Upgrade, Add, and Remove Cards and Nodes

note.gif

Noteblank.gif The terms "Unidirectional Path Switched Ring" and "UPSR" may appear in Cisco literature. These terms do not refer to using Cisco ONS 15xxx products in a unidirectional path switched ring configuration. Rather, these terms, as well as "Path Protected Mesh Network" and "PPMN," refer generally to Cisco's path protection feature, which may be used in any topological network configuration. Cisco does not recommend using its path protection feature in any particular topological network configuration.


This chapter provides procedures for adding and removing dense wavelength division multiplexing (DWDM) cards and nodes.

note.gif

Noteblank.gif Unless otherwise specified, “ONS 15454” refers to both ANSI and ETSI shelf assemblies.


Before You Begin

Before performing any of the following procedures, investigate all alarms and clear any trouble conditions. Refer to the Cisco ONS 15454 DWDM Troubleshooting Guide as necessary for general troubleshooting information and alarm or error descriptions.

This section lists the chapter procedures (NTPs). Turn to a procedure to view its tasks (DLPs).

1.blank.gif G107 Remove Permanently or Remove and Replace DWDM Cards—Complete as needed.

2.blank.gif G127 Add an AD-xC-xx.x Card to an OADM Node—Complete as needed.

3.blank.gif G129 Add a DWDM Node—Complete as needed.

4.blank.gif G130 Remove a DWDM Node—Complete as needed.

5.blank.gif G146 Add a Rack and/or Shelf to a Multishelf Node—Complete as needed.

6.blank.gif G147 Delete a Shelf and/or Rack from a Multishelf Node—Complete as needed.

7.blank.gif G173 Convert an OADM Node to a ROADM Node—Complete as needed.

8.blank.gif G176 Convert an Line Amplifier Node to an OADM Node—Complete as needed.

9.blank.gif G182 Convert a Line Amplifier Node to a ROADM Node—Complete as needed.

10.blank.gif G195 Convert a Protected ROADM Node from two Separate Nodes to a Single Multishelf Node—Complete as needed.

11.blank.gif G177 Upgrade ANS Parameters on a DWDM Node—Complete as needed.

NTP-G107 Remove Permanently or Remove and Replace DWDM Cards

 

Purpose

This procedure permanently removes or removes and replaces DWDM cards installed in the ONS 15454 shelf and rack.

Tools/Equipment

None

Prerequisite Procedures

G30 Install the DWDM Cards

G179 Install the TXP, MXP, GE_XP, 10GE_XP, GE_XPE, 10GE_XPE, ADM-10G, and OTU2_XP Cards

Required/As Needed

As needed

Onsite/Remote

Onsite

Security Level

Provisioning or higher

caut.gif

Caution blank.gif Removing and replacing cards can be traffic affecting.

caut.gif

Caution blank.gif Do not use this procedure to replace a TCC2 or TCC2P card.


Step 1blank.gif Complete the G46 Log into CTC.

note.gif

Noteblank.gif If you cannot log into Cisco Transport Controller (CTC) and you need to remove a card, remove the card as described in Step 6. After you log into CTC, troubleshoot the mismatched equipment alarm (MEA) with the Cisco ONS 15454 DWDM Troubleshooting Guide.


Step 2blank.gif Click the Alarms tab.

a.blank.gif Verify that the alarm filter is not on. See the G128 Disable Alarm Filtering as necessary.

b.blank.gif Verify that no unexplained alarms appear on the network. If alarms appear, investigate and resolve them before continuing. Refer to the Cisco ONS 15454 DWDM Troubleshooting Guide for procedures.

Step 3blank.gif If you are removing and replacing a card, go to Step 5.

Step 4blank.gif If you are permanently removing a card, go to Step 11.

Step 5blank.gif To remove and replace a card, complete the following tasks, as needed:

    • The circuits traversing through the card that needs to be replaced (for example, an amplifier) need to be protection switched. For instance, if the card you want to replace is an active transponder (TXP) or muxponder (MXP) in a Y-cable protection group, complete the G179 Apply a Force Y-Cable or Splitter Protection Switch to force traffic away from the TXP or MXP that you will remove. If the card you want to replace is the standby TXP or MXP in a Y-cable protection group, complete the G182 Apply a Lockout to prevent traffic from switching to the TXP or MXP that you will remove. See the Cisco ONS 15454 Procedure Guide or the Cisco ONS 15454 SDH Procedure Guide for other types of protection switching (path protection, BLSR, optical, and electrical).
    • If the card is used as a node timing reference, complete the G112 Change the Node Timing Reference to change the timing reference to a card that will not be removed.
    • If the card is an OSCM or OSC-CSM with an optical service channel (OSC) or TXP, MXP, GE_XP, 10GE_XP, GE_XPE, 10GE_XPE, ADM-10G, and OTU2_XP cards with generic communications channel (GCC) termination, complete the G85 Modify or Delete OSC Terminations, DCC/GCC Terminations, and Provisionable Patchcords to delete the termination and recreate it on a card that will not be removed.

Step 6blank.gif Physically remove the card:

a.blank.gif Disconnect any cables.

b.blank.gif Open the card latches/ejectors.

c.blank.gif Use the latches/ejectors to pull the card forward and away from the shelf.

Step 7blank.gif Insert the new card using one of the following procedures as applicable:

Step 8blank.gif Complete the G34 Install Fiber-Optic Cables on DWDM Cards and DCUs.

Step 9blank.gif Complete the following tasks or procedures, as needed:

Step 10blank.gif Go to Step 13.

Step 11blank.gif To permanently remove a card, complete the following tasks:

blank.gif Disconnect and remove any cables, patchcords, and attenuators attached to the card.

blank.gif Open the card latches/ejectors.

blank.gif Use the latches/ejectors to pull the card forward and away from the shelf.

Step 12blank.gif If the card you are removing is an OSCM, OSC-CSM, DWDM Amplifier, or Filter card, complete the following tasks; otherwise, go to Step 13.

Step 13blank.gif Click the Alarms tab.

a.blank.gif Verify that the alarm filter is not on. See the G128 Disable Alarm Filtering as necessary.

b.blank.gif Verify that no unexplained alarms appear on the network. If alarms appear, investigate and resolve them. Refer to the Cisco ONS 15454 DWDM Troubleshooting Guide for procedures.

Stop. You have completed this procedure.


 

DLP-G254 Place Amplifier Ports Out of Service

 

Purpose

This task places OPT-BST, OPT-BST-E, OPT-BST-L, OPT-PRE, OPT-AMP-L, or OPT-AMP-17-C card ports out of service in preparation for card removal.

Tools/Equipment

None

Prerequisite Procedures

G46 Log into CTC

Required/As Needed

As needed

Onsite/Remote

Onsite or remote

Security Level

Provisioning or higher


Step 1blank.gif On the shelf graphic in CTC, double-click the OPT-BST, OPT-BST-E, OPT-BST-L, OPT-PRE, OPT-AMP-L, or OPT-AMP-17-C card with the ports that you want to put out of service.

Step 2blank.gif Click the Provisioning > Optical Line > Parameters tabs.

Step 3blank.gif In the Admin State column for the card’s ports, choose OOS,MT (ANSI) or Locked,disabled (ETSI) for each port that does not have an OOS-MA,DSBLD or Locked-enabled,disabled service state.

Step 4blank.gif Click Apply.

Step 5blank.gif In the confirmation dialog box, click Yes.

Step 6blank.gif Click the Provisioning > Opt Apli Line > Parameters tabs.

Step 7blank.gif In the Admin State column for the card’s ports, choose OOS,MT or IS,AINS (ANSI) or Locked,maintenance or unlocked,automaticinservice (ETSI) for each port that does not have an OOS-MA,DSBLD or Locked,disabled service state.

Step 8blank.gif Click Apply.

Step 9blank.gif In the confirmation dialog box, click Yes.

Step 10blank.gif Return to your originating procedure (NTP).


 

DLP-G318 Place Amplifier Ports In Service

 

Purpose

This task places OPT-BST, OPT-BST-E, OPT-BST-L, OPT-PRE, OPT-AMP-L or OPT-AMP-17-C card ports in service.

Tools/Equipment

None

Prerequisite Procedures

G46 Log into CTC

Required/As Needed

As needed

Onsite/Remote

Onsite or remote

Security Level

Provisioning or higher


Step 1blank.gif On the shelf graphic in CTC, double-click the OPT-BST, OPT-BST-E, OPT-BST-L, OPT-PRE, OPT-AMP-L, or OPT-AMP-17-C card with the ports that you want to put in service.

Step 2blank.gif Click the Provisioning > Optical Line > Parameters tabs.

Step 3blank.gif In the Admin State column for the card’s ports, choose IS,AINS (ANSI) or Unlocked-automaticInService (ETSI) for Port 1 (COM-RX) of the OPT-PRE card (or OPT-AMP-L or OPT-AMP-17-C cards provisioned in OPT-PRE mode), or Port 2 (OSC-RX) and Port 3 (COM-TX) of the OPT-BST, OPT-BST-E, or OPT-BST-L cards (or OPT-AMP-L or OPT-AMP-17-C cards provisioned in OPT-LINE mode).

Step 4blank.gif Click Apply.

Step 5blank.gif In the confirmation dialog box, click Yes.

Step 6blank.gif Return to your originating procedure (NTP).


 

NTP-G127 Add an AD-xC-xx.x Card to an OADM Node

 

Purpose

This procedure adds an AD-xC-xx.x card to an optical add/drop multiplexing (OADM) node.

Tools/Equipment

None

Prerequisite Procedures

Chapter 6, “Turn Up a Network”

A Cisco TransportPlanner OADM site plan recalculated for the new OADM card

Required/As Needed

As needed

Onsite/Remote

Onsite

Security Level

Provisioning or higher

note.gif

Noteblank.gif Do not begin this procedure until the Cisco TransportPlanner site plan has been recalculated with the new AD-xC-xx.x card added to the OADM node.


caut.gif

Caution blank.gif This procedure will affect the service of unprotected circuits that pass through the OADM node.


Step 1blank.gif Complete the G46 Log into CTC at a node in the OADM network.

Step 2blank.gif In node view (single-shelf mode) or multishelf view (multishelf mode), display the OADM node where you will add the card.

Step 3blank.gif Click the Circuits tab.

Step 4blank.gif Make a list of all optical channel network connections (OCHNCs) and/or optical channel client connections (OCHCCs) that are carried on the express path for both the Side B-to-Side A and Side A-to-Side B directions.

Step 5blank.gif For OCHNCs and/or OCHCCs identified in Step 4 that are routed on the active path of a splitter or Y-cable protection group, force the traffic to the protect path in the opposite side of the ring using the G179 Apply a Force Y-Cable or Splitter Protection Switch.

Step 6blank.gif Click the Circuits tab.

Step 7blank.gif Complete the following steps for all OCHNCs and/or OCHCCs carried on the express path that were identified in Step 4:

a.blank.gif Choose the OCHNC or OCHCC circuit(s) and click Edit. (To choose multiple circuits, press the Shift key while you click the circuits.)

b.blank.gif In the Edit Circuit dialog box, click the State tab.

c.blank.gif In the State field on the right, choose OOS,DSBLD (ANSI) or Locked,disabled (ETSI) from the drop-down list.

d.blank.gif Click Apply.

e.blank.gif Repeat Steps a through d for each OCHNC or OCHCC circuit.

Step 8blank.gif From the Tools menu, choose Open TL1 Connection.

Step 9blank.gif In the Select Node dialog box, choose the OADM node where you will add the AD-xC-xx.x card and click OK.

Step 10blank.gif In the TL1 dialog box, use the DLT-OCHNC command to delete the OCHNC cross-connects for the express path OCHNC listed in Step 4blank.gif, using the following format:

DLT-OCHNC:[<TID>]:<SRC>,<DST>:<CTAG>:::[CKTID=<CKTID>],[CMDMDE=<CMDMDE>];

where:

    • <SRC> is the access identifier from the Channel section in a two-way wavelength.
    • <DST> is the destination access identifier from the LINEWL section in a two-way wavelength.
    • <CKTID> is the cross-connect ID. The default is Blank or None. CKTD is a string of ASCII characters. The maximum length is 48. If CKTID is empty or null, the CKTID field will not be displayed.
    • <CMDMDE> is the command execution mode. NORM mode is the default behavior for all commands but you can specify FRCD to force the system to override a state in which the command would normally be denied.

For additional information, including valid command values, refer to the Cisco ONS SONET TL1 Command Guide or the Cisco ONS 15454 SDH and Cisco ONS 15600 SDH TL1 Command Guide.

Step 11blank.gif In the TL1 dialog box, use the DLT-OCHCC command to delete the OCHCC cross-connects for the express path OCHCC listed in Step 4blank.gif, using the following format:

DLT-OCHCC:[<TID>]:<AID>:<CTAG>[:::CKTID=<CKTID>],[CMDMDE=<CMDMDE>];

where:

    • <AID> is the access identifier from the Channel section i in a two-way wavelength.
    • <CKTID> is the cross-connect ID. The default is Blank or None. CKTD is a string of ASCII characters. The maximum length is 48. If CKTID is empty or null, the CKTID field will not be displayed.
    • <CMDMDE> is the command execution mode. NORM mode is the default behavior for all commands but you can specify FRCD to force the system to override a state in which the command would normally be denied.

For additional information, including valid command values, refer to the Cisco ONS SONET TL1 Command Guide or the Cisco ONS 15454 SDH and Cisco ONS 15600 SDH TL1 Command Guide.

Step 12blank.gif Click Close to close the TL1 dialog box.

Step 13blank.gif In node view (single-shelf mode) or multishelf view (multishelf mode), click the Provisioning > WDM-ANS > Internal Patchcords tabs.

Step 14blank.gif Highlight the two express connections that carry the deleted circuits passing through the node. (The express connections are the only ones connecting an EXP_TX port on the last Side A OADM card, with an EXP_RX port on the first Side B OADM card.)

Step 15blank.gif Click Delete.

Step 16blank.gif Remove the physical express cables between the EXP_TX and EXP_RX ports specified in Step 14.

Step 17blank.gif Insert the new AD-xC-xx.x card in the slot identified by your Cisco TransportPlanner site plan.

Step 18blank.gif Complete the G34 Install Fiber-Optic Cables on DWDM Cards and DCUs for the OADM node, following the new internal connections table generated by Cisco TransportPlanner.

Step 19blank.gif Complete the G152 Create and Verify Internal Patchcords.

Step 20blank.gif Import the recalculated OADM site parameters. See the G143 Import the Cisco TransportPlanner NE Update Configuration File.

Step 21blank.gif In node view (single-shelf mode) or multishelf view (multishelf mode), click the Provisioning > WDM-ANS > Port Status tabs.

Step 22blank.gif Click Launch ANS.

Step 23blank.gif From the Tools menu, choose Open TL1 Connection.

Step 24blank.gif In the Select Node dialog box, choose the OADM node and click OK.

Step 25blank.gif In the TL1 dialog box, use the DLT-OCHNC command to delete the OCHNC cross-connects for the express path OCHNC listed in Step 14blank.gif, using the following format:

DLT-OCHNC:[<TID>]:<SRC>,<DST>:<CTAG>:::[CKTID=<CKTID>],[CMDMDE=<CMDMDE>];

where:

    • <SRC> is the access identifier from the Channel section in a two-way wavelength.
    • <DST> is the destination access identifier from the LINEWL section in a two-way wavelength.
    • <CKTID> is the cross-connect ID. The default is Blank or None. CKTD is a string of ASCII characters. The maximum length is 48. If CKTID is empty or null, the CKTID field will not be displayed.
    • <CMDMDE> is the command execution mode. NORM mode is the default behavior for all commands but you can specify FRCD to force the system to override a state in which the command would normally be denied.

For additional information, including valid command values, refer to the Cisco ONS SONET TL1 Command Guide or the Cisco ONS 15454 SDH and Cisco ONS 15600 SDH TL1 Command Guide.

Step 26blank.gif In the TL1 dialog box, use the DLT-OCHCC command to delete the OCHCC cross-connects for the express path OCHCC listed in Step 14blank.gif, using the following format:

DLT-OCHCC:[<TID>]:<AID>:<CTAG>[:::CKTID=<CKTID>], [CMDMDE=<CMDMDE>]

where:

    • <AID> is the access identifier from the Channel section.
    • <CKTID> is the cross-connect ID. The default is Blank or None. CKTD is a string of ASCII characters. The maximum length is 48. If CKTID is empty or null, the CKTID field will not be displayed.
    • <CMDMDE> is the command execution mode. NORM mode is the default behavior for all commands but you can specify FRCD to force the system to override a state in which the command would normally be denied.
    • <PST> is the Primary state, which indicates the current overall service condition of an entity. The default is IS (in service).
    • <SST> s the Secondary state, which provides additional information pertaining to PST and PSTQ. The default is AINS.

For additional information, including valid command values, refer to the Cisco ONS SONET TL1 Command Guide or the Cisco ONS 15454 SDH and Cisco ONS 15600 SDH TL1 Command Guide.

Step 27blank.gif Click Close to close the TL1 dialog box.

Step 28blank.gif In node view (single-shelf mode) or multishelf view (multishelf mode), click the Circuits tab.

Step 29blank.gif Complete the following steps for all OCHNCs and/or OCHCCs set to OOS,DSBLD (ANSI) or Locked,disabled (ETSI) in Step 7:

a.blank.gif Choose the OCHNC or OCHCC circuit(s) and click Edit. To choose multiple circuits, press the Shift key while you click the circuits.

b.blank.gif In the Edit Circuit dialog box, click the State tab.

c.blank.gif In the State field on the right, choose IS,AINS (ANSI) or Unlocked,automaticInService (ETSI) from the drop-down list.

d.blank.gif Click Apply, and then click OK.

Step 30blank.gif Complete the G180 Clear a Manual or Force Y-Cable or Splitter Protection Switch for OCHNCs and/or OCHCCs that were switched to the opposite side of the ring as part of a splitter or Y-cable protection group to return the traffic to its condition before the card was added.

Stop. You have completed this procedure.


 

NTP-G129 Add a DWDM Node

 

Purpose

This procedure adds a DWDM node to an existing DWDM network.

Tools/Equipment

None

Prerequisite Procedures

Chapter 6, “Turn Up a Network”

A Cisco TransportPlanner network plan recalculated for the new node

Required/As Needed

As needed

Onsite/Remote

Onsite

Security Level

Provisioning or higher

note.gif

Noteblank.gif Do not begin this procedure until the Cisco TransportPlanner network plan has been updated and recalculated with the new DWDM node.


note.gif

Noteblank.gif This procedures assumes that all turn-up procedures provided in Chapter 3, “Turn Up a Node” have been completed at the node that will be added. If they have not been completed, do not continue. Complete the turn-up procedures at the new node before you complete this procedure.


caut.gif

Caution blank.gif To complete this procedure, a span will be disconnected where the new node is added. This will affect the service of any unprotected circuits that pass through that span.


Step 1blank.gif At the node that will be added, complete the G51 Verify DWDM Node Turn Up. If the node has not been turned up, do not continue. Complete the relevant procedures in Chapter 3, “Turn Up a Node” and “Perform Node Acceptance Tests,” then begin this procedure again.

Step 2blank.gif If the Cisco TransportPlanner network design has not been updated and recalculated for the new node and client services, update and recalculate it now, following the procedures in the Cisco TransportPlanner documentation.

Step 3blank.gif Identify the fiber spans that must be disconnected to insert the new node.

Step 4blank.gif Complete the G46 Log into CTC at a DWDM node that is active on the network where you want to add the new DWDM node.

Step 5blank.gif From the View menu, choose Go to Network View.

Step 6blank.gif In network view, click the Circuits tab.

Step 7blank.gif Identify the OCHCCs and/or OCHNCs and/or OCHTRAILs that are carried on the fiber span express path that you identified in Step 3 in both the Side B-to-Side A and Side A-to-Side B directions.

Step 8blank.gif If the OCHCC and/or OCHNC and/or OCHTRAIL circuit is on the active path and is protected by a splitter or Y-cable protection group, complete the G179 Apply a Force Y-Cable or Splitter Protection Switch to force traffic away from the span where the node will be added. If not, continue with Step 9.

Step 9blank.gif For each circuit identified in Step 7 that was not switched in Step 8 (unprotected circuits), complete the following steps:

a.blank.gif In network view, select the OCHNC and/or OCHCC and/or OCHTRAIL circuit and click Edit.

b.blank.gif In the Edit Circuit dialog box, click the State tab.

c.blank.gif In the State field on the right, choose OOS,DSBLD (ANSI) or Locked,disabled (ETSI) from the drop-down list.

d.blank.gif Click Apply, then click OK.

Step 10blank.gif Remove the fibers from the cards at the adjacent nodes that will connect to the new node.

Step 11blank.gif Install the fibers from the adjacent nodes that will connect to the new node using the G34 Install Fiber-Optic Cables on DWDM Cards and DCUs.

Step 12blank.gif Update the ANS parameters at the adjacent nodes:

a.blank.gif Display an adjacent node in node view.

b.blank.gif Complete the G143 Import the Cisco TransportPlanner NE Update Configuration File to load the new NE Update file onto the node.

c.blank.gif Complete the G37 Run Automatic Node Setup to recalculate the ANS parameters at the node.

d.blank.gif Display the next adjacent node in node view.

e.blank.gif Repeat Steps b and c for the second adjacent node.

Step 13blank.gif Display the new node in node view.

Step 14blank.gif Log out of CTC and log back into a node in the network.

Step 15blank.gif From the View menu, choose Go to Network View to display the nodes. The new node should appear in the network map. Wait for a few minutes to allow all the nodes to appear.

Step 16blank.gif Click the Circuits tab and wait for all the circuits to appear, including spans. Count the number of incomplete circuits.

Step 17blank.gif In network view, right-click the new node and choose Update Circuits With New Node from the shortcut menu. Wait for the confirmation dialog box to appear. Verify that the number of updated circuits that appears in the dialog box is correct.

note.gif

Noteblank.gif If the circuits take more than a minute to appear, log out, then log back in.


Step 18blank.gif Click the Circuits tab and verify that no incomplete circuits appear.

Step 19blank.gif Repeat Step 9 to change the circuits placed in OOS,DSBLD (ANSI) or Locked,disabled (ETSI) back in service by choosing IS-AINS (ANSI) or Unlocked,automaticInService (ETSI) in the State drop-down list.

Step 20blank.gif Complete the G180 Clear a Manual or Force Y-Cable or Splitter Protection Switch for the circuits that were switched in Step 8 to return the traffic to its original paths.

Step 21blank.gif Complete the G105 Provision Optical Channel Network Connections to create new circuits.

Stop. You have completed this procedure.


 

NTP-G130 Remove a DWDM Node

 

Purpose

This procedure removes a node from a DWDM network.

Tools/Equipment

None

Prerequisite Procedures

A Cisco TransportPlanner network plan recalculated for the new topology.

Required/As Needed

As needed

Onsite/Remote

Onsite

Security Level

Provisioning or higher

note.gif

Noteblank.gif During this procedure, you will use TL1 commands to delete and recreate OCHNC or OCHCC cross-connects. You might need to refer to the Cisco ONS SONET TL1 Command Guide or the Cisco ONS 15454 SDH and Cisco ONS 15600 SDH TL1 Command Guide.


caut.gif

Caution blank.gif This procedure will affect the service of unprotected circuits that pass through the span where the node will be removed.


Step 1blank.gif If the Cisco TransportPlanner network design has not been updated and recalculated with the node removed, update and recalculate the design now by following the procedures in the Cisco TransportPlanner documentation.

Step 2blank.gif Complete the G46 Log into CTC at the DWDM target node that will be removed.

Step 3blank.gif Click the Circuits tab.

Step 4blank.gif Identify all the OCHNCs and OCHCCs that are passing through or are added and dropped at the node that will be removed.

Step 5blank.gif Delete the OCHNCs and OCHCCs identified in Step 4 that terminate (add/drop) on the target DWDM node. See the G347 Delete Optical Channel Client Connections and the G106 Delete Optical Channel Network Connections to delete OCHCCs and OCHNCs, respectively.

Step 6blank.gif For the protected pass through circuits on the target node, perform Step 7. Else, go to Step 10.

note.gif

Noteblank.gif Non-protected pass through circuits need not be modified or deleted.


Step 7blank.gif If the OCHNC and OCHCC circuits pass through the target node on the active path and are protected by a splitter or Y-cable protection group, navigate to an adjacent node connected to the target node and complete the G179 Apply a Force Y-Cable or Splitter Protection Switch to force the traffic away from the node that will be deleted. Otherwise, continue with Step 8.

Step 8blank.gif Complete the following steps for the protected pass through circuits:

a.blank.gif Select the OCHNCs or OCHCCs and click Edit.

b.blank.gif In the Edit Circuit dialog box, click the State tab.

c.blank.gif In the State field, choose OOS,DSBLD (ANSI) or Locked,disabled (ETSI) from the drop-down list.

d.blank.gif Click Apply, then click OK.

Step 9blank.gif Complete the following steps to delete the cross-connects on the target node for each circuit placed in the OOS,DSBLD (ANSI) or Locked,disabled (ETSI) state in Step 8blank.gif:

a.blank.gif From the Tools menu, choose Open TL1 Connection.

b.blank.gif In the Select Node dialog box, select the new node and click OK.

c.blank.gif In the TL1 dialog box, use the DLT-OCHNC command to delete the OCHNC cross-connects for each unprotected pass-through circuit as follows:

DLT-OCHNC:[<TID>]:<SRC>,<DST>:<CTAG>:::[CKTID=<CKTID>], [CMDMDE=<CMDMDE>];

where:

blank.gif <SRC> is the source access identifier from the Channel section in a two-way wavelength.

blank.gif <DST> is the destination access identifier from the LINEWL section in a two-way wavelength.

blank.gif <CKTID> is the cross-connect ID. The default is Blank or None. CKTD is a string of ASCII characters. The maximum length is 48. If CKTID is empty or null, the CKTID field will not be displayed.

blank.gif <CMDMDE> is the command execution mode. NORM mode is the default behavior for all commands but you can specify FRCD to force the system to override a state in which the command would normally be denied.

For additional information, including valid command values, refer to the Cisco ONS SONET TL1 Command Guide or the Cisco ONS 15454 SDH and Cisco ONS 15600 SDH TL1 Command Guide.

d.blank.gif Click Close to close the TL1 dialog box.

Step 10blank.gif Remove the fibers from the target node, and reconnect the fibers to the adjacent nodes.
Note that once the fibers are rerouted, the non-protected pass through circuits will go to OOS-PARTIAL (ANSI) or Locked-partial (ETSI) state.

Step 11blank.gif Complete the following steps to update the ANS parameters at the adjacent nodes:

a.blank.gif Display an adjacent node in node view.

b.blank.gif Complete the G143 Import the Cisco TransportPlanner NE Update Configuration File to load the new NE Update file onto the node.

c.blank.gif Complete the G37 Run Automatic Node Setup to recalculate the ANS parameters at the node.

d.blank.gif Display the next adjacent node in node view.

e.blank.gif Repeat Steps b and c for the second adjacent node.

Step 12blank.gif Repeat Step 8 to change the circuits placed in OOS,DSBLD (ANSI) or Locked,disabled (ETSI) back in service by changing the Target Circuit Admin State field to IS-AINS (ANSI) or Unlocked,AutomaticInService (ETSI).

Step 13blank.gif Complete the G180 Clear a Manual or Force Y-Cable or Splitter Protection Switch for the OCHNCs and OCHCCs that were switched in Step 7.

Step 14blank.gif To discover the non-protected pass though circuits that are in the OOS-PARTIAL (ANSI) or Locked-partial (ETSI) state after completing Step 10, select the circuit and choose Tools > Circuits > Reconfigure Circuits from the menu bar. The Reconfigure Circuits dialog box is displayed; click Yes.

Stop. You have completed this procedure.


 

NTP-G146 Add a Rack and/or Shelf to a Multishelf Node

 

Purpose

This procedure adds a rack and/or subtending shelf to a multishelf node.

Tools/Equipment

None

Prerequisite Procedures

One of the following:

Chapter 3, “Turn Up a Node”

Required/As Needed

As needed

Onsite/Remote

Onsite

Security Level

Provisioning or higher

note.gif

Noteblank.gif Each shelf you want to add to a multishelf configuration must have network connectivity. For more information, see Chapter2, “Connect the PC and Log into the GUI”



Step 1blank.gif Complete the G46 Log into CTC at the multishelf DWDM node where you want to add a shelf.

Step 2blank.gif To add a rack, in multishelf view right-click the gray area and choose Add Rack. If you do not need to add a rack, continue with Step 3blank.gif.

Step 3blank.gif To add a shelf, in multishelf view right-click the white space inside the rack and choose Add Shelf.

Step 4blank.gif In the Shelf ID Selection dialog box, choose a shelf ID from the drop-down list.

Step 5blank.gif Click OK. The shelf appears in the multishelf view.

Step 6blank.gif Complete the G46 Log into CTC at the new subtending shelf.

Step 7blank.gif In multishelf view, click the Provisioning > General > Multishelf Config tabs.

Step 8blank.gif Click Enable as Subtended Shelf.

Step 9blank.gif From the Shelf ID drop-down list, choose the shelf ID that you created in Step 4.

Step 10blank.gif Click Apply.

Step 11blank.gif In the confirmation dialog box, click Yes to reboot the shelf. The CTC view changes to network view and the node icon changes to gray. (This might take several minutes.)

Step 12blank.gif If you are connecting the new subtending shelf to the Ethernet Adapter Panel (EAP), complete the following steps. If not, continue with Step 13.

a.blank.gif Using a cross-over (CAT 5) LAN cable, plug one connector into the RJ-45 front panel port of the subtending shelf TCC2/TCC2P card in Slot 7 and plug the other end into the SSC port on the left patch panel.

b.blank.gif Using a cross-over (CAT 5) LAN cable, plug one connector into the RJ-45 front panel port of the subtending shelf TCC2/TCC2P card in Slot 11 and plug the other end into the SSC port on the right patch panel.

Step 13blank.gif If you are connecting the subtending shelf to the Catalyst 2950 switch, complete the following steps. If not, continue with Step 14.

a.blank.gif Plug one end of a cross-over (CAT-5) LAN cable into the RJ-45 front panel port of the subtending shelf TCC2/TCC2P card in Slot 7 and plug the other end into Port 2 of the first Catalyst 2950.

b.blank.gif Plug one end of a cross-over (CAT-5) LAN cable into the RJ-45 front panel port of the subtending shelf TCC2/TCC2P card in Slot 11 and plug the other end into Port 2 of the backup Catalyst 2950.

Step 14blank.gif Repeat Steps 3 through 13 for each subtending shelf in the multishelf configuration.

Stop. You have completed this procedure.


 

NTP-G147 Delete a Shelf and/or Rack from a Multishelf Node

 

Purpose

This procedure deletes a shelf and/or rack from a multishelf node.

Tools/Equipment

None

Prerequisite Procedures

One of the following:

Chapter 3, “Turn Up a Node”

Required/As Needed

As needed

Onsite/Remote

Onsite

Security Level

Provisioning or higher

note.gif

Noteblank.gif You cannot delete a node controller shelf from a multishelf node configuration.



Step 1blank.gif Complete the G46 Log into CTC at the multishelf DWDM node where you want to delete a shelf or rack. If you want to delete a shelf, continue with Step 2. If you want to delete a rack only, go to Step 9.

Step 2blank.gif Complete the following tasks, as needed:

note.gif

Noteblank.gif It is not necessary to delete the cards from the shelf before deleting a shelf.


Step 3blank.gif From the View menu, choose Go to Parent View to return to multishelf view.

Step 4blank.gif Right-click the subtending shelf you want to delete and choose Delete Shelf.

Step 5blank.gif In the confirmation dialog box, click Yes.

Step 6blank.gif To return the deleted shelf to a single-shelf node, you must use the LCD panel:

a.blank.gif Repeatedly press the Status button until Shelf Status appears.

b.blank.gif Repeatedly press the Port button until Controller Status=MS Config appears.

c.blank.gif Press Status again and press Port to set multishelf mode to MS=N.

d.blank.gif Press Status to choose Done.

e.blank.gif Repeatedly press Status until “Save and Reboot?” appears, and then press Slot to choose Apply. This reboots the shelf. A “Saving changes; TCC may reboot” message appears on the LCD.

Step 7blank.gif After the TCC2/TCC2P reboot is complete, complete the following steps to disconnect the removed subtending shelf from the patch panel or Catalyst 2950:

a.blank.gif Remove the cross-over (CAT 5) LAN cable from the RJ-45 front panel port of the TCC2/TCC2P card in Slot 7.

b.blank.gif Remove the cross-over (CAT 5) LAN cable from the RJ-45 front panel port of the TCC2/TCC2P card in Slot 11.

Step 8blank.gif Reconnect the shelf to the LAN through either the backplane or one of the RJ-45 front panel ports of the TCC2/TCC2P cards. For more information, see Chapter2, “Connect the PC and Log into the GUI”

Step 9blank.gif To delete an empty rack from the CTC window, right-click the gray area on the rack graphic and choose Delete Rack.

Stop. You have completed this procedure.


 

NTP-G173 Convert an OADM Node to a ROADM Node

 

Purpose

This procedure converts an OADM node to a ROADM node.

Tools/Equipment

None

Prerequisite Procedures

Chapter 6, “Turn Up a Network”

A Cisco TransportPlanner site plan recalculated for the new ROADM node.

Required/As Needed

As needed

Onsite/Remote

Onsite

Security Level

Provisioning or higher

note.gif

Noteblank.gif Do not begin this procedure until the Cisco TransportPlanner site plan has been recalculated with the new ROADM node. You will import the new NE Update file and run ANS to recalculate the ANS parameters. In addition, you will run ANS at the two adjacent nodes to recalculate the ANS parameters at those nodes.


note.gif

Noteblank.gif During this procedure, you will use TL1 commands to delete and recreate OCHNC or OCHCC cross-connects. You might need to refer to the Cisco ONS SONET TL1 Command Guide or the Cisco ONS 15454 SDH and Cisco ONS 15600 SDH TL1 Command Guide.


caut.gif

Caution blank.gif This procedure will affect the service of unprotected circuits that pass through the OADM node.


Step 1blank.gif Complete the G46 Log into CTC at a node in the OADM network.

Step 2blank.gif In node view (single-shelf mode) or multishelf view (multishelf mode), display the OADM node that you will convert to a ROADM node.

Step 3blank.gif Click the Circuits tab.

Step 4blank.gif Make a list of the following OCHNCs and/or optical channel client connections (OCHCCs) that:

    • Terminate (add/drop) at the node.
    • Pass through the node on the express path for both the Side B-to-Side A and Side A-to-Side B directions.

Step 5blank.gif If OCHNCs and/or OCHCCs identified in Step 4 are routed on the active path of a splitter or Y-cable protection group, complete the following steps. If not, continue with Step 6.

a.blank.gif Display the node containing the TXP, MXP, ADM-10G, GE_XP, 10GE_XP, GE_XPE, 10GE_XPE, or ITU-T line card with the Y-cable or splitter protection.

a.blank.gif Force the traffic to the protect path in the opposite side of the ring using the G179 Apply a Force Y-Cable or Splitter Protection Switch.

Step 6blank.gif In node view, display node that will be converted.

Step 7blank.gif Complete the G347 Delete Optical Channel Client Connections and/or the G106 Delete Optical Channel Network Connections to delete OCHCCs and/or OCHNCs identified in Step 4 that:

    • Terminate (add/drop) at the node.
    • Pass through the node on an unprotected express path for both the Side B-to-Side A and Side A-to-Side B directions.

Step 8blank.gif From the Tools menu, choose Open TL1 Connection.

Step 9blank.gif In the Select Node dialog box, choose the OADM node and click OK.

Step 10blank.gif In the TL1 dialog box, use the DLT-OCHNC command to delete the OCHNC cross-connects for the express path OCHNCs listed in Step 4blank.gif, using the following format:

DLT-OCHNC:[<TID>]:<SRC>,<DST>:<CTAG>:::[CKTID=<CKTID>],[CMDMDE=<CMDMDE>];

where:

    • <SRC> is the source access identifier from the Channel section in a two-way wavelength.
    • <DST> is the destination access identifier from the LINEWL section in a two-way wavelength.
    • <CKTID> is the cross-connect ID. The default is Blank or None. CKTD is a string of ASCII characters. The maximum length is 48. If CKTID is empty or null, the CKTID field will not be displayed.
    • <CMDMDE> is the command execution mode. NORM mode is the default behavior for all commands but you can specify FRCD to force the system to override a state in which the command would normally be denied.

For additional information, including valid command values, refer to the Cisco ONS SONET TL1 Command Guide or the Cisco ONS 15454 SDH and Cisco ONS 15600 SDH TL1 Command Guide.

Step 11blank.gif In the TL1 dialog box, use the DLT-OCHCC command to delete the OCHCC cross-connects for the express path OCHCCs listed in Step 4blank.gif, using the following format:

DLT-OCHCC:[<TID>]:<AID>:<CTAG>[:::CKTID=<CKTID>],[CMDMDE=<CMDMDE>];

where:

    • <AID> is the access identifier from the Facility section.
    • <CKTID> is the cross-connect ID. The default is Blank or None. CKTD is a string of ASCII characters. The maximum length is 48. If CKTID is empty or null, the CKTID field will not be displayed.
    • <CMDMDE> is the command execution mode. NORM mode is the default behavior for all commands but you can specify FRCD to force the system to override a state in which the command would normally be denied.

For additional information, including valid command values, refer to the Cisco ONS SONET TL1 Command Guide or the Cisco ONS 15454 SDH and Cisco ONS 15600 SDH TL1 Command Guide.

Step 12blank.gif Click Close to close the TL1 dialog box.

Step 13blank.gif Delete the internal patchcords:

a.blank.gif In node view (single-shelf mode) or multishelf view (multishelf mode), click the Provisioning > WDM-ANS > Internal Patchcords tabs.

b.blank.gif Highlight all of the internal patchcords.

c.blank.gif Click Delete.

d.blank.gif Click Yes on the confirmation dialog box.

Step 14blank.gif Delete the OSC terminations:

a.blank.gif Click the Provisioning > Comm Channels > OSC tabs.

b.blank.gif Highlight all of the OSC terminations.

c.blank.gif Click Delete.

d.blank.gif Click Yes on the confirmation dialog box.

Step 15blank.gif Remove the cables from all the AD-xC-xx.x and/or AD-xB-xx.x cards.

Step 16blank.gif Remove the AD-xC-xx.x and/or AD-xB-xx.x cards from the shelf.

Step 17blank.gif Remove any amplifier cards (OPT-BST, OPT-PRE) that are installed but not required in the ROADM node.

Step 18blank.gif Install the new ROADM cards in the slots identified by your Cisco TransportPlanner site plan using the G30 Install the DWDM Cards.

Step 19blank.gif Complete the G34 Install Fiber-Optic Cables on DWDM Cards and DCUs for the ROADM node, following the new internal connections table generated by Cisco TransportPlanner.

Step 20blank.gif Complete the G152 Create and Verify Internal Patchcords to recreate the internal patchcords deleted in Step 13.

Step 21blank.gif Complete the G38 Provision OSC Terminations to recreate the OSC terminations deleted in Step 14.

Step 22blank.gif Import the recalculated ROADM site parameters using the G143 Import the Cisco TransportPlanner NE Update Configuration File.

Step 23blank.gif Complete the G37 Run Automatic Node Setup.

Step 24blank.gif Update the ANS parameters at the adjacent nodes:

a.blank.gif Display an adjacent node in node view.

b.blank.gif Complete the G143 Import the Cisco TransportPlanner NE Update Configuration File to load the new NE Update file onto the node.

c.blank.gif Complete the G37 Run Automatic Node Setup to recalculate the ANS parameters at the node.

d.blank.gif Display the next adjacent node in node view.

e.blank.gif Repeat Steps b and c for the second adjacent node.

Step 25blank.gif Display the new ROADM node in node view.

Step 26blank.gif Recreate the OCHNCs and/or OCHCCs deleted in Step 7 using the following tasks:

Step 27blank.gif Complete the G180 Clear a Manual or Force Y-Cable or Splitter Protection Switch for OCHNCs and/or OCHCCs that were switched to the opposite side of the ring as part of a splitter or Y-cable protection group to return the traffic to its condition before the card was added.

Stop. You have completed this procedure.


 

NTP-G176 Convert an Line Amplifier Node to an OADM Node

 

Purpose

This procedure converts a full line amplifier node with OPT-PRE and OPT-BST cards installed on each side of the shelf to an OADM node.

Tools/Equipment

Cisco TransportPlanner reports and NE Update file for the new OADM node.

Prerequisite Procedures

Chapter 6, “Turn Up a Network”

A Cisco TransportPlanner site plan recalculated for the new ROADM node.

Required/As Needed

As needed

Onsite/Remote

Onsite

Security Level

Provisioning or higher

caut.gif

Caution blank.gif This procedure will affect the service of unprotected circuits that pass through the OADM node.

caut.gif

Caution blank.gif This procedure applies to line amplifier nodes with OPT-BST and OPT-PRE cards installed on both sides of the shelf. If the line amplifier node has a different configuration, the upgrade might affect the adjacent nodes and require an update of their ANS parameters. If the line amplifier node is not a full line amplifier, contact your next level of support.


Step 1blank.gif Complete the G139 Verify Cisco TransportPlanner Reports and Files procedure to verify that you have the files and reports prepared by Cisco TransportPlanner for the OADM node.

Step 2blank.gif Complete the G46 Log into CTC at the line amplifier node.

Step 3blank.gif Click the Circuits tab.

Step 4blank.gif Make a list of the OCHNCs, OCH trails, and OCHCCs that pass through the node on the express path for both the Side B-to-Side A and Side A-to-Side B directions.

caut.gif

Caution blank.gif You will delete the optical channel circuits in the next step and use the list to recreate the circuits later. Do not proceed until you complete the circuit list.

Step 5blank.gif Delete the circuits identified in Step 4 using one or more of the following tasks:

Step 6blank.gif Click the Provisioning > WDM-ANS > Internal Patchcords tabs.

Step 7blank.gif In the internal patchcords table, click the OPT-PRE COM-TX to OPT-BST COM-RX internal patchcord.

Step 8blank.gif Click Delete.

Step 9blank.gif On the confirmation dialog, click OK.

Step 10blank.gif Remove the physical fiber and attenuators, if present, that connect the COM-TX to COM-RX ports and COM-RX to COM-TX ports between the OPT-BST and OPT-PRE cards installed in Side B.

Step 11blank.gif Referring to the Cisco TransportPlanner Shelf Layout report, install the AD-xC-xx-x and/or AD-xB-xx.x cards on both Side B and Side A of the node.

Step 12blank.gif Referring to the Cisco TransportPlanner Internal Connections report, connect the fibers to the new AD-xC-xx-x and/or AD-xB-xx.x cards.

Step 13blank.gif Click Default Patchcords.

Step 14blank.gif Verify that the new internal patchcords are created for the physical cables connected to the new AD-xC-xx.x and AD-xB-xx.x card(s) in Step 12. If not, complete the G354 Create an Internal Patchcord Manually to manually create the internal patchcords.

Step 15blank.gif Complete the G143 Import the Cisco TransportPlanner NE Update Configuration File.

Step 16blank.gif Complete the G37 Run Automatic Node Setup.

Step 17blank.gif In node view, click the Circuits tab.

Step 18blank.gif Complete one or more of the following procedures to recreate circuits identified in Step 4 that will pass through the OADM node:

note.gif

Noteblank.gif Cisco recommends that you recreate the circuits one at a time.


Step 19blank.gif Verify that each circuit appears on the Circuits table with a DISCOVERED status and an IS/Unlocked state. If not, complete Steps 17 and 18 .

If the circuits still do not appear with a DISCOVERED status and IS/Unlocked state, contact your next level of support.

Step 20blank.gif Referring to the Cisco TransportPlanner Traffic Matrix report, repeat Steps 18 and 19 to create the new add/drop circuits at the node, as needed.

Stop. You have completed this procedure.


 

NTP-G182 Convert a Line Amplifier Node to a ROADM Node

 

Purpose

This procedure converts a line amplifier node with OPT-PRE and OPT-BST cards installed on each side of the shelf to an ROADM node.

Tools/Equipment

Cisco TransportPlanner reports and NE Update file for the new ROADM node.

Prerequisite Procedures

Chapter 6, “Turn Up a Network”

A Cisco TransportPlanner site plan recalculated for the new ROADM node.

Required/As Needed

As needed

Onsite/Remote

Onsite

Security Level

Provisioning or higher

caut.gif

Caution blank.gif This procedure will affect the service of unprotected circuits that pass through the ROADM node.

caut.gif

Caution blank.gif This procedure applies to line amplifier nodes with OPT-BST and OPT-PRE cards installed on both sides of the shelf. If the line amplifier node has a different configuration, the upgrade might affect the adjacent nodes and require an update of their ANS parameters. If the line amplifier node is not a full line amplifier, contact your next level of support.


Step 1blank.gif Complete the G139 Verify Cisco TransportPlanner Reports and Files to verify that you have the files and reports prepared by Cisco TransportPlanner for the ROADM node.

Step 2blank.gif Complete the G46 Log into CTC at the line amplifier node.

Step 3blank.gif Click the Circuits tab.

Step 4blank.gif Make a list of the following OCHNCs, OCH trails, and OCHCCs that pass through the node on the express path for both the Side B-to-Side A and Side A-to-Side B directions.

caut.gif

Caution blank.gif You will delete the optical channel circuits in the next step and use the list to recreate the circuits later. Do not proceed until you complete the circuit list.

Step 5blank.gif Delete the circuits identified in Step 4 using one or more of the following tasks:

Step 6blank.gif Click the Provisioning > WDM-ANS > Internal Patchcords tabs.

Step 7blank.gif In the internal patchcords table, click the OPT-PRE COM-TX to OPT-BST COM-RX internal patchcord.

Step 8blank.gif Click Delete.

Step 9blank.gif In the confirmation dialog box, click OK.

Step 10blank.gif Remove the physical fiber and attenuators, if present, that connect the COM-TX to COM-RX ports and COM-RX to COM-TX ports between the OPT-BST and OPT-PRE cards installed in Side B.

Step 11blank.gif Referring to the Cisco TransportPlanner Shelf Layout report, install one of the following sets of cards on both Side B and Side A of the node as described by the Cisco TransportPlanner NE Update file:

    • 32WSS and 32DMX cards
    • 32WSS-L and 32DMX-L cards
    • 40-WSS-C/40-WSS-CE and 40-DMX-C/40-DMX-CE cards

Step 12blank.gif Referring to the Cisco TransportPlanner Internal Connections report, connect the fibers to the new wavelength selective switch and demultiplexer cards.

Step 13blank.gif Click Default Patchcords.

Step 14blank.gif Verify that the new internal patchcords are created for the physical cables connected to the new wavelength selective switch and demultiplexer cards in Step 12. If not, complete the G354 Create an Internal Patchcord Manually to manually create the internal patchcords.

Step 15blank.gif Complete the G143 Import the Cisco TransportPlanner NE Update Configuration File.

Step 16blank.gif Complete the G37 Run Automatic Node Setup.

Step 17blank.gif In node view, click the Circuits tab.

Step 18blank.gif Complete one or more of the following procedures to recreate circuits identified in Step 4 that will pass through the ROADM node:

note.gif

Noteblank.gif Cisco recommends that you recreate the circuits one at a time.


Step 19blank.gif Verify that each circuit appears on the Circuits table with a DISCOVERED status and an IS/Unlocked state. If not, repeat Steps 17 and 18 .

If the circuits still do not appear with a DISCOVERED status and IS/Unlocked state, contact your next level of support.

Step 20blank.gif Referring to the Cisco TransportPlanner Traffic Matrix report, repeat Steps 17 and 18 to create the new add/drop circuits at the node, as needed.

Stop. You have completed this procedure.


 

NTP-G195 Convert a Protected ROADM Node from two Separate Nodes to a Single Multishelf Node

 

Purpose

This procedure converts a protected ROADM node from two separate nodes to a single multishelf node.

Tools/Equipment

None.

Prerequisite Procedures

Chapter 6, “Turn Up a Network”

A Cisco TransportPlanner site plan recalculated for the new node.

Required/As Needed

As needed

Onsite/Remote

Onsite

Security Level

Provisioning or higher

caut.gif

Caution blank.gif This procedure will affect the service of unprotected circuits that pass through the ROADM node.

caut.gif

Caution blank.gif This procedure applies to two ROADM nodes, where ROADM Node 1 has amplifier cards (such as, OPT-BST and OPT-PRE) or optical service channel cards (OSCM or OSC-CSM) installed on both the sides of the shelf and 40-WSS-C/40-DMX-C card (or the 32WSS/32DMX and 32WSS-L/32DMX-L cards) installed in Side A (Slots 1 through 6) and the ROADM Node 2 has amplifier cards (such as, OPT-BST and OPT-PRE) or optical service channel cards (OSCM or OSC-CSM) installed on both the sides of the shelf and 40-WSS-C/40-DMX-C card (or the 32WSS/32DMX and 32WSS-L/32DMX-L cards) installed in Side B (Slots 12 through 17).

note.gif

Noteblank.gif In this procedure, ROADM Node 1 will be used as node controller and ROADM Node 2 will be added to the multishelf configuration as a subtending shelf.



Step 1blank.gif Complete the G139 Verify Cisco TransportPlanner Reports and Files to verify that you have the files and reports prepared by Cisco TransportPlanner for the ROADM nodes.

Step 2blank.gif Complete the G46 Log into CTC at the ROADM Node 1. Figure 12-1 shows the shelf view of ROADM Node 1 and Figure 12-2 shows the functional view of ROADM Node 1.

Figure 12-1 ROADM Node 1 Shelf View

 

240933.tif

Figure 12-2 ROADM Node 1 Functional View

 

240935.tif

Step 3blank.gif Click the Circuits tab.

Step 4blank.gif Make a list of all the OCHNCs, OCH trails, and OCHCCs that pass through or terminate (add/drop) at the amplifier or optical service channel cards installed in Side B of ROADM Node 1.

caut.gif

Caution blank.gif You will delete only the pass-through circuits in the next step and use the list to recreate the circuits later. Do not proceed until you complete the circuit list. The add/drop circuits will not be deleted and continues to transport traffic.

Step 5blank.gif If OCHNCs and/or OCHCCs identified in Step 4 are routed on the active path of a splitter or Y-cable protection group, complete the following steps. If not, continue with Step 6.

a.blank.gif Display the node containing the amplifier or optical service channel cards with the Y-cable or splitter protection.

b.blank.gif Force the traffic to the protect path in the opposite side of the ring using the G179 Apply a Force Y-Cable or Splitter Protection Switch.

Step 6blank.gif Delete the circuits identified in Step 4 using one or more of the following tasks:

Step 7blank.gif Click the Provisioning > WDM-ANS > Optical Side tab.

Step 8blank.gif In the optical sides table, click the optical side corresponding to the amplifier or optical service channel cards installed in Side B of ROADM Node 1.

Step 9blank.gif Click Delete.

Step 10blank.gif In the confirmation dialog box, click Yes.

Step 11blank.gif Click the Provisioning > WDM-ANS > Internal Patchcords tab.

Step 12blank.gif Look in the To column of the internal patchcords table and make a list of internal patchcords that connect the amplifier or optical service channel cards in Side B to the 40-WSS-C/40-DMX-C card (or the 32WSS/32DMX and 32WSS-L/32DMX-L cards) in Side A of ROADM Node 1.

Step 13blank.gif Click Delete.

Step 14blank.gif In the confirmation dialog box, click Yes.

Step 15blank.gif Remove the physical fiber and attenuators, if present, that connect the amplifier or optical service channel cards in Side B to the 40-WSS-C/40-DMX-C card (or the 32WSS/32DMX and 32WSS-L/32DMX-L cards) in Side A of ROADM Node 1.

Step 16blank.gif Complete the G107 Remove Permanently or Remove and Replace DWDM Cards to delete the amplifier or optical service channel cards installed in Side B of ROADM Node 1.

Step 17blank.gif Complete the G46 Log into CTC at the ROADM Node 2. Figure 12-3 shows the ROADM Node 2 shelf view and Figure 12-4 shows the functional view of ROADM Node 1.

Figure 12-3 ROADM Node 2 Shelf View

 

240931.tif

Figure 12-4 ROADM Node 2 Functional View

 

240936.tif

Step 18blank.gif Click the Circuits tab.

Step 19blank.gif Make a list of all the OCHNCs, OCH trails, and OCHCCs that pass through or terminate (add/drop) at the amplifier or optical service channel cards installed in Side A of ROADM Node 2.

caut.gif

Caution blank.gif You will delete all the pass-through and add/drop circuits in the next step and use the list to recreate the circuits later. Do not proceed until you complete the circuit list.

Step 20blank.gif If OCHNCs and/or OCHCCs identified in Step 19 are routed on the active path of a splitter or Y-cable protection group, complete the following steps. If not, continue with Step 21.

a.blank.gif Display the node containing the amplifier or optical service channel cards with the Y-cable or splitter protection.

b.blank.gif Force the traffic to the protect path in the opposite side of the ring using the G179 Apply a Force Y-Cable or Splitter Protection Switch.

Step 21blank.gif Delete the circuits identified in Step 19 using one or more of the following tasks:

Step 22blank.gif If overhead circuits exist in the amplifier or optical service channel cards installed in Side A of ROADM Node 2, complete G112 Delete Overhead Circuits to delete these overhead circuits.

Step 23blank.gif Click the Provisioning > WDM-ANS > Optical Side tab.

Step 24blank.gif In the optical sides table, click the optical side corresponding to the amplifier or optical service channel cards installed in Side A of ROADM Node 2.

Step 25blank.gif Click Delete.

Step 26blank.gif In the confirmation dialog box, click Yes.

Step 27blank.gif Click the Provisioning > WDM-ANS > Internal Patchcords tab.

Step 28blank.gif Look in the To column of the internal patchcords table and make a list of internal patchcords that connect the amplifier or optical service channel cards in Side A to the 40-WSS-C/40-DMX-C card (or the 32WSS/32DMX and 32WSS-L/32DMX-L cards) in Side B of ROADM Node 2.

Step 29blank.gif Click Delete.

Step 30blank.gif In the confirmation dialog box, click Yes.

Step 31blank.gif Remove the physical fiber and attenuators, if present, that connect the amplifier or optical service channel cards in Side A to the 40-WSS-C/40-DMX-C card (or the 32WSS/32DMX and 32WSS-L/32DMX-L cards) in Side B of ROADM Node 2.

Step 32blank.gif If there are pluggable port modules (PPMs) that terminate on the ROADM Node 2, complete the G280 Delete a PPM to delete these PPMs.

Step 33blank.gif Complete the G107 Remove Permanently or Remove and Replace DWDM Cards to delete the amplifier or optical service channel cards installed in Side A of ROADM Node 2.

Step 34blank.gif Complete the G163 Upgrade Nodes in Single-Shelf Mode to Multishelf Mode to upgrade ROADM Node 1 to a multishelf configuration and add ROADM Node 2 as a subtending shelf. Figure 12-5 shows the final multishelf view of the node.

Figure 12-5 Final Multishelf View of the Node

 

240939.tif

Step 35blank.gif In the multishelf view, click the Provisioning > WDM-ANS > Internal Patchcords tab.

Step 36blank.gif Click Create. The Internal Patchcord Creation wizard appears.

Step 37blank.gif In the Internal Patchcord Attributes page, choose OTS/OCH to OTS/OCH option and select the Bidirectional checkbox.

Step 38blank.gif Click Next.

Step 39blank.gif In the Internal Patchcord Origination page, provision the internal patchcord origination parameters.

  • Shelf—Choose the shelf where the internal patchcord originates.
  • Slot—Choose one of the two 40-WSS-C cards (or the 32WSS/32DMX and 32WSS-L/32DMX-L cards) where the internal patchcord originates.
  • Tx Port—Choose the EXP TX port were the internal patchcord originates.

Step 40blank.gif Click Next.

Step 41blank.gif In the Internal Patchcord Termination page, provision the internal patchcord origination parameters.

  • Shelf—Choose the shelf where the internal patchcord terminates.
  • Slot—Choose the other 40-WSS-C card (or the 32WSS/32DMX and 32WSS-L/32DMX-L cards) where the internal patchcord terminates.
  • Rx Port—Choose the EXP RX port were the internal patchcord terminates.

Step 42blank.gif Click Next.

Step 43blank.gif Review the display-only information on the Internal Patchcord Origination Reverse page. This page shows the shelf, slot, and port that CTC will use for the opposite internal patchcord origination route.

Step 44blank.gif Click Next.

Step 45blank.gif Review the information displayed on the Internal Patchcord Termination Reverse page. This display-only page shows the shelf, slot, and port that CTC will use for the reverse internal patchcord termination route.

Step 46blank.gif Click Finish. The new internal patchcord appears on the Internal Patchcord table.

Step 47blank.gif Complete the G37 Run Automatic Node Setup.

Step 48blank.gif In node view, click the Circuits tab.

Step 49blank.gif Complete one or more of the following procedures to recreate circuits identified in Steps 4 and 19 :

note.gif

Noteblank.gif Cisco recommends that you recreate the circuits one at a time.


Step 50blank.gif Complete the G60 Create and Delete Overhead Circuits to recreate circuits deleted in Step 22.

Step 51blank.gif Verify that each circuit appears on the Circuits table with a DISCOVERED status and an IS/Unlocked state. If not, repeat Steps 48 and 49 .

If the circuits still do not appear with a DISCOVERED status and IS/Unlocked state, contact your next level of support.

Step 52blank.gif Click the Provisioning > Pluggable Port Module > Pluggable Port Module tab and click Create to recreate the PPMs deleted in Step 32blank.gif.

Step 53blank.gif Complete the G180 Clear a Manual or Force Y-Cable or Splitter Protection Switch for OCHNCs and/or OCHCCs that were switched to the opposite side of the ring as part of a splitter or Y-cable protection group to return the traffic to its original condition.

Stop. You have completed this procedure.


 

NTP-G177 Upgrade ANS Parameters on a DWDM Node

 

Purpose

This procedure upgrades the ANS parameters on a DWDM node.

Tools/Equipment

None

Prerequisite Procedures

Chapter 3, “Turn Up a Node”

An updated Cisco TransportPlanner NE Update file recalculated for the node.

Required/As Needed

As needed

Onsite/Remote

Onsite

Security Level

Provisioning or higher

note.gif

Noteblank.gif Do not begin this procedure until the Cisco TransportPlanner NE Update file is prepared for the node. You will import the new NE Update file and run ANS to recalculate the ANS parameters for the node.


caut.gif

Caution blank.gif Upgrading ANS parameters on one node requires ANS upgrades on all the other nodes within the network. Do not begin this procedure until you are prepared to complete the upgrade on all network nodes.

caut.gif

Caution blank.gif This procedure will affect the service of unprotected circuits that pass through the node.


Step 1blank.gif Complete the G46 Log into CTC at the node you want to update.

Step 2blank.gif Click the Circuits tab.

Step 3blank.gif Make a list of the OCHCCs, OCHNCs, and OCH trails that:

    • Terminate (add/drop) at the node.
    • Pass through the node on the express path for both the Side B-to-Side A and Side A-to-Side B directions.

Step 4blank.gif If OCHNCs, OCH trails, and/or OCHCCs identified in Step 3 are routed on the active path of a splitter or Y-cable protection group, complete the following steps. If not, continue with Step 5.

a.blank.gif Display the node containing the TXP, MXP, ADM-10G, GE_XP, 10GE_XP, GE_XPE, 10GE_XPE, or ITU-T line card with the Y-cable or splitter protection.

a.blank.gif Force the traffic to the protect path in the opposite side of the ring using the G179 Apply a Force Y-Cable or Splitter Protection Switch.

Step 5blank.gif For each circuit identified in Step 3 that was not switched in Step 4, place the circuit out of service using one or more of the following tasks.

Step 6blank.gif Complete the G143 Import the Cisco TransportPlanner NE Update Configuration File.

Step 7blank.gif Complete the G37 Run Automatic Node Setup.

Step 8blank.gif In node view, click the Circuits tab.

Step 9blank.gif If you placed circuits out of service in Step 5, complete one or more of the following tasks to put them in service.

Step 10blank.gif Verify that each circuit appears on the Circuits table with a DISCOVERED status and an IS/Unlocked state. If not, complete one or more of the following tasks to recreate the circuits.

note.gif

Noteblank.gif Cisco recommends that you recreate the circuits one at a time.


If the circuits still do not appear with a DISCOVERED status and IS/Unlocked state, contact your next level of support.

Stop. You have completed this procedure.