Specifications

This appendix contains the following topics:

Rack Specifications

Observe the following rack specifications for the Cisco UCS 6500 Series Fabric Interconnect.

Overview of Racks

You can install the fabric interconnect in the following types of cabinets and racks, assuming an external ambient air temperature range of 0 to 104°F (0 to 40°C):

  • Standard perforated cabinets

  • Solid-walled cabinets with a roof fan tray (bottom to top cooling)

  • Standard open racks


Note

If you are selecting an enclosed cabinet, we recommend one of the thermally validated types, either standard perforated or solid-walled with a fan tray.



Note

We do not recommend that you use racks that have obstructions (such as power strips), because the obstructions could impair access to field-replaceable units (FRUs).


General Requirements for Cabinets and Racks

The cabinet or rack must also meet the following requirements:

  • Standard 19-inch (48.3 cm) (two- or four-post EIA cabinet or rack, with mounting rails that conform to English universal hole spacing per section 1 of ANSI/EIA-310-D-1992). For more information, see Requirements Specific to Perforated Cabinets.

  • For a one RU (rack unit) fabric interconnect, the minimum vertical rack space requirement per chassis is 1.75 inches (4.4 cm)

  • The width between the rack-mounting rails must be at least 17.75 inches (45.0 cm) if the rear of the device is not attached to the rack. For four-post EIA racks, this measurement is the distance between the two front rails.

Four-post EIA cabinets (perforated or solid-walled) must meet the following requirements:

  • The minimum spacing for the bend radius for fiber-optic cables should have the front-mounting rails of the cabinet offset from the front door by a minimum of 3 inches (7.6 cm).

  • The distance between the outside face of the front mounting rail and the outside face of the back mounting rail should be 23.0 to 30.0 inches (58.4 to 76.2 cm) to allow for rear-bracket installation.

Requirements Specific to Standard Open Racks

If you are mounting the chassis in an open rack (no side panels or doors), ensure that the rack meets the following requirements:

  • The minimum vertical rack space per chassis must be equal to the rack unit (RU) of the chassis. One rack unit is equal to 1.75 inches (4.4 cm).

  • The distance between the chassis air vents and any walls should be 2.5 inches (6.4 cm).

Requirements Specific to Perforated Cabinets

A perforated cabinet has perforations in its front and rear doors and side walls. Perforated cabinets must meet the following requirements:

  • The front and rear doors must have at least a 60 percent open area perforation pattern, with at least 15 square inches (96.8 square cm) of open area per rack unit of door height.

  • The roof should be perforated with at least a 20 percent open area.

  • The cabinet floor should be open or perforated to enhance cooling.

The Cisco R Series rack conforms to these requirements.

Cable Management Guidelines

To help with cable management, you might want to allow additional space in the rack above and below the chassis to make it easier to route all of the fiber optic or copper cables through the rack.

System Specifications

Observe the following system specifications when installing and operating the Cisco UCS 6500 Series Fabric Interconnect.

Environmental Specifications

Environment

Specification

Temperature

Ambient operating temperature

32 to 104°F (0 to 40°C)

Ambient nonoperating

–40 to 158°F (–40 to 70°C)

Relative humidity

Nonoperating

5 to 95%

Altitude

Operating

0 to 13,123 feet (0 to 4,000 meters)

Fabric Interconnect Dimensions

Fabric Interconnect

Width

Depth

Height

Cisco UCS 6536 Fabric Interconnect

17.3 inches (43.9 cm)

24.7 inches (62.7 cm)

1.72 inches (4.4 cm) (1 RU)

Fabric Interconnect and Module Weights and Quantities

Component

Weight per Unit

Quantity

Cisco UCS 6536 Fabric Interconnect Chassis (UCS-6536-FI)

18.8 lb (8.5 kg)

1

Fan Module (UCS-FAN-6536), Port-side exhaust (dark grey)

0.6 lb (0.3 kg)

6

Power Supply module

– 1100-W AC port-side exhaust (dark grey) (UCS-PSU-6536-AC)

2.42 lb (1.1 kg)

2 (1 for operations and 1 for redundancy)

Fabric Interconnect Power Input Requirements

The following table lists the typical amount of power that the fabric interconnect consumes. It also lists the maximum amount of power that you must provision for the fabric interconnect and power supply for peak conditions.


Note

Some power supplies have capabilities that are greater than the maximum power requirements for a fabric interconnect. To determine the power consumption characteristics for the fabric interconnect, use the typical and maximum requirements that are listed in the following table.


Switch Typical Power Consumption (AC or DC) Maximum Power Consumption (AC or DC) Heat Dissipation Requirement

Power Specifications

Power specifications include the specifications for each type of power supply module.

1100-W AC Power Supply Specifications

These specifications apply to the fabric interconnect's AC power supply modules (UCS-PSU-6536-AC).

Characteristic Specification

AC input voltage

Nominal range: 100 and 240 VAC (Range: 90-132 VAC, 180-264 VAC)

AC input frequency

Nominal range: 50 to 60 Hz (Range: 47-63 Hz)

Maximum AC input current

13 A at 100 VAC

6 A at 240 VAC

Maximum input volt-amperes

1300 VA at 100 VAC

Maximum output power per power supply

1100 W

Maximum inrush current

33 A

Maximum hold-up time

12 ms at 1100 W

Power supply output voltage

12 VDC

Power supply standby voltage

12 VDC

Efficiency rating

Climate Savers Platinum Efficiency (80Plus Platinum certified)

Form factor

RSP1

Power Cable Specifications

The following sections specify the power cables that you can order and use with this fabric interconnect.

Power Cable Specifications for AC Power Supplies

Power Type Power Cord Part Number Cord Set Description

CAB-C13-C14-2M

Power Cord Jumper, C13-C14 Connectors, 6.6 feet (2.0 m)

CAB-C13-CBN

Cabinet jumper power cord, 250 VAC, 10 A, C14-C13 connectors, 2.3 feet (0.7 m)

Argentina

CAB-250V-10A-AR

250 V, 10 A, 8.2 feet (2.5 m)

Australia

CAB-9K10A-AU

250 VAC, 10 A, 3112 plug, 8.2 feet (2.5 m)

Brazil

CAB-250V-10A-BR

250 V, 10 A, 6.9 feet (2.1 m)

European Union

CAB-9K10A-EU

250 VAC, 10 A, CEE 7/7 plug, 8.2 feet (2.5 m)

India

CAB-IND-10A

10 A, 8.2 feet (2.5 m)

India

CAB-C13-C14-2M-IN

Power Cord Jumper, C13-C14 Connectors, 6.6 feet (2.0 m)

India

CAB-C13-C14-3M-IN

Power Cord Jumper, C13-C14 Connectors, 9.8 feet (3.0 m)

Israel

CAB-250V-10A-IS

250 V, 10 A, 8.2 feet (2.5 m)

Italy

CAB-9K10A-IT

250 VAC, 10 A, CEI 23-16/VII plug, 8.2 feet (2.5 m)

Japan

CAB-C13-C14-2M-JP

Power Cord Jumper, C13-C14 Connectors, 6.6 feet (2.0 m)

North America

CAB-9K12A-NA

125 VAC, 13 A, NEMA 5-15 plug, 8.2 feet (2.5 m)

North America

CAB-AC-L620-C13

NEMA L6-20-C13, 6.6 feet (2.0 m)

North America

CAB-N5K6A-NA

200/240V, 6A, 8.2 feet (2.5 m)

Peoples Republic of China

CAB-250V-10A-CN

250 V, 10 A, 8.2 feet (2.5 m)

South Africa

CAB-250V-10A-ID

250 V, 10 A, 8.2 feet (2.5 m)

Switzerland

CAB-9K10A-SW

250 VAC, 10 A, MP232 plug, 8.2 feet (2.5 m)

United Kingdom

CAB-9K10A-UK

250 VAC, 10 A, BS1363 plug (13 A fuse), 8.2 (2.5 m)

All except Argentina, Brazil, and Japan

NO-POWER-CORD

No power cord included with fabric interconnect

Regulatory Standards Compliance Specifications

The following table lists the regulatory standards compliance for the fabric interconnect.

Table 1. Regulatory Standards Compliance: Safety and EMC

Specification

Description

Regulatory compliance

Products should comply with CE Markings according to directives 2004/108/EC and 2006/95/EC.

Safety

  • UL 60950-1

  • CAN/CSA 22.2 No 60950-1-07

  • AS/NZS 60950.1

  • EN 60950-1 plus Am2

  • IEC 60950-1 plus Am 2 with all country deviations

  • UL 62368-1

  • CAN/CSA 22.2 No 62368-1

  • EN 62368-1

  • IEC 62368-1 with all country deviations

  • Additional Certifications may be required as countries adopt new Standards like IEC 62368-1

EMC: Emissions

  • 47CFR Part 15 (CFR 47) Class A

  • AS/NZS CISPR22 Class A

  • CISPR22 Class A

  • EN55022 Class A

  • ICES003 Class A

  • VCCI Class A

  • EN61000-3-2

  • EN61000-3-3

  • KN22 Class A

  • CNS13438 Class A

EMC: Immunity

  • EN55024

  • CISPR24

  • EN300386

  • KN 61000-4 series

RoHS

The product is RoH-6 compliant with exceptions for leaded-ball grid-array (BGA) balls and lead press-fit connectors.