System Specifications

Environmental Specifications

Environment

Specification

Temperature

Ambient operating temperature

32 to 104°F (0 to 40°C)

Ambient nonoperating

–40 to 158°F (–40 to 70°C)

Relative humidity

Nonoperating

5 to 95%

Operating

5 to 90%

Altitude

Altitude rating is based on power supply installed; see critical components list in the system CB report for altitude rating.

Environment

Specification

Temperature

Ambient operating temperature

32 to 104°F (0 to 40°C)

Ambient nonoperating

–40 to 158°F (–40 to 70°C)

Relative humidity

Nonoperating

5 to 95%

Operating

5 to 90%

Altitude

Operating

0 to 13,123 feet (0 to 4,000 meters)

Switch Dimensions

Switch

Width

Depth

Height

Cisco Nexus 9332D-GX2B

17.3 inches (43.9 cm)

23.9 in (60.8 cm)

1.72 inches (4.4 cm) (1 RU)

Chassis or Module

Width

Depth

Height

Cisco Nexus 9508 chassis

17.5 inches (44.5 cm)

31.76 inches (80.67 cm) for chassis and handles

22.70 inches (57.78 cm) (13 RU)

Supervisor modules

Without mounting brackets: 7.0 inches (17.78 cm)

With mounting brackets: 8.0 inches (20.32 cm)

Inside chassis: 20.67 inches (52.5 cm)

Ejector levers outside chassis: 0.75 inches (1.9 cm)

1.75 inches (4.4 cm)

System controller modules

Without mounting brackets: 6.81 inches (17.3 cm)

With mounting brackets: 7.81 inches (19.84 cm)

Inside chassis: 10.74 inches (27.28 cm)

Ejector levers outside chassis: 0.75 inches (1.9 cm)

1.42 inches (3.61 cm)

Line cards

17.0 inches (43.18 cm)

Inside chassis: 16.5 inches (41.91 cm)

Ejector levers outside chassis: 2.5 inches (6.35 cm)

1.75 inches (4.4 cm)

Fabric modules

2.46 inches (6.25 cm)

11.7 inches (29.72 cm)

16.4 inches (41.66 cm)

Fan trays

5.04 inches (12.81 cm)

5.12 inches (13.0 cm)

Without mounting brackets: 16.5 inches (41.91 cm)

With mounting brackets: 18.08 inches (45.92 cm)

Power supply

5.25 inches (13.33 cm)

Inside chassis: 17.75 inches (44.96 cm)

Ejector levers outside chassis: 0.75 inches (1.9 cm)

1.75 inches (4.4 cm)

Weights for the Chassis, Modules, Fan Trays, and Power Supplies

Component

Weight per Unit

Cisco Nexus 9508 Chassis (N9K-C9508)

150.0 lb (68.2 kg)

Supervisor Modules

Supervisor A module (N9K-SUP-A)

4.84 lb (2.2 kg)

Supervisor A+ module (N9K-SUP-A+)

5.2 lb (2.37 kg)

Supervisor B module (N9K-SUP-B)

6.0 lb (2.72 kg)

Supervisor B+ module (N9K-SUP-B+)

5.3 lb (2.39 kg)

System Controller Module (N9K-SC-A)

1.9 lb (0.9 kg)

Line cards that the N9K-C9508-FM fabric modules support

36-port 40-Gigabit Ethernet QSFP+ ACI Spine line card (N9K-X9736PQ)

11.2 lb (5.1 kg)

Line cards that the N9K-C9508-FM-E fabric modules support

32-port 100-Gigabit Ethernet QSFP+ ACI Spine line card (N9K-X9732C-EX)

12.13 lb (5.5 kg)

36-port 100-Gigabit Ethernet QSFP28 ACI Spine line card (N9K-X9736C-FX)

14.6 lb (6.62 kg)

36-port 40-Gigabit Ethernet QSFP28 ACI Spine line card (N9K-X9736Q-FX)

14.6 lb (6.62 kg)

Line cards that the N9K-C9508-FM-E2 fabric modules support

32-port 100-Gigabit Ethernet QSFP+ ACI Spine line card (N9K-X9732C-EX)

12.13 lb (5.5 kg)

36-port 100-Gigabit Ethernet QSFP28 ACI Spine line card (N9K-X9736C-FX)

14.6 lb (6.62 kg)

36-port 40-Gigabit Ethernet QSFP28 ACI Spine line card (N9K-X9736Q-FX)

14.6 lb (6.62 kg)

Line cards that the N9K-C9508-FM-G fabric modules support

36-port 100-Gigabit Ethernet QSFP28 ACI Spine line card (N9K-X9736C-FX)

14.6 lb (6.62 kg)

36-port 40-Gigabit Ethernet QSFP28 ACI Spine line card (N9K-X9736Q-FX)

14.6 lb (6.62 kg)

16-port 400-Gigabit Ethernet QSFP-DD ACI Spine line card (N9K-X9716D-GX)

15.2 lb (6.8 kg)

Fabric Modules

40-Gigabit N9K-C9508-FM fabric module

9.59 lb (4.4 kg)

100-Gigabit N9K-C9508-FM-E fabric module

11.6 lb (5.28 kg)

100-Gigabit N9K-C9508-FM-E2 fabric module

10.94 lb (5.0 kg)

400-Gigabit N9K-C9508-FM-G fabric module

14.08 lb (6.39 kg)

Fan Trays

(N9K-C9508-FAN)

8.2 lb (3.72 kg)

(N9K-C9508-FAN2)

10.8 lb (4.9 kg)

Blank Fan Power Cards

400-Gigabit N9K-C9508-FAN-PWR spinner card

7.2 lb (3.27 kg)

Power Supplies

3-kW AC Power Supply (N9K-PAC-3000W-B)

6.2 lb (2.8 kg)

3-kW Universal AC/DC Power Supply (N9K-PUV-3000W-B)

5.9 lb (2.67 kg)

3.15-kW Dual Input Universal AC/DC Power Supply (N9K-PUV2-3000W-B)

5.9 lb (2.67 kg)

3-kW DC Power Supply (N9K-PDC-3000W-B)

6.4 lb (2.9 kg)

Power Specifications

Power specifications include the specifications for each type of power supply module.

Power Requirements for Switch Modules

Determine the number of power supplies required to operate all the modules in a switch by adding the maximum power amounts for each module in the switch. Then divide the sum by 3000 W. If there is a fractional amount in the result, add 1 to the result. For n+1 redundancy, add one more power supply. For n+n redundancy, double the number of power supplies and provision for a second power source.

To determine the typical consumption, add the typical power amounts for each module in the switch.

Make sure that any new power supplies use the same type of power (AC or DC) as the rest of the power supplies in the switch. Do not use a mix of AC and DC power sources for a switch.

Maximum Power Available to the Switch

The maximum power available for operations depends on the input power from your power source. Also, the number and output capabilities of your power supplies, and the power redundancy mode that you use. The following table lists the amount of power available for 3-kW power supplies depending on power inputs, numbers of power supplies, and the mode used.

Table 1. Maximum Power Available for a Switch with 3-kW Power Supplies

Power Inputs

Power Supplies

Combined Mode

n+1 Redundancy Mode

n+n Redundancy Mode

1 input (220 V)

1

3000 W

2

6000 W

3000 W

3000 W

3

9000 W

6000 W

3000 W

4

12,000 W

9000 W

6000 W

5

15,000 W

12,000 W

6000 W

6

18,000 W

15,000 W

9000 W

7

21,000 W

18,000 W

9000 W

8

24,000 W

21,000 W

12,000 W

The following power supply unit supports dual high-voltage AC/DC inputs and offers more flexibility to support input-source redundancy.

Table 2. Maximum Power Available for a Switch with 3.15-kW Universal AC/DC Power Supplies

Power Inputs

Power Supplies

Combined Mode

n+1 Redundancy Mode

n+n Redundancy Mode

1 input (220 V)

1

3150 W

2

6300 W

3150 W

3150 W

3

9450 W

6300 W

3150 W

4

12,600 W

9450 W

6300 W

5

15,750 W

12,600 W

6300 W

6

18,900 W

15,750 W

9450 W

7

22,050 W

18,900 W

9450 W

8

25,200 W

22,050 W

12,600 W

Power Supply Specifications

The following subtopics list the specifications for each power supply that this switch supports.

3000-W AC Power Supply Specifications

Property Specification

Power

3000 W

Input Voltage

200 to 240 VAC

Frequency

50 to 60 Hz

Efficiency

90% or greater (20 to 100% load)

Redundancy Modes

Combined, n+1, and n+n

RoHS Compliance

Yes

Hot Swappable

Yes

Airflow Direction

Port-side intake airflow

3000-W Universal AC/DC Power Supply Specifications

Property Specification

Power

3000 W

Input Voltage

200 to 277 VAC or

240 to 380 VDC or

Frequency

47 to 63 Hz

Efficiency

90% or greater (20 to 100% load)

Redundancy Modes

Combined, n+1, and n+n

RoHS Compliance

Yes

Hot Swappable

Yes

Airflow Direction

Port-side intake airflow

3000-W Dual Input Universal AC/DC Power Supply Specifications

Property Specification

Power

3150 W

Input Voltage

180 to 305 VAC or

192 to 400 VDC or

Frequency

50 to 60 Hz

Efficiency

90% or greater (20 to 100% load)

Redundancy Modes

Combined, n+1, and n+n

RoHS Compliance

Yes

Hot Swappable

Yes

Airflow Direction

Port-side intake airflow

Power Cable Specifications

The following subtopics list the specifications for supported power cables.

3-kW AC Power Cable Specifications

Locale Power Cord Part Number Cord Set Rating Power Cord Illustration

Argentina

CAB-9K16A-ARG

16 A, 250 VAC

Brazil

CAB-9K16A-BRZ

16 A, 250 VAC

Korea

CAB-9K16A-KOR

16 A, 250 VAC

South Africa

CAB-9K16A-SA

16 A, 250 VAC

TBD

Australia and New Zealand

CAB-AC-16A-AUS

16 A, 250 VAC

Peoples Republic of China

CAB-AC-16A-CH

16 A, 250 VAC

Continental Europe

CAB-AC-2500W-EU

16 A, 250 VAC

India

CAB-C19-C20-IND

16 A, 250 VAC

India

PWR-CORD10-IND

16 A, 250 VAC

International

CAB-AC-2500W-INT

16 A, 250 VAC

Israel

CAB-AC-2500W-ISRL

16 A, 250 VAC

Japan and North America (nonlocking) 200-240 VAC operation

CAB-AC-2500W-US1

16 A, 250 VAC

Japan and North America (locking) 200-240 VAC operation

CAB-AC-C6K-TWLK

16 A, 250 VAC

Power distribution unit (PDU)

CAB-C19-CBN

16 A, 250 VAC

Switzerland

CAB-ACS-16

16 A, 250 VAC

Taiwan

CAB-AC-C19-TW

16 A, 250 VAC (IEC 60320 C19 to EL 218)

US

CAB-AC-STRT-C19US

16 A, 250 VAC (straight blade NEMA 6-20 plug)

All except Argentina, Brazil, and Japan

NO-PWR-CORD

No power cord is included with order.

N.A.

3-kW Universal AC/DC and 3-kW Dual Input Universal AC/DC Power Cable Specifications

Locale

Power Cord Part Number

Cord Set Rating

Power Cord Illustration

Australia and New Zealand

CAB-AC-16A-SG-AZ

16 A, 250 VAC (AU20LS3/Saf-D-Grid)

CAB-AC-16A-SG-EU

16A, 250 VAC

Israel

CAB-AC-16A-SG-IS

16 A, 250 VAC

International/UK

CAB-AC-16A-SG-IN

16 A, 250 VAC

Italy

CAB-AC-16A-SG-IT

16 A, 250 VAC

South Africa

CAB-AC-16A-SG-SA

16 A, 250 VAC

Switzerland

CAB-AC-16A-SG-SW

16 A, 250 VAC

North America

CAB-AC-20A-SG-C20

250 VAC 20 A

North America

CAB-AC-20A-SG-US

16 A, 250 VAC

North America (non locking) 200-240 VAC operation

CAB-AC-20A-SG-US2

250 VAC 20 A

North America

CAB-AC-20A-SG-US3

250 VAC 20 A

North America 277 VAC operation

CAB-AC-20A-SG-US4

277 VAC 20 A

International, Saf-D-Grid/Saf-D-Grid

CAB-HV-25A-SG-IN1

400 VAC 20 A

International, Ring Terminal source plug, Ring Terminal/Saf-D-Grid

CAB-HV-25A-SG-IN2

20A, 300 VAC/500 VDC

North America

CAB-HV-25A-SG-US1

277 VAC/ 240 VDC/ 380 VDC 25 A

North America

CAB-HV-25A-SG-US2

277 VAC/ 240 VDC/ 380 VDC 25 A

All except Argentina, Brazil, and Japan

NO-PWR-CORD

No power cord included with order

N.A.

3-kW DC Power Supply Power Cord Specifications

Each 3-kW DC power supply requires four customer-supplied power cables (two negative cables and two positive cables). We recommend using six gauge cables. Cisco supplies 6-gauge lugs for connections to the power supply. You supply the connectors that are required to connect the cables to the DC power source.