurs when the audit trail log is 80 percent full.


Note AUD-LOG-LOW is an informational condition. The condition does not require troubleshooting.


2.7.26  AU-LOF

Critical (CR), Service-Affecting (SA)

SDH Logical Object: VCTRM-HP

The AU Loss of Frame (LOF) alarm indicates that the ONS 15454 SDH detects frame loss in the regenerator section of the SDH overhead.

Clear the AU-LOF Alarm


Step 1 Complete the "Clear the LOF (TRUNK) Alarm" procedure, which is located in the "Alarm Troubleshooting" chapter of the Cisco ONS 15454 DWDM Troubleshooting Guide.

Step 2 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country to report a Service-Affecting (SA) problem.


2.7.27  AU-LOP

Default Severity: Critical (CR), Service-Affecting (SA)

SDH Logical Objects: VCMON-HP, VCTRM-HP

An AU-LOP alarm indicates that the SDH high order path overhead section of the administration unit has detected a loss of path. AU-LOP occurs when there is a mismatch between the expected and provisioned circuit size. For the TXP card, an AU-LOP is raised if a port is configured for an SDH signal but receives a SDH signal instead. (This information is contained in the H1 byte bits 5 and 6.)


Warning Invisible laser radiation could be emitted from the end of the unterminated fiber cable or connector. Do not stare into the beam directly with optical instruments. Viewing the laser output with certain optical instruments (for example, eye loupes, magnifiers, and microscopes) within a distance of 100 mm could pose an eye hazard. Statement 1056



Warning Use of controls, adjustments, or performing procedures other than those specified could result in hazardous radiation exposure. Statement 1057



Note For more information about MXP and TXP cards, refer to the Cisco ONS 15454 SDH Reference Manual.


Clear the AU-LOP Alarm


Step 1 In node view, click the Circuits tab and view the alarmed circuit.

Step 2 Verify that the correct circuit size is listed in the Size column. If the size is different from what is expected, such as a VC4-4c instead of a VC4, this causes the alarm.

Step 3 If you have been monitoring the circuit with optical test equipment, a mismatch between the provisioned circuit size and the size expected by the test set can cause this alarm. Ensure that the test set monitoring is set up for the same size as the circuit provisioning. For specific procedures to use the test set equipment, consult the manufacturer.

Step 4 If you have not been using a test set, or if the test set is correctly set up, the error is in the provisioned CTC circuit size. Complete the "Delete a Circuit" procedure.

Step 5 Recreate the circuit for the correct size. For procedures, refer to the "Create Circuits and Tunnels" chapter in the Cisco ONS 15454 SDH Procedure Guide.

Step 6 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country in order to report a Service-Affecting (SA) problem.


2.7.28  AUTOLSROFF

Default Severity: Critical (CR), Service-Affecting (SA)

SDH Logical Object: STMN

The Auto Laser Shutdown alarm occurs when the STM-64 card temperature exceeds 194 degrees F (90 degrees C). The internal equipment automatically shuts down the STM-64 laser when the card temperature rises to prevent the card from self-destructing.


Warning On the OC192 LR/STM64 LH 1550 card, the laser is on when the card is booted and the safety key is in the on position (labeled 1). The port does not have to be in service for the laser to be on. The laser is off when the safety key is off (labeled 0). Statement 293.



Warning Invisible laser radiation could be emitted from the end of the unterminated fiber cable or connector. Do not stare into the beam directly with optical instruments. Viewing the laser output with certain optical instruments (for example, eye loupes, magnifiers, and microscopes) within a distance of 100 mm could pose an eye hazard. Statement 1056



Warning Use of controls, adjustments, or performing procedures other than those specified could result in hazardous radiation exposure. Statement 1057


Clear the AUTOLSROFF Alarm


Step 1 View the temperature displayed on the ONS 15454 SDH LCD front panel (Figure 2-1).

Figure 2-1 shows the shelf LCD panel.

Figure 2-1 Shelf LCD Panel

Step 2 If the temperature of the shelf exceeds 194 degrees F (90 degrees C), the alarm should clear if you solve the ONS 15454 SDH temperature problem. Complete the "Clear the HITEMP Alarm" procedure.

Step 3 If the temperature of the shelf is under 194 degrees F (90 degrees C), the HITEMP alarm is not the cause of the AUTOLSROFF alarm. Complete the "Physically Replace a Traffic Card" procedure for the STM-64 card.


Note When you replace a card with the identical type of card, you do not need to make any changes to the database.


Step 4 If card replacement does not clear the alarm, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country in order to report a Service-Affecting (SA) problem.


2.7.29  AUTONEG-RFI

Default Severity: Major (MJ), Service-Affecting (SA)

SDH Logical Object: ML1000

The autonegotiation remote fault indication (RFI) indicates that an ML1000 Gigabit Ethernet port cannot detect its far-end link partner. This is typically caused by a far-end port shutdown or a unidirectional fiber cut. The partner node is likely raising a CARLOSS alarm.

AUTONEG-RFI may also be caused by misconfigured autonegotiation parameters. This causes more of a soft failure as opposed to CARLOSS, which is typically caused by a failure like a loss of light or optical fiber. The alarm clears the partner node is detected.


Note The far end of an Ethernet link is usually a switch or router that does not use an ONS management system.


Clear the AUTONEG-RFI Alarm


Step 1 Check for a "CARLOSS (EQPT)" alarm on page 2-61, or "CARLOSS (ML100T, ML1000, MLFX)" alarm on page 2-65, at the partner node. If the alarm exists there, follow the appropriate clearing procedure in this chapter.

Step 2 If the alarm does not clear or if there is no far-end CARLOSS, check the near-end Gigabit Ethernet port autonegotiation settings:

a. Double-click the ML1000 card to display the card view.

b. Click the IOS tab, then click Open IOS Connection.

c. In Privileged Executive mode, enter the following command:

router# show interface gigabitethernet 0

d. View the command output and record the autonegotiation setting, such as the following example:

Full-duplex, 1000Mb/s, Gbic not connected, Auto-negotiation
output flow-control is off, input flow-control is on

Step 3 View the autonegotiation configuration for the partner node. If it is ONS equipment, follow the previous step for this node. If the node is different vendor client equipment, follow that equipment documentation to obtain the information.

Step 4 If the alarm does not clear, check for any fiber breaks such as on the transmit cable from the partner node to the near-end node.

Step 5 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.30  AUTORESET

Default Severity: Minor (MN), Non-Service-Affecting (NSA)

SDH Logical Object: EQPT

The Automatic System Reset alarm occurs when a card is performing an automatic warm reboot. An AUTORESET occurs when you change an IP address or perform any other operation that causes an automatic card-level reboot.

Resets performed during a software upgrade also prompt the condition. This condition clears automatically when the card finishes resetting.

Clear the AUTORESET Alarm


Step 1 Determine whether there are additional alarms that could have triggered an automatic reset. If there are, troubleshoot these alarms using the applicable section of this chapter.

Step 2 If the card automatically resets more than once a month with no apparent cause, complete the "Physically Replace a Traffic Card" procedure.


Caution Always use the supplied electrostatic discharge wristband when working with a powered ONS 15454 SDH. Plug the wristband cable into the ESD jack located on the middle-right outside edge of the shelf assembly.


Note When you replace a card with the identical type of card, you do not need to make any changes to the database.


Step 3 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.31  AUTOSW-AIS-SNCP

Default Severity: Not Reported (NR), Non-Service-Affecting (NSA)

SDH Logical Objects: VCMON-HP, VCMON-LP

The Automatic SNCP Switch Caused by an AIS condition indicates that automatic SNCP protection switching occurred because of the "TU-AIS" condition on page 2-251. If the SNCP ring is configured for revertive switching, it switches back to the working path after the fault clears. The AUTOSW-AIS-SNCP clears when you clear the primary alarm on the upstream node.


Note This condition is only reported if the SNCP is set up for revertive switching.


Generally, any AIS is a special SDH signal that communicates to the receiving node when the transmit node does not send a valid signal. AIS is not considered an error. It is raised by the receiving node on each input when it detects the AIS instead of a real signal. In most cases when this condition is raised, an upstream node is raising an alarm to indicate a signal failure; all nodes downstream from it only raise some type of AIS. This condition clears when you resolved the problem on the upstream node.

Clear the AUTOSW-AIS-SNCP Condition


Step 1 Complete the "Clear the AIS Condition" procedure.

Step 2 If the condition does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.32  AUTOSW-LOP-SNCP

Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)

SDH Logical Objects: VCMON-HP, VCMON-LP

An Automatic SNCP Switch Caused by LOP alarm indicates that an automatic SNCP protection switching occurred because of the "AU-LOP" alarm on page 2-48. If the SNCP ring is configured for revertive switching, it switches back to the working path after the fault clears.


Note This condition is only reported if the SNCP is set up for revertive switching.


Clear the AUTOSW-LOP-SNCP Alarm


Step 1 Complete the "Clear the AU-LOP Alarm" procedure.

Step 2 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.33  AUTOSW-SDBER-SNCP

Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)

SDH Logical Object: VCMON-HP, VCMON-LP

The Automatic SNCP Switch Caused by Signal Degrade Bit Error Rate (SDBER) condition indicates that a signal degrade [see the "SD (DS1, DS3, E1, E3, E4, STMN)" condition on page 2-221] caused automatic SNCP protection switching to occur. If the SNCP ring is configured for revertive switching, it reverts to the working path when the SD is resolved.


Note This condition is only reported if the SNCP is set up for revertive switching.


Clear the AUTOSW-SDBER-SNCP Condition


Step 1 Complete the "Clear the SD (DS3, E1, E3, E4, STMN) Condition" procedure.

Step 2 If the condition does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.34  AUTOSW-SFBER-SNCP

Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)

SDH Logical Object: VCMON-HP, VCMON-LP

The Automatic SNCP Switch Caused by Signal Fail Bit Error Rate (SFBER) condition indicates that a signal fail [see the "SF (DS1, DS3, E1, E3, E4, STMN)" condition on page 2-225] caused automatic SNCP protection switching to occur. If the SNCP ring is configured for revertive switching, it reverts to the working path when the SF is resolved.


Note This condition is only reported if the SNCP is set up for revertive switching.


Clear the AUTOSW-SFBER-SNCP Condition


Step 1 Complete the "Clear the SF (DS3, E1, E3, E4, STMN) Condition" procedure.

Step 2 If the condition does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.35  AUTOSW-UNEQ-SNCP (VCMON-HP)

Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)

SDH Logical Object: VCMON-HP

The Automatic SNCP Switch Caused by an Unequipped condition indicates that an HP-UNEQ alarm caused automatic SNCP protection switching to occur (see the "HP-UNEQ" alarm on page 2-131). If the SNCP ring is configured for revertive switching, it reverts to the working path after the fault clears.


Warning Class 1 laser product. Statement 1008



Warning Class 1M laser radiation when open. Do not view directly with optical instruments. Statement 1053



Warning Invisible laser radiation could be emitted from the end of the unterminated fiber cable or connector. Do not stare into the beam directly with optical instruments. Viewing the laser output with certain optical instruments (for example, eye loupes, magnifiers, and microscopes) within a distance of 100 mm could pose an eye hazard. Statement 1056



Warning Use of controls, adjustments, or performing procedures other than those specified could result in hazardous radiation exposure. Statement 1057



Note This condition is only reported if the SNCP is set up for revertive switching.


Clear the AUTOSW-UNEQ-SNCP (VCMON-HP) Condition


Step 1 Complete the "Clear the HP-UNEQ Alarm" procedure.

Step 2 If the condition does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.36  AUTOSW-UNEQ-SNCP (VCMON-LP)

Default Severity: Minor (MN), Non-Service-Affecting (NSA)

SDH Logical Object: VCMON-LP

AUTOSW-UNEQ-SNCP for VCMON-LP indicates that the "LP-UNEQ" alarm on page 2-178 caused automatic SNCP protection switching to occur. If the SNCP ring is configured for revertive switching, it reverts to the working path after the fault clears.


Warning Class 1 laser product. Statement 1008



Warning Class 1M laser radiation when open. Do not view directly with optical instruments. Statement 1053



Warning Invisible laser radiation could be emitted from the end of the unterminated fiber cable or connector. Do not stare into the beam directly with optical instruments. Viewing the laser output with certain optical instruments (for example, eye loupes, magnifiers, and microscopes) within a distance of 100 mm could pose an eye hazard. Statement 1056



Note This condition is only reported if the SNCP is set up for revertive switching.


Clear the AUTOSW-UNEQ-SNCP (VCMON-LP) Condition


Step 1 Display the CTC network view and right-click the span reporting AUTOSW-UNEQ. Select Circuits from the shortcut menu.

Step 2 If the specified circuit is a low-order path tunnel, determine whether low-order paths are assigned to the tunnel.

Step 3 If the low-order path tunnel does not have assigned low-order paths, delete the low-order path tunnel from the list of circuits.

Step 4 If you have complete visibility to all nodes, determine whether there are incomplete circuits such as stranded bandwidth from circuits that were not completely deleted.

Step 5 If you find incomplete circuits, determine whether they are working circuits and if they are still passing traffic.

Step 6 If the incomplete circuits are not needed or are not passing traffic, delete them and log out of CTC. Log back in and search for incomplete circuits again. Recreate any needed circuits.

Step 7 If the condition does not clear, verify that all circuits terminating in the reporting card are active by completing the following steps:

a. In node view, click the Circuits tab.

b. Verify that the Status column lists the port as active.

c. If the Status column lists the port as incomplete, and the incomplete does not change after a full initialization, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.

Step 8 After you determine that the port is active, verify the signal source received by the card reporting the alarm.

Step 9 If the condition does not clear, verify that the far-end STM-N card providing payload to the card is working properly.

Step 10 If the condition does not clear, verify the far-end cross-connect between the STM-N card and the E-N card.

Step 11 If the condition does not clear, clean the far-end optical fiber cable ends according to site practice. If no site practice exists, complete the procedure for cleaning optical connectors in the "Maintain the Node" chapter of the Cisco ONS 15454 SDH Procedure Guide.


Warning On the OC192 LR/STM64 LH 1550 card, the laser is on when the card is booted and the safety key is in the on position (labeled 1). The port does not have to be in service for the laser to be on. The laser is off when the safety key is off (labeled 0). Statement 293



Warning Invisible laser radiation could be emitted from the end of the unterminated fiber cable or connector. Do not stare into the beam directly with optical instruments. Viewing the laser output with certain optical instruments (for example, eye loupes, magnifiers, and microscopes) within a distance of 100 mm could pose an eye hazard. Statement 1056



Warning Use of controls, adjustments, or performing procedures other than those specified could result in hazardous radiation exposure. Statement 1057


Step 12 If the condition does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country.


2.7.37  AWG-DEG

For information about this alarm or condition, refer to the "Alarm Troubleshooting" chapter in the Cisco ONS 15454 DWDM Troubleshooting Guide. This guide discusses all DWDM alarms.

2.7.38  AWG-FAIL

For information about this alarm or condition, refer to the "Alarm Troubleshooting" chapter in the Cisco ONS 15454 DWDM Troubleshooting Guide. This guide discusses all DWDM alarms.

2.7.39  AWG-OVERTEMP

For information about this alarm or condition, refer to the "Alarm Troubleshooting" chapter in the Cisco ONS 15454 DWDM Troubleshooting Guide. This guide discusses all DWDM alarms.

2.7.40  AWG-WARM-UP

For information about this alarm or condition, refer to the "Alarm Troubleshooting" chapter in the Cisco ONS 15454 DWDM Troubleshooting Guide. This guide discusses all DWDM alarms.

2.7.41  BAT-FAIL

Default Severity: Major (MJ), Service-Affecting (SA)

SDH Logical Object: PWR

The Battery Fail alarm occurs when one of the two power supplies (A or B) is not detected. This could be because the supply is removed or is not operational. The alarm does not distinguish between the individual power supplies, so onsite information about the conditions is necessary for troubleshooting.

Clear the BATFAIL Alarm


Step 1 At the site, determine which battery is not present or operational.

Step 2 Remove the power cable from the faulty supply.

If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country to report a Service-Affecting (SA) problem.


2.7.42  BKUPMEMP

Default Severity: Critical (CR), Service-Affecting (SA)


Note The severity is Minor (MN), Non-Service-Affecting (NSA) for SBY TCC2/TCC2P card.


SDH Logical Object: EQPT

The Primary Nonvolatile Backup Memory Failure alarm refers to a problem with the TCC2/TCC2P card flash memory. This alarm is raised on ACT/SBY TCC2/TCC2P cards. The alarm occurs when the TCC2/TCC2P card is in active or standby state and has one of four problems:

Failure to format a flash partition.

Failure to write a file to a flash partition.

Problem at the driver level.

Code volume fails cyclic redundancy checking (CRC, a method to verify for errors in data transmitted to the TCC2/TCC2P card).

The BKUPMEMP alarm can also cause the "EQPT" alarm on page 2-85. If the EQPT alarm is caused by BKUPMEMP, complete the following procedure to clear the BKUPMEMP and the EQPT alarm.

Clear the BKUPMEMP Alarm


Step 1 Verify that both TCC2/TCC2P cards are powered and enabled by confirming lighted ACT/SBY LEDs on the TCC2/TCC2P cards.

Step 2 Determine whether the active or standby TCC2/TCC2P card has the alarm.

Step 3 If both cards are powered and enabled, reset the TCC2/TCC2P card where the alarm is raised. If the card is the active TCC2/TCC2P card, complete the "Reset an ActiveTCC2/TCC2P Card and Activate the Standby Card" procedure.
Wait ten minutes to verify that the card you reset completely reboots and becomes the standby card. The ACT/STBY LED of this card should be amber and the newly active TCC2/TCC2P card LED should be green.
If the card is the standby TCC2/TCC2P card, complete the "Reset the Standby TCC2/TCC2P Card" procedure.

Step 4 If the reset TCC2/TCC2P card has not rebooted successfully, or the alarm has not cleared, log into the Cisco Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country. If the Technical Support technician tells you to reseat the card, complete the "Remove and Reinsert (Reseat) Any Card" procedure. If the Technical Support technician tells you to remove the card and reinstall a new one, follow the "Physically Replace a Traffic Card" procedure.


2.7.43  CARLOSS (CE100T, CE1000)

Default Severity: Major (MJ), Service-Affecting (SA)

SDH Logical Objects: CE100T, CE1000

The Carrier Loss alarm is raised on CE-Series cards in Mapper mode when the port is In-Service (IS) state and if there is no carrier signal. Circuit need not be present to raise the alarm. In releases prior to 6.01 the Carrier Loss alarm is raised on CE-100T-8 cards in Mapper mode when there is a circuit failure due to link integrity. It does not get raised when a user simply puts the port in the In-Service and Normal (IS-NR) service state.


Note For more information about Ethernet cards, refer to the Cisco ONS 15454 and Cisco ONS 15454 SDH Ethernet Card Software Feature and Configuration Guide.


Clear the CARLOSS (CE100T, CE1000) Alarm


Step 1 Complete the "Clear the CARLOSS (G1000) Alarm" procedure. However, rather than checking for a TPTFAIL (G1000) at the end of the procedure, check for a "TPTFAIL (CE100T, CE1000)" alarm on page 2-247.

Step 2 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country in order to report a Service-Affecting (SA) problem.


2.7.44  CARLOSS (E100T, E1000F)

Default Severity: Major (MJ), Service-Affecting (SA)

SDH Logical Objects: E100T, E1000F

A Carrier Loss alarm on the LAN E-Series Ethernet card is the data equivalent of the "LOS (STM1E, STMN)" alarm on page 2-161. The Ethernet card has lost its link and is not receiving a valid signal. The most common causes of the CARLOSS alarm are a disconnected cable, an Ethernet Gigabit Interface Converter (GBIC) fiber connected to an optical card rather than an Ethernet device, or an improperly installed Ethernet card. Ethernet card ports must be enabled for CARLOSS to occur. CARLOSS is declared after no signal is received for approximately 2.5 seconds.

CARLOSS also occurs after the restoration of a node database. In this instance, the alarm clears approximately 30 seconds after the node reestablishes Spanning Tree Protocol (STP). Reestablishment applies to the E-Series Ethernet cards but not to the G-Series card. The G-Series card does not use STP and is not affected by STP reestablishment.


Note For more information about Ethernet cards, refer to the Cisco ONS 15454 and Cisco ONS 15454 SDH Ethernet Card Software Feature and Configuration Guide.


Clear the CARLOSS (E100T, E1000F) Alarm


Step 1 Verify that the fiber cable is properly connected and attached to the correct port. For more information about fiber connections and terminations, refer to the "Install Cards and Fiber-Optic Cable" chapter in the Cisco ONS 15454 SDH Procedure Guide.


Caution Always use the supplied electrostatic discharge wristband when working with a powered ONS 15454 SDH. Plug the wristband cable into the ESD jack located on the middle-right outside edge of the shelf assembly.

Step 2 If the fiber cable is properly connected and attached to the port, verify that the cable connects the card to another Ethernet device and is not misconnected to an STM-N card. For more information about fiber connections and terminations, refer to the "Install Cards and Fiber-Optic Cable" chapter in the Cisco ONS 15454 SDH Procedure Guide.

Step 3 If no misconnection to an STM-N card exists, verify that the transmitting device is operational. If not, troubleshoot the device.

Step 4 If the alarm does not clear, use an Ethernet test set to determine whether a valid signal is coming into the Ethernet port. For specific procedures to use the test set equipment, consult the manufacturer.

Step 5 If a valid Ethernet signal is not present and the transmitting device is operational, replace the fiber cable connecting the transmitting device to the Ethernet port. To do this, refer to the "Install Cards and Fiber-Optic Cable" chapter in the Cisco ONS 15454 SDH Procedure Guide.

Step 6 If a valid Ethernet signal is present, complete the "Remove and Reinsert (Reseat) Any Card" procedure for the Ethernet card.

Step 7 If the alarm does not clear, complete the "Physically Replace a Traffic Card" procedure for the Ethernet card.


Note When you replace a card with the identical type of card, you do not need to make any changes to the database.


Step 8 If a CARLOSS alarm repeatedly appears and clears, use the following steps to examine the layout of your network to determine whether the Ethernet circuit is part of an Ethernet manual cross-connect.

An Ethernet manual cross-connect is used when another vendor's equipment sits between ONS 15454 SDHs, and the open systems interconnect/target identifier address resolution protocol (OSI/TARP)-based equipment does not allow tunneling of the ONS 15454 SDH TCP/IP-based DCC. To circumvent a lack of continuous DCC, the Ethernet circuit is manually cross connected to a channel riding through the non-ONS network.

If the reporting Ethernet circuit is part of an Ethernet manual cross-connect, then the reappearing alarm could be a result of mismatched circuit sizes in the set up of the manual cross-connect. Determine this by completing the following steps. If the Ethernet circuit is not part of a manual cross-connect, the following steps do not apply.

a. Right-click anywhere in the row of the CARLOSS alarm.

b. Click Select Affected Circuits in the shortcut menu that appears.

c. Record the information in the type and size columns of the highlighted circuit.

d. From the examination of the layout of your network, determine which ONS 15454 SDH node and card are hosting the Ethernet circuit at the other end of the Ethernet manual cross-connect and complete the following substeps:

Log into the ONS 15454 SDH at the other end of the Ethernet manual cross-connect.

Double-click the Ethernet card that is part of the Ethernet manual cross-connect.

Click the Circuits tab.

Record the information in the type and size columns of the circuit that is part of the Ethernet manual cross-connect. The Ethernet manual cross-connect circuit connects the Ethernet card to an STM-N card at the same node.

e. Use the information you recorded to determine whether the two Ethernet circuits on each side of the Ethernet manual cross-connect have the same circuit size.

If one of the circuit sizes is incorrect, complete the "Delete a Circuit" procedure and reconfigure the circuit with the correct circuit size. For procedures, refer to the "Create Circuits and Tunnels" chapter in the Cisco ONS 15454 SDH Procedure Guide.

Step 9 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport for more information or log into http://www.cisco.com/warp/public/687/Directory/DirTAC.shtml to obtain a directory of toll-free Technical Support numbers for your country in order to report a Service-Affecting (SA) problem.


2.7.45  CARLOSS (EQPT)

Default Severity: Major (MJ), Service-Affecting (SA)

SDH Logical Object: EQPT

The Carrier Loss Equipment alarm occurs when the ONS 15454 SDH and the workstation hosting CTC do not have a TCP/IP connection. CARLOSS is a problem involving the LAN or data circuit used by the RJ-45 connector on the TCC2/TCC2P card or the LAN backplane pin connection on the back of the ONS 15454 SDH. The alarm does not involve an Ethernet circuit connected to a port on an Ethernet (traffic) card. The problem is in the connection (usually a LAN problem) and not the CTC or the ONS 15454 SDH.

On TXP_MR_10G, TXP_MR_2.5G, TXPP_MR_2.5G, and MXP_2.5G_10G cards, CARLOSS is also raised against trunk ports when ITU-T G.709 monitoring is turned off.

A TXP_MR_2.5G card can raise a CARLOSS alarm when the payload is incorrectly configured for the 10 Gigabit Ethernet or 1 Gigabit Ethernet payload data types.


Note For more information about MXP and TXP cards, refer to the "Provision Transponder and Muxponder Cards" chapter in the Cisco ONS 15454 DWDM Procedure Guide. For more information about MRC-12 cards and OC192-XFP/STM64-XFP cards, refer to the "Change Card Settings of the Cisco ONS 15454 SDH Procedure Guide.


Clear the CARLOSS (EQPT) Alarm


Step 1 If the reporting card is an MXP, TXP, MRC-12, or OC192-XVP/STM64-XFP card in an ONS 15454 SDH node, verify the data rate configured on the PPM by completing the following steps:

a. Double-click the reporting card.

b. Click the Provisioning > Pluggable Port Modules tabs.

c. View the Pluggable Port Modules area port listing in the Actual Equipment Type column for the card and compare this with the Selected PPM area Rate column contents.

d. If the rate does not match the actual equipment, you must delete and recreate the selected PPM. Select the PPM, click Delete, then click Create and choose the correct rate for the port rate.


Note For more information about provisioning PPMs, refer to the "Provision Transponder and Muxponder Cards" chapter in the Cisco ONS 15454 DWDM Procedure Guide.


Step 2 If the reporting card is an STM-N card, verify connectivity by pinging the ONS 15454 SDH that is reporting the alarm by completing the procedure in the "1.8.8  Verify PC Connection to the ONS 15454 SDH (ping)" section on page 1-107.

Step 3 If the ping is successful, it demonstrates that an active TCP/IP connection exists. Restart CTC by completing the following steps:

a. Exit from CTC.

b. Reopen the browser.

c. Log into CTC.

Step 4 Using optical test equipment, verify that proper receive levels are achieved. (For specific procedures to use the test set equipment, consult the manufacturer.)

Step 5 Verify that the optical LAN cable is properly connected and attached to the correct port. For more information about fiber connections and terminations, refer to the "Install Cards and Fiber-Optic Cable" chapter in the Cisco ONS 15454 SDH Procedure Guide

Step 6 If the fiber cable is properly connected and attached to the port, verify that the cable connects the card to another Ethernet device and is not misconnected to an STM-N card. For more information about fiber connections and terminations, refer to the "Install Cards and Fiber-Optic Cable" chapter in the Cisco ONS 15454 SDH Procedure Guide.

Step 7 If you are unable to establish connectivity, replace the fiber cable with a new known-good cable. To do this, refer to the "Install Cards and Fiber-Optic Cable" chapter of the Cisco ONS 15454 SDH Procedure Guide for procedures.

Step 8 If you are unable to establish connectivity, perform standard network or LAN diagnostics. For example, trace the IP route, verify cable continuity, and troubleshoot any routers between the node and CTC. To verify cable continuity, follow site practices.

Step 9