THIS FIELD NOTICE IS PROVIDED ON AN "AS IS" BASIS AND DOES NOT IMPLY ANY KIND OF GUARANTEE OR WARRANTY, INCLUDING THE WARRANTY OF MERCHANTABILITY. YOUR USE OF THE INFORMATION ON THE FIELD NOTICE OR MATERIALS LINKED FROM THE FIELD NOTICE IS AT YOUR OWN RISK. CISCO RESERVES THE RIGHT TO CHANGE OR UPDATE THIS FIELD NOTICE AT ANY TIME.
Revision | Publish Date | Comments |
---|---|---|
1.0
|
01-Apr-13
|
Initial Release
|
10.0
|
12-Oct-17
|
Migration to new field notice system
|
10.1
|
05-Apr-19
|
Updated the How to Identify Affected Products and Defect Information Sections and Removed the Upgrade Program Section
|
Affected Product ID | Comments |
---|---|
15454-M6-DC
|
Fixed HW ===>
|
15454-M6-DC=
|
Fixed HW ===>
|
Defect ID | Headline |
---|---|
CSCvf34445 | There were no defects filed with this field notice at the time of publication. |
Under certain conditions, the M6 chassis DC unit is exposed to fuse failure and damage. When the input voltage is greater than 55V as measured at the input connector to the node, the 7A fuse of the DC unit may blow open and may also damage the K9 opto-coupler during system power up. This situation results in powering off the related battery on the fan tray unit. The fuse failure also causes the fuse monitoring system to fail, which prevents a failure alarm to be raised on the DC unit.
Additionally, in case of a fuse failure, an M6 chassis alarm is incorrectly generated against the fan-tray assembly (FTA) unit instead of the defective DC unit. This issue is due to a software bug and is fixed in R9.2.1 and R9.3.
Under certain conditions, the M6 chassis DC unit is exposed to fuse failure and damage. The issue is seen when the input voltage is greater than 55V as measured at the input connector to the node. Under these conditions, the 7A fuse of the DC unit may blow open and may also damage the K9 opto-coupler of the DC unit rendering the fuse monitoring system inoperable.
For affected units, an M6 chassis alarm is generated instructing the operator to replace the FTA unit while the DC unit is down, and the DC unit will not recover. In releases 9.2.1 (June 29, 2011) and R9.3, the false alarm will not be raised on the fan tray, and there will be no alarm on the affected DC units.
There is no workaround solution identified for this issue. Customers should check their hardware against the serial number tool provided.
Customers can compare their hardware serial number against the serial number validation tool provided with this field notice. If the serial number validation tool indicates that the customer's hardware is affected and the hardware has failed, Cisco recommends replacement of the 15454-M6-DC under this field notice.
To determine the serial number of your line cards, complete these steps:
If you use TL1 commands, complete these steps.
>ACT-USER::
>RTRV-INV::ALL
>CANC-USER::
A serial number validation tool has been provided so customers can easily check their hardware's serial number to identify affected units.
If you require further assistance, or if you have any further questions regarding this field notice, please contact the Cisco Systems Technical Assistance Center (TAC) by one of the following methods: