Table Of Contents
Cisco Nexus 7000 Series FPGA/EPLD Upgrade Release Notes, Release 5.0
Deciding When to Upgrade EPLDs
Supported Switch Operating Systems
EPLDs Available with Release 5.0(3)
Determining Whether to Upgrade EPLD Images
Determining Whether to Upgrade EPLDs for All Modules
Determining Whether to Upgrade EPLDs for an I/O or Supervisor Module
Determining Whether to Upgrade EPLDs for a Fabric Module
Determining Whether to Upgrade EPLDs for a Fan Tray Module
Preparing the EPLD Images for Installation
Upgrading the EPLD Images for All Installed Modules
Upgrading the EPLD Images for an I/O or Standby Supervisor Module
Upgrading EPLDs for a Supervisor Module in a Single Supervisor Switch
Upgrading EPLDs for a Fabric Module
Upgrading EPLDs for a Fan Tray Module
Displaying EPLD Versions for an I/O or Supervisor Module
Displaying EPLD Versions for a Fabric Module
Displaying EPLD Versions for a Fan Tray Module
Displaying the Available EPLD Versions
Displaying the Status of EPLD Upgrades
Open Caveats in Release 5.0(3)
Resolved Caveats in Release 5.0(3)
Open Caveats in Release 5.0(2)
Resolved Caveats in Release 5.0(2)
Obtaining Documentation and Submitting a Service Request
Cisco Nexus 7000 Series FPGA/EPLD Upgrade Release Notes, Release 5.0
Part Number: OL-23077-03 B0
Release Date: November 04, 2011
Table 1 shows the online history changes for this document.
Contents
This document includes the following sections:
•Deciding When to Upgrade EPLDs
•EPLDs Available with Release 5.0(3)
•Determining Whether to Upgrade EPLD Images
•Preparing the EPLD Images for Installation
•Displaying the Status of EPLD Upgrades
•Obtaining Documentation and Submitting a Service Request
Introduction
The Cisco Nexus 7000 Series switches contain several programmable logical devices (PLDs) that provide hardware functionalities in all modules. Cisco provides electronic programmable logic device (EPLD) image upgrades to enhance hardware functionality or to resolve known issues. PLDs include electronic programmable logic devices (EPLDs), field programmable gate arrays (FPGAs), and complex programmable logic devices (CPLDs), but they do not include ASICs. In this document, the term EPLD is used for FPGA and CPLDs.
The advantage of having EPLDs for some module functions is that when you need to upgrade those functions, you just upgrade their software images instead of replacing their hardware.
Note EPLD image upgrades for an I/O module disrupt the traffic going through the module because the module must power down briefly during the upgrade. The system performs EPLD upgrades on one module at a time, so at any one time the upgrade disrupts only the traffic going through one module.
Cisco does not provide upgrade EPLD images very frequently, and you do not have to upgrade your EPLD images unless they fix the functions for the hardware that you are using in your Cisco Nexus 7000 Series switch. The EPLD image upgrades are independent from the Cisco NX-OS In Service Software Upgrade (ISSU) process, which upgrades the system and kickstart images with no impact on the network environment.
When Cisco makes an EPLD image upgrade available, these release notes announce their availability, and you can download them from http://www.cisco.com.
Deciding When to Upgrade EPLDs
You do not always need to upgrade EPLD images; however, when new EPLD images are available, the upgrades are always recommended if your network environment allows for a maintenance period in which some level of traffic disruption is acceptable. If such a disruption is not acceptable at this time, then you might consider postponing the upgrade until a better time.
Note The EPLD upgrade operation is a disruptive operation. You should execute this operation only at a programmed maintenance time. The system/kickstart ISSU upgrade is a nondisruptive upgrade.
Note Do not perform an EPLD upgrade during an ISSU system/kickstart upgrade.
Table 2 provides high-level guidelines to help network administrators determine whether an EPLD upgrade is necessary. The Cisco Defect and Enhancement Tracking System (CDETS) listed in this table can be found in the following earlier versions of FPGA/EPLD release notes:
•Cisco Nexus 7000 Series FPGA/EPLD Upgrade Release Notes, Release 4.0
•Cisco Nexus 7000 Series FPGA/EPLD Upgrade Release Notes, Release 4.1
Table 2 Conditions For Upgrading EPLD Images
Condition Modules Recommended for Upgrades 1Upgrading the Cisco NX-OS operating system from Release 4.x to Release 5.0 or later releases.
Update all supervisor, I/O, and fabric modules with the latest EPLD images.
Upgrading the Cisco NX-OS operating system from Release 4.0 to Release 4.1(2) or later releases.
Supervisor modules (N7K-SUP1)
•Cisco Nexus 7010—Required for CSCsr03766 and to fix a kernel booting failure.
•Cisco Nexus 7018—Required for CSCsq28232, CSCsr03766, CSCsu55410, and to fix a kernel booting failure.
32-port 10-Gbps Ethernet I/O modules (N7K-M132XP-12)
•Cisco Nexus 7010—Required for CSCsu50821.
•Cisco Nexus 7018—Required for CSCsq28232 and CSCsu50821.
48-port 10/100/1000 Ethernet I/O modules (N7K-M148GT-11)
•Cisco Nexus 7010—Required for CSCsq97271, CSCsr42519, and CSCsr44846.
•Cisco Nexus 7018—Required for CSCsq28232, CSCsq97271, CSCsr42519, and CSCsr44846.
Moving 32-port 10-Gbps Ethernet I/O modules from a Cisco Nexus 7010 switch to a Cisco Nexus 7018 switch.
32-port 10-Gbps Ethernet I/O modules (N7K-M132XP-12)
Moving 48-port 10/100/1000 Ethernet I/O modules from a Cisco Nexus 7010 switch to a Cisco Nexus 7018 switch.
48-port 10/100/1000 Ethernet I/O modules (N7K-M148GT-11)
Moving the supervisor (N7K-SUP1) modules from a Cisco Nexus 7010 switch to a Cisco Nexus 7018 switch.
Supervisor (N7K-SUP1) modules
Upgrading the Cisco NX-OS operating system from Release 4.1(2) to Release 4.1(3) or later releases on a switch that shipped with Release 4.1(2).
32-port 10-Gbps Ethernet I/O modules (N7K-M132XP-12)
•Cisco Nexus 7010 and 7018—Required for CSCsv92355.
Fabric modules for Cisco Nexus 7018 (N7K-C7018-FAB1)
•Required for CSCsv92355 and CSCsx22079.
Upgrading the Cisco NX-OS operating system from Release 4.1(2) to Release 4.1(3) or later releases on a switch that did not ship with Release 4.1(2) and a full EPLD upgrade to Release 4.1(2) was not performed.
Supervisor modules (N7K-SUP1)
•Cisco Nexus 7010—Required for CSCsr03766 and to fix a kernel booting failure.
•Cisco Nexus 7018—Required for CSCsq28232, CSCsr03766, CSCsu55410, and to fix a kernel booting problem.
48-port 10/100/1000 Ethernet I/O modules (N7K-M148GT-11)
•Cisco Nexus 7010—Required for CSCsq97271, CSCsr42519, and CSCsr44846.
•Cisco Nexus 7018—Required for CSCsq28232, CSCsq97271, CSCsr42519, and CSCsr44846.
Using vPC on a system that you are upgrading NX-OS from Release 4.0 to Release 4.1(2) or later releases.
32-port 10-Gbps Ethernet I/O modules (N7K-M132XP-12)
•Cisco Nexus 7010 and 7018—Required upgrade for using vPC.
Using Cisco Trusted Security on a system that you are upgrading Cisco NX-OS from Release 4.0 to Release 4.1(2) or later releases.
32-port 10-Gbps Ethernet I/O modules (N7K-M132XP-12)
•Cisco Nexus 7010 and 7018—Required upgrade for using Cisco Trusted Security.
1 It is recommended (not mandatory) that you upgrade the EPLD images for the supervisor, I/O, and fabric modules.
Switch Requirements
This section includes the following topics:
•Supported Switch Operating Systems
Hardware Requirements
The Cisco Nexus 7000 Series switch must include the following hardware:
•One or two supervisor modules, each with at least 120 MB of available bootflash or slot0 memory
•One or more I/O modules
•One or more fabric modules
•Two fabric fan tray modules (Cisco Nexus 7010)
•Two system fan tray modules (Cisco Nexus 7010)
•Two fan tray modules (Cisco Nexus 7018)
You must be able to access the switch through a console, SSH, or Telnet.
You must have administrator privileges to work with the Cisco Nexus 7000 Series switch.
Supported Switch Operating Systems
The Cisco Nexus 7000 Series switch must be running the Cisco NX-OS operating system, which is used to perform the EPLD upgrades.
EPLDs Available with Release 5.0(3)
Each EPLD image that you can download from http://www.cisco.com is a bundle of EPLD upgrades. To see the updated EPLD versions for each release, see Table 3.
Note There are no new EPLD images for Release 5.0(3) or Release 5.0(5)—the EPLD images are the same for Release 5.0(2), d 5.0(3), and 5.0(5).
Table 3 EPLD Upgrades for Cisco NX-OS Releases
Module Type Release EPLD Device 4.0(x) 4.1(1) 4.1(2) 4.1(3) 4.2(4) 4.2(5) 4.2(6) 5.0(2) 5.0(3) 5.0(5)Supervisor module (N7K-SUP1)
Power Manager
IO
INBAND
Local Bus and CPLD
CMP CPLD3.6
3.23
1.7
2.1
6.0-
-
-
-
-3.7
3.26
-
3.0
--
-
-
-
--
-
-
-
--
-
-
-
--
-
-
-
-3.009
3.028
1.008
-
--
-
-
-
--
-
-
-
-48-port 10/100/1000 Ethernet I/O module
(N7K-M148GT-11)Power Manager
IO
Forwarding Engine5.3
2.10
1.6-
-
-5.4
2.11
--
-
--
-
--
-
--
-
-5.006
2.013
--
-
--
-
-48-port 1 Gbps Ethernet I/O module
(N7K-M148GS-11 and N7K-M148GS-11L)Power Manager
IO
SFP
Forwarding EngineN.A.
N.A.
N.A.
N.A.-
-
-
-4.6
1.3
1.4
1.6-
-
-
--
-
-
--
-
-
--
-
-
-4.008
1.005
-
--
-
-
--
-
-
-32-port 10 Gbps Ethernet I/O module
(N7K-M132XP-12)Power Manager
IO
LinkSec Engine
FE Bridge
Forwarding Engine4.4
1.10
1.7
186.3
1.6-
-
-
-
-4.6
1.13
-
-
--
-
-
-
--
1.14
1.13
-
--
-
-
-
--
1.15
-
-
-4.008
-
2.006
186.005
--
-
-
-
--
-
-
-
-8-port 10-Gbps Ethernet I/O module
(N7K-M108X2-12L)Power Manager
IO
CDL FPGA
Forwarding EngineN.A.
N.A.
N.A.
N.A.N.A.
N.A.
N.A.
N.A.N.A.
N.A.
N.A.
N.A.N.A.
N.A.
N.A.
N.A.N.A.
N.A.
N.A.
N.A.N.A.
N.A.
N.A.
N.A.N.A.
N.A.
N.A.
N.A.4.008
2.006
2.004
1.006-
-
-
--
-
-
-Fabric module (Cisco Nexus 7010)
Power Manager
2.8
-
2.9
-
-
-
-
2.010
-
-
Fabric module (Cisco Nexus 7018)
(N7K-C7018-FAB1)Power Manager
N.A.
-
1.1
-
1.2
-
-
1.003
-
-
Fan (Cisco Nexus 7010)
Fan Controller
0.7
-
-
-
-
-
-
-
-
-
Fan (Cisco Nexus 7018)
Fan Controller
N.A.
-
0.2
-1
-
-
-
-
-
-
1 Release 4.1(3) does not support EPLD upgrades for the Cisco Nexus 7018 fan controller.
Note To list the EPLDs running on your switch, use the show version module_number epld command. If any of the versions that you list are older than the newest version listed in Table 3, it is recommended that you update the EPLDs.
Determining Whether to Upgrade EPLD Images
You can upgrade EPLD images for all online modules on your switch (except for the active supervisor module) or for individual online modules.
This section includes the following topics:
•Determining Whether to Upgrade EPLDs for All Modules
•Determining Whether to Upgrade EPLDs for an I/O or Supervisor Module
•Determining Whether to Upgrade EPLDs for a Fabric Module
•Determining Whether to Upgrade EPLDs for a Fan Tray Module
Determining Whether to Upgrade EPLDs for All Modules
To determine whether you need to update the EPLDs for any of the online modules on your switch, use the show install all impact epld url command as shown in Example 1. This command displays a report that indicates whether the upgrade is disruptive for the module, whether each module can be upgraded, and whether an upgrade is available for each EPLD on each module.
Example 1 Determining Upgradability of All Online Modules
switch# show install all impact epld bootflash:n7000-s1-epld.5.0.3.imgCompatibility check:Module Type Upgradable Impact Reason------ ---- ---------- ---------- ------1 LC Yes disruptive Module Upgradable2 LC Yes disruptive Module Upgradable3 LC Yes disruptive Module Upgradable6 SUP Yes disruptive Module Upgradable1 Xbar Yes disruptive Module Upgradable2 Xbar Yes disruptive Module Upgradable3 Xbar Yes disruptive Module Upgradable1 FAN Yes disruptive Module Upgradable2 FAN Yes disruptive Module Upgradable3 FAN Yes disruptive Module Upgradable4 FAN Yes disruptive Module UpgradableRetrieving EPLD versions... Please wait.Images will be upgraded according to following table:Module Type EPLD Running-Version New-Version Upg-Required------ ---- ------------- --------------- ----------- ------------1 LC Power Manager 5.004 5.006 Yes1 LC IO 2.011 2.013 Yes1 LC Forwarding Engine 1.006 1.006 No2 LC Power Manager 4.006 4.008 Yes2 LC IO 1.003 1.005 Yes2 LC Forwarding Engine 1.006 1.006 No2 LC SFP 1.004 1.004 No3 LC Power Manager 4.006 4.008 Yes3 LC IO 1.014 1.015 Yes3 LC Forwarding Engine 1.006 1.006 No3 LC FE Bridge(1) 186.003 186.005 Yes3 LC FE Bridge(2) 186.003 186.005 Yes3 LC Linksec Engine(1) 1.008 2.006 Yes3 LC Linksec Engine(2) 1.008 2.006 Yes3 LC Linksec Engine(3) 1.008 2.006 Yes3 LC Linksec Engine(4) 1.008 2.006 Yes3 LC Linksec Engine(5) 1.008 2.006 Yes3 LC Linksec Engine(6) 1.008 2.006 Yes3 LC Linksec Engine(7) 1.008 2.006 Yes3 LC Linksec Engine(8) 1.008 2.006 Yes5 SUP Power Manager 3.007 3.009 Yes5 SUP IO 3.026 3.028 Yes5 SUP Inband 1.007 1.008 Yes5 SUP Local Bus CPLD 3.000 3.000 No5 SUP CMP CPLD 6.000 6.000 No6 SUP Power Manager 3.007 3.009 Yes6 SUP IO 3.026 3.028 Yes6 SUP Inband 1.007 1.008 Yes6 SUP Local Bus CPLD 3.000 3.000 No6 SUP CMP CPLD 6.000 6.000 No1 Xbar Power Manager 2.009 2.010 Yes2 Xbar Power Manager 2.009 2.010 Yes3 Xbar Power Manager 2.009 2.010 Yes1 FAN Fan Controller (1) 0.007 0.007 No1 FAN Fan Controller (2) 0.007 0.007 No2 FAN Fan Controller (1) 0.007 0.007 No2 FAN Fan Controller (2) 0.007 0.007 No3 FAN Fan Controller (1) 0.007 0.007 No3 FAN Fan Controller (2) 0.007 0.007 No4 FAN Fan Controller (1) 0.007 0.007 No4 FAN Fan Controller (2) 0.007 0.007 NoDetermining Whether to Upgrade EPLDs for an I/O or Supervisor Module
To determine whether you need to update the EPLDs for an online I/O or supervisor module, use the show install module number impact epld url command as shown in Example 2. This command displays a report that indicates which EPLDs need to be upgraded for the module that you specified.
Example 2 Determining Upgradability of an I/O or Supervisor Module
switch# show install module 5 impact epld bootflash:n7000-s1-epld.5.0.3.imgRetrieving EPLD versions... Please wait.Images will be upgraded according to following table:Module Type EPLD Running-Version New-Version Upg-Required------ ---- ------------- --------------- ----------- ------------5 SUP Power Manager 3.007 3.009 Yes5 SUP IO 3.026 3.028 Yes5 SUP Inband 1.007 1.008 Yes5 SUP Local Bus CPLD 3.000 3.000 No5 SUP CMP CPLD 6.000 6.000 NoDetermining Whether to Upgrade EPLDs for a Fabric Module
To determine whether you need to update the EPLDs for an online fabric module, use the show install xbar-module number impact epld url command as shown in Example 3. This command displays a report that indicates which EPLDs need to be upgraded for the fabric module that you specified.
Example 3 Determining Upgradability of a Fabric Module
switch# show install xbar-module 1 impact epld bootflash:n7000-s1-epld.5.0.3.imgRetrieving EPLD versions... Please wait.Images will be upgraded according to following table:Module Type EPLD Running-Version New-Version Upg-Required------ ---- ------------- --------------- ----------- ------------1 Xbar Power Manager 2.009 2.010 YesDetermining Whether to Upgrade EPLDs for a Fan Tray Module
To determine whether you need to update the EPLDs for an online fan tray module, use the show install fan-module number impact epld url command as shown in Example 4. This command displays a report that indicates which EPLDs need to be upgraded for the fan module that you specified.
Example 4 Determining Upgradability of a Fan Module
switch# show install fan-module 1 impact epld bootflash:n7000-s1-epld.5.0.3.imgRetrieving EPLD versions... Please wait.Images will be upgraded according to following table:Module Type EPLD Running-Version New-Version Upg-Required------ ---- ------------- --------------- ----------- ------------1 FAN Fan Controller (1) 0.007 0.007 No1 FAN Fan Controller (2) 0.007 0.007 NoDownloading the EPLD Images
Before you can prepare the EPLD images for installation, you must download them to the FTP or management server.
To download the EPLD images, follow these steps:
Step 1 From a browser, go to the following URL:
The browser will display the Cisco web site.
Step 2 From the Products & Services tab, choose Switches.
The Switches page opens.
Step 3 In the Data Center area, click the arrow next to View Products.
The page lists the Data Center products.
Step 4 Click Nexus 7000.
The Cisco Nexus 7000 Series Switches page opens.
Step 5 In the Support area, click Download Software.
The Downloads page opens and lists the Data Center switches.
Step 6 Choose a Cisco Nexus 7000 Series switch from the list under Data Center Switches > Cisco Nexus 7000 Series Switches.
The Log In page opens.
Step 7 If you are an existing user, enter your username in the User Name field and your password in the Password field. If you are a new user, click Register Now and provide the required information before returning to the Log In page and logging in with your new username.
The Downloads page lists the software types that can be downloaded for the switch you specified.
Step 8 Click NX-OS EPLD Updates.
The Downloads page lists software releases that you can download.
Step 9 Choose Latest Releases >5.0.3.
The Downloads page displays image information, including a link to the downloadable Tar file, to the right of the releases.
Step 10 Click the link for the Tar file.
The Downloads page displays a Download button and lists information for the Tar file.
Step 11 Click Download.
The Supporting Documents page opens to display the rules for downloading the software.
Step 12 Read the rules and click Agree.
A File Download dialog box opens to ask if you want to open or save the images file.
Step 13 Click Save.
The Save As dialog box appears.
Step 14 Indicate where to save the Tar file and click Save.
The Tar file saves to the location that you specified.
You are ready to prepare the EPLD images for Installation (see the "Preparing the EPLD Images for Installation" section).
EPLD Images Needed for vPCs
The virtual port channel (vPC) feature is available beginning with Cisco NX-OS Release 4.1(3). When you enable vPC on the chassis, you must have EPLD image 186.3 (or later image) on the 32-port 10 Gbps Ethernet IO modules (N7K-M132XP-12).
Note The EPLD upgrade operation is a disruptive operation. You should execute this operation only at a programmed maintenance time. The system/kickstart ISSU upgrade is a nondisruptive upgrade.
Note Do not perform an EPLD upgrade during an ISSU system/kickstart upgrade.
Most of the N7K-M132XP-12 modules in the chassis already meet this minimum EPLD requirement, but if you are working with a N7K-M132XP-12 module that was shipped before June 2008, you might need to upgrade the EPLD version.
To determine the EPLD version for all N7K-M132XP-12 modules, enter the show version module module_id epld. If the line FE Bridge(x) version displays a version earlier than 186.003 (for example, 186.2 or 186.002), you should schedule an EPLD upgrade to a version that is compatible with the target NX-OS release. For example, if you want to run Cisco NX-OS Release 5.0(3), you should choose Release 5.0(3) EPLDs.
The following example shows Release 186.003 on the FE Bridge line, which is the correct EPLD version:
switch(config)# show ver mod 7 epld EPLD Device Version --------------------------------------- Power Manager 4.006 IO 1.014 Forwarding Engine 1.006 FE Bridge(1) 186.003 << OK! FE Bridge(2) 186.003 << OK! Linksec Engine(1) 1.013 Linksec Engine(2) 1.013 Linksec Engine(3) 1.013 Linksec Engine(4) 1.013 Linksec Engine(5) 1.013 Linksec Engine(6) 1.013 Linksec Engine(7) 1.013 Linksec Engine(8) 1.013Installation Guidelines
You can upgrade (or downgrade) EPLDs using CLI commands on the Cisco Nexus 7000 Series switch. Follow these guidelines when you upgrade or downgrade EPLDs:
•Before you upgrade any EPLD images, be sure that you have updated the Cisco NX-OS operating system to the level required for the changes.
•You can execute an upgrade from the active supervisor module only. All the modules, including the active supervisor module, can be updated individually.
•You can individually update each module whether it is online or offline as follows:
–If you upgrade EPLD images on an online module, only the EPLD images with version numbers that differ from the new EPLD images are upgraded.
–If you upgrade EPLD images on an offline module, all of the EPLD images are upgraded.
•On a switch that has two supervisor modules, upgrade the EPLDs for the standby supervisor and then switch the active supervisor to the standby mode to upgrade its EPLDs (the supervisor switchover is not disruptive to traffic on Cisco Nexus 7000 Series switches). On a switch that has only one supervisor module, you can upgrade the active supervisor, but this will disrupt its operations during the upgrade.
•If you interrupt an upgrade, you must upgrade the module that is being upgraded again.
•The upgrade process disrupts traffic on the targeted module.
•Do not insert or remove any modules while an EPLD upgrade is in progress.
Preparing the EPLD Images for Installation
Before you can update the EPLD images for each of your switch modules, you must determine the Cisco NX-OS version that your switch is using, make sure there is space for the new EPLD images, and download the images.
To prepare the EPLD images for installation, follow these steps:
Step 1 Log into the switch through the console port, an SSH session, or a Telnet session.
Step 2 Verify that the switch is using the expected version of the Cisco NX-OS operating system. The kickstart and system lines indicate the Cisco NX-OS version. This step determines the versions of EPLD images that you must download.
switch# show version...SoftwareBIOS: version 3.22.0loader: version N/Akickstart: version 5.0(2) [gdb]system: version 5.0(2) [gdb]BIOS compile time: 02/20/10kickstart image file is: bootflash:/n7000-s1-kickstart.5.0.2.binkickstart compile time: 12/25/2020 12:00:00 [05/18/2010 04:24:07]system image file is: bootflash:/n7000-s1-dk9.5.0.2.binsystem compile time: 2/7/2010 3:00:00 [05/18/2010 05:06:22]Step 3 Verify that you have 120 MB of free space on the active or standby supervisor memory devices for the EPLD images that you will be downloading by using the dir bootflash: or dir slot0: commands.
By default, these commands display the used and free memory for the active supervisor. If your switch has an additional supervisor (a standby supervisor), use the show module command to find the module number for the other supervisor, use the attach module command to attach to the module number, and then use the dir bootflash: or dir slot0: command to determine the amount of used and free memory. See Example 5 to determine the amount of available bootflash memory, and see Example 6 to determine the amount of available slot0 memory.
Example 5 Determining the Amount of Available Bootflash Memory
switch# dir bootflash:12695 Jan 20 22:04:49 2010 LLDP0 May 25 18:46:17 2010 admin.rc.cli307162 Jul 27 09:37:23 2009 amlog_vdc1_pid331634984 Jul 25 14:54:01 2009 amlog_vdc2_pid663319765 Jun 08 15:21:11 2009 backup-startup-config1454646 Apr 29 12:46:45 2009 cmd_syntax.txt71220 Jan 09 00:01:33 2008 cmpdc3_bios_util-4.0.2.45.02210717 Oct 05 16:27:01 2009 config24540 Feb 27 13:20:26 2010 dcnm-172.28.254.254-ckpnt.cfg14397 Mar 19 13:00:36 2010 doc29 May 14 16:28:42 2009 lc2_version49152 May 20 09:13:43 2010 lost+found/2386687 May 20 09:09:50 2010 n7000-s1-debug-sh.5.0.2.bin108604827 May 20 09:03:45 2010 n7000-s1-dk9.5.0.2.bin24345600 Feb 04 12:03:47 2010 n7000-s1-kickstart.4.2.4.bin23667200 May 20 09:07:28 2010 n7000-s1-kickstart.5.0.2.bin10362 Nov 20 07:24:31 2009 temp_file4096 Jun 09 11:32:41 2009 testDIR/4096 Jun 09 11:30:47 2009 testdir/31956 Jun 21 10:19:14 2009 user_cp_14096 Jan 09 00:21:32 2008 vdc_2/4096 Jan 09 00:21:32 2008 vdc_3/4096 Jan 09 00:21:32 2008 vdc_4/1622 May 14 16:28:16 2009 ver0 May 19 06:05:27 2009 vpc_hw_check_disable27935 Jun 26 13:43:43 2009 vrrp_cfg.log28833 Jun 26 13:46:26 2009 vrrp_eng.logUsage for bootflash://sup-local398700544 bytes used1405636608 bytes free1804337152 bytes totalswitch# show module
Mod Ports Module-Type Model Status--- ----- -------------------------------- ------------------ ------------6 8 10 Gbps Ethernet XL Module N7K-M108X2-12L ok7 48 1000 Mbps Optical Ethernet Modul N7K-M148GS-11 ok8 48 1000 Mbps Optical Ethernet XL Mo N7K-M148GS-11L ok9 0 Supervisor module-1X N7K-SUP1 ha-standby10 0 Supervisor module-1X N7K-SUP1 active *...switch# attach module 9
Attaching to module 9 ...To exit type 'exit', to abort type '$.'Cisco Nexus Operating System (NX-OS) SoftwareTAC support: http://www.cisco.com/tacCopyright (c) 2002-2010, Cisco Systems, Inc. All rights reserved.The copyrights to certain works contained in this software areowned by other third parties and used and distributed underlicense. Certain components of this software are licensed underthe GNU General Public License (GPL) version 2.0 or the GNULesser General Public License (LGPL) Version 2.1. A copy of eachsuch license is available athttp://www.opensource.org/licenses/gpl-2.0.php andhttp://www.opensource.org/licenses/lgpl-2.1.phpswitch#Example 6 Determining the Amount of Available Slot0 Memory
switch# dir slot0:...Usage for slot0://sup-local1380352 bytes used2073866240 bytes free2075246592 bytes totalswitch# show module
Mod Ports Module-Type Model Status--- ----- -------------------------------- ------------------ ------------2 48 10/100/1000 Mbps Ethernet Module N7K-M148GT-11 ok3 48 10/100/1000 Mbps Ethernet Module N7K-M148GT-11 ok4 48 10/100/1000 Mbps Ethernet Module N7K-M148GT-11 ok5 0 Supervisor module-1X N7K-SUP1 ha-standby6 0 Supervisor module-1X N7K-SUP1 active *7 32 10 Gbps Ethernet Module N7K-M132XP-12 ok9 48 1000 Mbps Optical Ethernet Modul N7K-M148GS-11 ok...switch(standby)# dir slot0://sup-standby/
...Usage for slot0://sup-standby1376256 bytes used2073870336 bytes free2075246592 bytes totalStep 4 If there is not at least 120 MB of memory free for the EPLD files, delete some unneeded files, such as earlier images, so there is enough free memory.
switch# delete bootflash:n7000-s1-kickstart.4.2.4.binStep 5 Copy the EPLD image file from the FTP or management server to the bootflash or slot0 memory in the active supervisor module. The following example shows how to copy from the FTP server to the bootflash memory.
switch# copy ftp://10.1.7.2/n7000-s1-epld.5.0.3.img bootflash:n7000-s1-epld.5.0.3.imgStep 6 Copy the EPLD image to the standby supervisor.
switch# copy bootflash:n7000-s1-epld.5.0.3.img bootflash://sup-standby/n7000-s1-epld.5.0.3.img
You are ready to upgrade the EPLD images (see the "Upgrading EPLD Images" section).
Upgrading EPLD Images
You can update the EPLD images for all of the installed modules or a specific installed module. When you request an upgrade, the Cisco NX-OS software tries to list the current and new versions for each EPLD with the following results:
•If a module is installed and online, the software lists the installed and new versions for each EPLD. Where there is a difference in versions, the software indicates an upgrade or downgrade to occur when you confirm the upgrade.
•If a module is installed and offline, the software cannot list its current EPLD versions so all EPLDs will be updated when you confirm the upgrade.
•If a module is not installed, the software displays an error message and does not upgrade the EPLDs.
The following sections explain how to upgrade the EPLD images for I/O and standby modules, the active supervisor module on switches with single-supervisor modules, fabric modules, and fan tray modules.
•Upgrading the EPLD Images for All Installed Modules
•Upgrading the EPLD Images for an I/O or Standby Supervisor Module
•Upgrading EPLDs for a Supervisor Module in a Single Supervisor Switch
•Upgrading EPLDs for a Fabric Module
•Upgrading EPLDs for a Fan Tray Module
Upgrading the EPLD Images for All Installed Modules
You can upgrade the EPLD images for all installed modules while the switch is operational. This type of upgrade includes updates of EPLD images for the standby supervisor module, all I/O modules, all fabric modules, and all fan modules, but this upgrade does not update the EPLDs for the active supervisor module. To upgrade the EPLDs for the active supervisor module, see the "Upgrading EPLDs for a Supervisor Module in a Single Supervisor Switch" section.
To upgrade EPLDs for all installed modules (except the active supervisor module), follow these steps:
Step 1 Enter the install all epld url command.
switch# install all epld bootflash:n7000-s1-epld.5.0.3.imgCompatibility check:Module Type Upgradable Impact Reason------ ---- ---------- ---------- ------1 LC Yes disruptive Module Upgradable2 LC Yes disruptive Module Upgradable3 LC Yes disruptive Module Upgradable6 SUP Yes disruptive Module Upgradable1 Xbar Yes disruptive Module Upgradable2 Xbar Yes disruptive Module Upgradable3 Xbar Yes disruptive Module Upgradable1 FAN Yes disruptive Module Upgradable2 FAN Yes disruptive Module Upgradable3 FAN Yes disruptive Module Upgradable4 FAN Yes disruptive Module UpgradableRetrieving EPLD versions... Please wait.Images will be upgraded according to following table:Module Type EPLD Running-Version New-Version Upg-Required------ ---- ------------- --------------- ----------- ------------1 LC Power Manager 5.004 5.006 Yes1 LC IO 2.011 2.013 Yes1 LC Forwarding Engine 1.006 1.006 No2 LC Power Manager 4.006 4.008 Yes2 LC IO 1.003 1.005 Yes2 LC Forwarding Engine 1.006 1.006 No2 LC SFP 1.004 1.004 No3 LC Power Manager 4.006 4.008 Yes3 LC IO 1.014 1.015 Yes3 LC Forwarding Engine 1.006 1.006 No3 LC FE Bridge(1) 186.003 186.005 Yes3 LC FE Bridge(2) 186.003 186.005 Yes3 LC Linksec Engine(1) 1.008 2.006 Yes3 LC Linksec Engine(2) 1.008 2.006 Yes3 LC Linksec Engine(3) 1.008 2.006 Yes3 LC Linksec Engine(4) 1.008 2.006 Yes3 LC Linksec Engine(5) 1.008 2.006 Yes3 LC Linksec Engine(6) 1.008 2.006 Yes3 LC Linksec Engine(7) 1.008 2.006 Yes3 LC Linksec Engine(8) 1.008 2.006 Yes5 SUP Power Manager 3.007 3.009 Yes5 SUP IO 3.026 3.028 Yes5 SUP Inband 1.007 1.008 Yes5 SUP Local Bus CPLD 3.000 3.000 No5 SUP CMP CPLD 6.000 6.000 No6 SUP Power Manager 3.007 3.009 Yes6 SUP IO 3.026 3.028 Yes6 SUP Inband 1.007 1.008 Yes6 SUP Local Bus CPLD 3.000 3.000 No6 SUP CMP CPLD 6.000 6.000 No1 Xbar Power Manager 2.009 2.010 Yes2 Xbar Power Manager 2.009 2.010 Yes3 Xbar Power Manager 2.009 2.010 Yes1 FAN Fan Controller (1) 0.007 0.007 No1 FAN Fan Controller (2) 0.007 0.007 No2 FAN Fan Controller (1) 0.007 0.007 No2 FAN Fan Controller (2) 0.007 0.007 No3 FAN Fan Controller (1) 0.007 0.007 No3 FAN Fan Controller (2) 0.007 0.007 No4 FAN Fan Controller (1) 0.007 0.007 No4 FAN Fan Controller (2) 0.007 0.007 NoThe above modules requie upgrade.Do you want to continue (y/n) ? [n] yStep 2 If one or more of the EPLDs should be upgraded, enter y to begin the upgrade. Otherwise, enter n for no upgrade.
Upgrading the EPLD Images for an I/O or Standby Supervisor Module
You can upgrade the EPLD images for an I/O module or standby supervisor module while the switch is operational. If you need to upgrade EPLD images for a single supervisor module, see the "Upgrading EPLDs for a Supervisor Module in a Single Supervisor Switch" section.
Caution Upgrading EPLD images for an online I/O module can disrupt traffic going through that module.
To upgrade EPLDs for an I/O module or the standby supervisor module, follow these steps:
Step 1 Determine the slot number for the module by entering the show module command.
switch# show moduleMod Ports Module-Type Model Status--- ----- -------------------------------- ------------------ ------------1 48 10/100/1000 Mbps Ethernet Module N7K-N148GT-11 ok3 32 10 Gbps Ethernet Module N7K-M132XP-12 ok5 0 Supervisor module-1X N7K-SUP1 active6 0 Supervisor module-1X N7K-SUP1 ha-standby10 48 10/100/1000 Mbps Ethernet Module N7K-M148GT-11 okMod Sw Hw World-Wide_name(s) (WWN)--- -------------- ------ -------------------------------------------------1 4.0(2) 0.503 --3 4.0(2) 0.601 --5 4.0(2) 0.900 --6 4.0(2) 0.802 --10 4.0(2) 0.902 --Mod MAC-Address(es) Serial-Num--- -------------------------------------- ----------1 00-19-07-6c-c0-6c to 00-19-07-6c-c0-a0 JAB110601443 00-1b-54-c1-33-98 to 00-1b-54-c1-33-bc JAB1152010K5 00-1b-54-c1-16-18 to 00-1b-54-c1-16-20 JAB114902HF6 00-19-07-c1-00-b8 to 00-1b-54-c1-00-c0 JAB114402JX10 00-1b-54-c1-07-88 to 00-1b-54-c1-07-bc JAB114501RW* this terminal sessionswitch#Step 2 Install the EPLDs by entering the install module slot_number epld url command.
switch# install module 6 epld bootflash:n7000-s1-epld.5.0.3.img...EPLD Curr Ver New Ver-------------------------------------------------------Power Manager 3.007 3.009IO 3.026 3.028Inband 1.007 1.008Local Bus CPLD 3.000 3.000CMP CPLD 6.000 6.000WARNING: Upgrade process could take upto 30 minutes.Do you want to continue (y/n) ?Step 3 Begin upgrading the EPLD images by entering Y for yes.
Do you want to continue (y/n) ? YStep 4 For Release 4.0(2) or earlier releases, if you updated the power management EPLD image, you must reset the power for the module so that EPLD can take effect (this is not required for Release 4.0(3) or later releases). You can reset the power in one of the following two ways:
•To reset the power for a module, physically remove the module and reinstall it.
Note A module reload or just pressing the ejector buttons on the module is not sufficient for this reset requirement.
•To reset an entire switch, power cycle the switch.
To confirm the EPLD upgrade, see the "Displaying EPLD Versions for an I/O or Supervisor Module" section.
Caution Resetting the power disrupts any data traffic going through the affected modules. If you power cycle the entire switch, all data traffic going through the switch at the time of the power cycling is disrupted. This is not necessary for Release 4.0(3) or later releases.
Note As of Release 4.0(3) or later releases, the switch automatically loads the new power management EPLD after an upgrade, so it is no longer necessary to reset the power for the module or switch.
Upgrading EPLDs for a Supervisor Module in a Single Supervisor Switch
When you upgrade EPLDs on a switch with only one supervisor module, data traffic on the switch will be affected when you reload the device after the upgrade. If you are upgrading EPLDs for a switch with two supervisor modules, you can upgrade the standby supervisor while the switch is operational as explained in the "Upgrading the EPLD Images for an I/O or Standby Supervisor Module" section, and then switch the active supervisor into standby mode and update that module.
To upgrade EPLDs for a supervisor module in a system with a single supervisor module, follow these steps:
Step 1 Determine the slot number for the supervisor module. On a Cisco Nexus 7010 switch, the supervisor module is in either slot 5 or slot 6. On a Cisco Nexus 7018 switch, the supervisor module is in either slot 9 or slot 10.
switch# show moduleMod Ports Module-Type Model Status--- ----- -------------------------------- ------------------ ------------1 48 10/100/1000 Mbps Ethernet Module N7K-N148GT-11 ok3 32 10 Gbps Ethernet Module N7K-M132XP-12 ok5 0 Supervisor module-1X N7K-SUP1 active10 48 10/100/1000 Mbps Ethernet Module N7K-M148GT-11 okMod Sw Hw World-Wide_name(s) (WWN)--- -------------- ------ -------------------------------------------------1 4.0(2) 0.503 --3 4.0(2) 0.601 --5 4.0(2) 0.900 --10 4.0(2) 0.902 --Mod MAC-Address(es) Serial-Num--- -------------------------------------- ----------1 00-19-07-6c-c0-6c to 00-19-07-6c-c0-a0 JAB110601443 00-1b-54-c1-33-98 to 00-1b-54-c1-33-bc JAB1152010K5 00-1b-54-c1-16-18 to 00-1b-54-c1-16-20 JAB114902HF10 00-1b-54-c1-07-88 to 00-1b-54-c1-07-bc JAB114501RW* this terminal sessionStep 2 Enter the install module slot_number epld url command.
switch# install module 5 epld bootflash:n7000-s1-epld.5.0.3.img...EPLD Curr Ver New Ver-------------------------------------------------------Power Manager 3.007 3.009IO 3.026 3.028Inband 1.007 1.008Local Bus CPLD 3.000 3.000CMP CPLD 6.000 6.000WARNING: Upgrade process could take upto 30 minutes.Active Supervisor is being upgraded.Data traffic on the switch will be affected!!The switch will reload after the upgrade process.Do you want to continue (y/n) ?
Step 3 Confirm the upgrade by entering Y for yes.
Do you want to continue (y/n) ? YThe Cisco Nexus 7000 Series switch reloads as soon as the upgrade occurs.
Step 4 For Release 4.0(2) or earlier releases, if you updated the power management EPLD image, you must reset the power for the module so that EPLD can take effect (this is not required for Release 4.0(3) or later releases). You can reset the power in one of the following two ways:
•To reset the power for a module, physically remove the module and reinstall it.
Note A module reload or just pressing the ejector buttons on the module is not sufficient for this reset requirement.
•To reset an entire switch, power cycle the switch.
To confirm the EPLD upgrade, see the "Displaying EPLD Versions for an I/O or Supervisor Module" section.
Caution Resetting the power disrupts any data traffic going through the affected modules. If you power cycle the entire switch, all data traffic going through the switch at the time of the power cycling is disrupted. This is not necessary for Release 4.0(3) or later releases.
Note For Release 4.0(3) and later releases, the switch automatically loads the new power management EPLD after an upgrade, so it is no longer necessary to reset the power for the module or switch.
Upgrading EPLDs for a Fabric Module
You can upgrade EPLDs for a fabric (Xbar) module while the switch is operational as long as at least one other fabric module is operational.
To upgrade EPLDs for a fabric module, follow these steps:
Step 1 Determine which fabric modules are present on the Cisco Nexus 7000 Series switch.
switch# show module xbarXbar Ports Module-Type Model Status--- ----- -------------------------------- ------------------ ------------1 0 Xbar N7K-C7010-FAB-1 ok2 0 Xbar N7K-C7010-FAB-1 ok3 0 Xbar N7K-C7010-FAB-1 okXbar Sw Hw--- -------------- ------1 NA 0.4042 NA 0.4054 NA 0.405Xbar MAC-Address(es) Serial-Num------------------------------------------- ------------------1 NA JAB114700WL2 NA JAB115000LU4 NA JAB115000LJ* this terminal sessionStep 2 Enter the install xbar-module slot_number epld url command.
switch# install xbar-module 1 epld bootflash:n7000-s1-epld.5.0.3.img...EPLD Curr Ver New Ver-------------------------------------------------------Power Manager 2.009 2.010WARNING: Upgrade process could upto 30 minutes.Module could be powered down and up.Xbar Module 1 will be powered down now!!Do you want to continue (y/n) ? [n]Step 3 Confirm the upgrade by entering Y for yes.
Do you want to continue (y/n) ? [n] y
To confirm the EPLD upgrade, see the "Displaying EPLD Versions for a Fabric Module" section.
Upgrading EPLDs for a Fan Tray Module
You can upgrade EPLDs for a fan tray module while the switch is operational.
To upgrade EPLDs for a fan tray module, follow these steps:
Step 1 Display fan tray information, such as module numbers and fan tray types.
switch# show environment fanFan:------------------------------------------------------Fan Model Hw Status------------------------------------------------------Fan1(sys_fan1) N7K-C7018-FAN 0.204 OkFan2(sys_fan2) N7K-C7018-FAN 0.204 OkFan_in_PS1 -- -- OkFan_in_PS2 -- -- OkFan_in_PS3 -- -- OkFan_in_PS4 -- -- AbsentFan Air Filter : Absentswitch#Step 2 Enter the install fan-module slot_number epld url command.
switch# install fan-module 1 epld bootflash:n7000-s1-epld.5.0.3.img
...EPLD Curr Ver New Ver-------------------------------------------------------Fan Controller 0.005 0.007Fan Controller 0.005 0.007WARNING: Upgrade process could upto 30 minutes.Module could be powered down and up.Programming Fan Module 1 !!Do you want to continue (y/n) ? [n]Step 3 Confirm the upgrade by entering a Y for yes.
Do you want to continue (y/n) ? [n] Y
To confirm the EPLD upgrade, see the "Displaying EPLD Versions for a Fan Tray Module" section.
Displaying the EPLD Versions
The following sections explain how to display the EPLD versions on each module in your switch and the available EPLD versions:
•Displaying EPLD Versions for an I/O or Supervisor Module
•Displaying EPLD Versions for a Fabric Module
•Displaying EPLD Versions for a Fan Tray Module
•Displaying the Available EPLD Versions
Displaying EPLD Versions for an I/O or Supervisor Module
To display all of the current EPLD versions on a specific I/O or supervisor module, use the show version module slot_number epld command as shown in Example 7.
Example 7 Displaying the Current EPLD Versions for a Module
switch# show version module 2 epldEPLD Device Version---------------------------------------Power Manager 4.008IO 1.015Forwarding Engine 1.006FE Bridge(1) 186.005FE Bridge(2) 186.005Linksec Engine(1) 2.006Linksec Engine(2) 2.006Linksec Engine(3) 2.006Linksec Engine(4) 2.006Linksec Engine(5) 2.006Linksec Engine(6) 2.006Linksec Engine(7) 2.006Linksec Engine(8) 2.006Displaying EPLD Versions for a Fabric Module
To view all current EPLD versions on a fabric module, use the show version xbar slot_number epld command as shown in Example 8.
Example 8 Displaying the Current EPLD Versions for a Fabric Module
switch# show version xbar 1 epldEPLD Device Version---------------------------------------Power Manager 2.010Displaying EPLD Versions for a Fan Tray Module
To view all current EPLD versions on a specific fan tray, use the show version fan slot_number epld command as shown in Example 9.
Example 9 Displaying Current EPLD Versions for Fan Tray 1
switch# show version fan 1 epldEPLD Device Version---------------------------------------Fan Controller(BUS A) 0.007 Fan Controller(BUS B) 0.007Displaying the Available EPLD Versions
To view the available EPLD versions, use the show version epld url command as shown in Example 10.
Example 10 Displaying the Available EPLD Versions
switch# show version epld bootflash:n7000-s1-epld.5.0.3.img...Module Type EPLD Device Version---------------------------------------------------------------Supervisor-1X Power Manager 3.009Supervisor-1X IO 3.028Supervisor-1X Inband 1.008Supervisor-1X Local Bus CPLD 3.000Supervisor-1X CMP CPLD 6.00010/100/1000 Mbps Eth Module Power Manager 5.00610/100/1000 Mbps Eth Module IO 2.01310/100/1000 Mbps Eth Module Forwarding Engine 1.00610 Gbps Ethernet Module Power Manager 4.00810 Gbps Ethernet Module IO 1.01510 Gbps Ethernet Module Forwarding Engine 1.00610 Gbps Ethernet Module FE Bridge 186.00510 Gbps Ethernet Module Linksec Engine 2.0061000 Mbps Optical Ethernet Module Power Manager 4.0081000 Mbps Optical Ethernet Module IO 1.0051000 Mbps Optical Ethernet Module Forwarding Engine 1.0061000 Mbps Optical Ethernet Module SFP 1.004Fabric Module Power Manager 2.010Fabric Module 2 Power Manager 1.003Fan Fan Controller 0.007Fan Fan Controller 0.007Displaying the Status of EPLD Upgrades
To display the status of EPLD upgrades on the switch, use the show install epld status command.
Example 11 Displaying EPLD Upgrades
switch# show install epld status...Status: EPLD Upgrade was SuccessfulEPLD Curr Ver Old Ver------------------------------------------------------Power Manager 5.006 5.004IO 2.013 2.011Forwarding Engine 1.006 1.003Caveats
This section includes the following topics:
•Open Caveats in Release 5.0(2)
•Resolved Caveats in Release 5.0(2)
Open Caveats in Release 5.0(3)
There are no open caveats for Release 5.0(3).
Resolved Caveats in Release 5.0(3)
There are no resolved caveats for Release 5.0(3).
Open Caveats in Release 5.0(2)
There are no open caveats for Release 5.0(2).
Resolved Caveats in Release 5.0(2)
The following caveats are resolved in Release 5.0(2):
•CSCsy48709
Symptom: When you power down an I/O module or a standby supervisor module, the active supervisor falsely detects the removal of another I/O, supervisor, or fabric module.
Condition: When you power down an I/O module or a standby supervisor module, that module temporarily interferes with the shared status bus used by all of the modules and causes a false detection of a module removal. This problem occurs with very few I/O or supervisor modules and its occurrence depends on each FPGA component and the power-down sequence timing of each module.
Workaround: Modify the power-down sequence for all I/O and supervisor modules so that no glitch on the shared status bus will occur again when powering down. New PM FPGA and ADM sequencer images are required to fix this problem.
Resolution: Upgrade the following PM FPGAs and ADM sequencers:
–8-port 10-Gbps Ethernet I/O module: PM FPGA version 4.8 and ADM sequencer version 02
–32-port 10-Gbps Ethernet I/O module: PM FPGA version 4.8 and ADM sequencer version 02
–48-port 1-Gbps Ethernet I/O module: PM FPGA version 4.8 and ADM sequencer version 03
–48-port 10/100/1000 I/O module: PM FPGA version 5.6 and ADM sequencer version 13
–Supervisor module: PM FPGA version 3.9 and ADM sequencer 1, 2, 3, and 4 versions 03, 03, 02, and 04, respectively
•CSCsz51316
Symptom: Backplane IDPROM corruption (MAC address is set incorrectly) after power cycling.
Root Cause: A transaction is started but not completed when the supervisor is powered down. The beginning bits of the transaction are concatenated with the next transaction after power up, which results in a write operation to the backplane IDPROM.
Workaround: None.
Resolution: IOFGPA version 3.28 fixes this problem for the supervisor module.
•CSCta96378
Symptom: Erroneous exceptions occur on the active supervisor module when you press the front panel reset button.
Condition: A switchover occurs when you press the reset button on the active supervisor module.
Workaround: None.
Resolution: PMFGPA version 3.9 fixes this problem for the supervisor module.
•CSCtc26802
Symptom: Interrupts from the port ASIC instances 5 to 8 did not propagate to the CPU.
Condition: When one or more of the port ASIC instances 5 to 8 generate interrupts in an 8-port 10-Gbps Ethernet I/O module or in a 32-port 10-Gbps Ethernet I/O module, the CPU does not receive the interrupts.
Workaround: None.
Resolution: The following FPGAs fix this problem:
–IOFPGA version 2.5 for the 8-port 10-Gbps Ethernet I/O module
–IOFPGA version 1.15 for the 32-port 10-Gbps Ethernet I/O module
•CSCtc33523
Symptom: The CPU receives interrupts from front panel 1-Gbps Ethernet port temperature sensors on the supervisor modules.
Condition: Occurs when the supervisor module is at a normal temperature.
Root Cause: Wrong interrupt polarity.
Workaround: None.
Resolution: IOFGPA version 3.28 fixes this problem for the supervisor module.
•CSCtc37177
Symptom: Port ASIC errors logged.
Condition: Occurs when reloading I/O modules.
Root Cause: Caused by the default value of PLL resets of the port ASICs.
Workaround: None.
Resolution: The following FPGAs fix this problem:
–IOFGPA version 2.13 for the 48-port 10/100/1000 I/O module
–IOFPGA version 1.5 for the 48-port 1-Gbps I/O module
Limitations
When EPLDs are upgraded or downgraded, the following guidelines and observations apply:
•You cannot upgrade the Local Bus CPLD and CMP CPLD while you are upgrading a supervisor module in the 4.0(1) release only.
•You must upgrade each installed module individually. If the module is online, Cisco NX-OS upgrades only the EPLD images that have different current and new versions. If the module is offline, all EPLDs are upgraded, even if their version numbers are the same.
•If you interrupt an upgrade, you must upgrade the module again.
•You can execute an upgrade or downgrade only from the active supervisor module. On switches with two supervisors, upgrade the standby supervisor and then switch the standby supervisor to active to place the previously active supervisor module in standby mode. Upgrade the EPLDs on the standby supervisor. On switches that have only one supervisor, you must upgrade or downgrade the EPLDs on the active supervisor, which will interfere with data traffic during the upgrade.
•Release 4.1(2) does not provide EPLD upgrades for the Cisco Nexus 7018 fan controller.
Related Documentation
Cisco Nexus 7000 Series documentation is available at the following URL:
http://www.cisco.com/en/US/products/ps9402/tsd_products_support_series_home.html
The documentation set includes the following documents:
•Cisco Nexus 7000 Series Site Preparation Guide
•Cisco Nexus 7000 Series Hardware Installation and Reference Guide
•Cisco Nexus 7000 Series Regulatory Compliance and Safety Information
•Cisco Nexus 7000 Series Connectivity Management Processor Configuration Guide
The release notes for upgrading Cisco NX-OS are available at the following URL:
The release notes for upgrading DCNM are available at the following URL:
http://www.cisco.com/en/US/docs/switches/datacenter/sw/4_2/dcnm/release/notes/dcnm_4_2_relnotes.html
Obtaining Documentation and Submitting a Service Request
For information on obtaining documentation, submitting a service request, and gathering additional information, see the monthly What's New in Cisco Product Documentation, which also lists all new and revised Cisco technical documentation, at:
http://www.cisco.com/en/US/docs/general/whatsnew/whatsnew.html
Subscribe to the What's New in Cisco Product Documentation as a Really Simple Syndication (RSS) feed and set content to be delivered directly to your desktop using a reader application. The RSS feeds are a free service and Cisco currently supports RSS version 2.0.
This document is to be used in conjunction with the documents listed in the "Related Documentation" section.
Cisco and the Cisco logo are trademarks or registered trademarks of Cisco and/or its affiliates in the U.S. and other countries. To view a list of Cisco trademarks, go to this URL: www.cisco.com/go/trademarks. Third-party trademarks mentioned are the property of their respective owners. The use of the word partner does not imply a partnership relationship between Cisco and any other company. (1110R)
Copyright © 2010 Cisco Systems, Inc. All rights reserved.