The documentation set for this product strives to use bias-free language. For the purposes of this documentation set, bias-free is defined as language that does not imply discrimination based on age, disability, gender, racial identity, ethnic identity, sexual orientation, socioeconomic status, and intersectionality. Exceptions may be present in the documentation due to language that is hardcoded in the user interfaces of the product software, language used based on RFP documentation, or language that is used by a referenced third-party product. Learn more about how Cisco is using Inclusive Language.
This appendix contains tables that list the specifications for the main components of the Line Card Chassis.
This appendix contains tables that list the specifications for the main components of the Line Card Chassis.
Note | For a complete list of cards supported in the Cisco CRS 16-slot line card chassis, go to the Cisco Carrier Routing System Data Sheets at: http://www.cisco.com/c/en/us/products/routers/carrier-routing-system/datasheet-listing.html |
The appendix includes the following topics:
The table below lists the specifications for the Cisco CRS Carrier Routing System 16-Slot Line Card Chassis.
Chassis Dimensions |
|
Height |
80 in. (203.2 cm) as shipped84 in. (213.4 cm) as installed |
Width |
23.6 in. (60.0 cm) 26.1 in. (66.3 cm) with PDU and brackets |
Depth
|
36 in. (91 cm) without doors and other cosmetics39.7 in. (101 cm) with front and rear doors |
Floor space requirement |
Chassis: 6 sq ft (0.56 sq m) Aisle spacing to install chassis (front): 48 in. (122 cm) Aisle spacing to service FRUs (front): 36 in. (91 cm) Aisle spacing to service FRUs (rear): 36 in. (91 cm) |
Chassis |
|
Chassis shipping weight |
1175 lb (532 kg) LCC with shipping crate and pallet |
Chassis with power shelves only, no power modules |
849 lb (385 kg) |
Chassis with power shelves, power modules, alarm module |
970 lb (440 kg) |
Chassis, fully loaded with cards, without cosmetics |
1585 lb (719 kg) |
Chassis, fully loaded with cards and cosmetics (doors, panels, grilles, and so on) |
1629 lb (739 kg) |
Chassis, fully loaded with cards and cosmetics (doors, panels, grilles, and so on), AC Wye PDU, and brackets |
1689 lb (766 kg) |
Chassis, fully loaded with cards and cosmetics (doors, panels, grilles, and so on), AC Delta PDU, and brackets |
1715 lb (778 kg) |
Floor Loading |
|
Chassis footprint |
4.72 sq ft (4385 sq cm) |
Floor contact area |
680 sq in. (4385 sq cm) |
Maximum floor loading |
Without cosmetics and doors: 1585 lb/4.72 sq. ft = 335 lb/sq. ft719 kg/4385 sq. cm = 0.164 kg/sq. cm With cosmetics and doors: 1695 lb/4.72 sq. ft = 359 lb/sq. ft769 kg/4385 sq. cm = 0.175 kg/sq. cm |
Cards/Ports/Slots |
1-port OC-768c/STM-256c packet over Synchronous Optical Network (POS) 4-port OC-192c/STM-64c POS/Dynamic Packet Transport (DPT) 16-port OC-48c/STM-16 POS/DPT 8-port 10 Gigabit Ethernet 4-port 10 Gigabit Ethernet CRS1-SIP-800 Carrier Card 4-Port OC-3/STM-1 POS SPA 8-Port 1 Gigabit Ethernet SPA 1-port OC-768c/STM-256c Tunable WDMPOS 4-port 10GE Tunable WDMPHY |
Chassis Cooling |
2 fan trays, push-pull configuration |
Chassis airflow |
Up to 2050 cubic ft (58,050 liters) per minute |
Power shelf airflow |
100 to 140 cubic ft (2832 to 3964 liters) per minute |
AC power cord length |
167 in. (4.25 m) |
The table below lists the fixed configuration power specifications for the LCC.
Description |
Value |
---|---|
Power shelves |
2 AC or 2 DC power shelves (Cannot mix AC and DC power shelves.) |
DC power shelf |
3 power entry modules (PEMs) per shelf |
AC power shelf |
3 PEMs per shelf |
Maximum Input Power |
|
Fixed configuration DC, chassis fully loaded |
13,895 W (13.9 kW) 95% efficiency |
Fixed configuration AC, chassis fully loaded |
15,000 W (15.0 kW) 88% efficiency |
Maximum Output Power |
|
Chassis fully loaded (DC and AC) |
12,744 W (12.7 kW) |
Power Redundancy (2N) |
|
DC |
2N: Requires 6 “A” battery plant feeds and 6 “B” battery plant feeds (up to 12 total) |
AC, 3-phase |
2N: Requires two independent 3-phase AC sources |
DC Input |
|
Nominal input voltage |
–48 VDC North America–60 VDC European Community(range –42 to –75 VDC) |
Input current
|
50 A max at –48 VDC40 A max at –60 VDC |
AC Input, Delta 3-phase |
3W+PE (3 wire + protective earthing1) |
Nominal input voltage |
3-phase 200 to 240 VAC, phase-to-phase(range 180 to 264 VAC, phase-to-phase) |
Nominal line frequency |
50/60 Hz (range 47 to 63 Hz) |
Recommended AC service |
60 A |
AC Input, Wye 3-phase |
3W+N+PE (3 wire + neutral + protective earthing1) |
Nominal input voltage |
3-phase 200-240/346-415 VAC(range 180 to 264 VAC, phase-to-neutral)(range 311 to 456 VAC, phase-to-phase) |
Nominal line frequency |
50/60 Hz (range 47 to 63 Hz) |
Recommended AC service |
40 A (North America)32 A (International) |
The table below lists the modular configuration power specifications for the Cisco CRS 16-Slot Line Card Chassis.
Description |
Value |
---|---|
Power shelves |
2 AC or 2 DC power shelves (Cannot mix AC and DC power shelves.) |
DC power shelf |
Supports up to 8 DC power modules (PMs) 6 PMs are shipped per shelf |
AC power shelf |
Supports up to 6 DC power modules (PMs) 5 PMs are shipped per shelf |
Maximum Input Power |
|
Modular configuration, DC, chassis fully loaded |
14,667 watts (14.7 kW) 88% efficiency
|
Modular configuration, AC, chassis fully loaded |
14,348 watts (14.4 kW) 92% efficiency |
Maximum Output Power |
|
Chassis fully loaded (DC and AC) |
13,200 W (13.2 kW) |
Power Redundancy |
|
DC |
2N: Up to 8 “A” battery plant feeds and up to 8 “B” battery plant feeds |
AC |
2N: Up to 6 “A” AC single-phase power sources and up to 6 “B” single-phase AC power sources required. |
DC Input |
|
Nominal input voltage |
–48 VDC North America–60 VDC InternationalRange: 40 to –72 VDC |
Input current |
40 A max at –48 VDC30 A max at –60 VDC50 A at –40 VDC (maximum) |
AC Input |
Single-phase |
Nominal input voltage |
200 to 240 VAC (range 180 to 264 VAC) |
Nominal line frequency |
50/60 Hz (range 47 to 63 Hz) |
Recommended AC service |
20 A (North America) dedicated branch circuit16 A (International) dedicated branch circuit |
The table below lists the environmental specifications for the line card chassis.
Description |
Value |
---|---|
Temperature |
Operating, nominal: 41° to 104°F (5° to 40°C) Operating, short-term: 23° to 122°F (–5° to 50°C)2 Nonoperating: –40° to 158°F (–40° to 70°C) |
Humidity |
Operating: 5 to 85% noncondensing Nonoperating: 5 to 90% noncondensing, short-term operation |
Altitude |
–197 to 5906 ft (–60 to 1800 m) at 122°F (50°C), short-term Up to 13,123 ft (4000 m) at 104°F (40°C) or below |
Heat dissipation |
47,408 BTU per hour (maximum) fixed configuration DC3 51,180 BTU per hour—(maximum) fixed configuration AC4 50,042 BTU per hour (maximum) modular configuration DC5 48,955 BTU per hour—(maximum) modular configuration AC6 |
Air exhaust temperature |
129°F (54°C)—at room temperatures of 95 to 102°F (35 to 39°C) 149°F (65°C)—maximum exhaust temperature on a fully loaded system during worst-case operating conditions (50°C and 6000 ft altitude) Air temperature rise is 59°F (15°C) on a fully loaded system with fans running at maximum speed (5150 RPM). At room temperatures below 95°F (35°C), exhausted air is 66.2°F (19°C) higher than room temperature. At temperatures above 102°F (39°C), exhausted air is 59°F (15°C) higher than room temperature. |
Air velocity (at exhaust) |
1400 ft per minute (426.7 m per minute) at normal room temperature, low fan speed (4000 RPM) 1800 ft per minute (548.6 m per minute) at high temperature or altitude, maximum fan speed (5150 RPM) Software controls the speed of the fans based on measurements from the chassis thermal sensors. |
Sound power level(fixed configuration power) |
Room temp 27°C, sound power, 76.2dB with Arctic Room temp 40°C, sound power, 88 dB with Arctic Room temp 27°C, sound power, 82.2dB with TDI AC Room temp 27°C, sound power, 77.2dB with TDI DC Room temp 40°C, sound power, 89dB with TDI AC Room temp 40°C, sound power, 88dB with TDI |
Sound power level(modular configuration power) |
Fan speed 3300 RPM, temperature 80°F (27°C): 76.2 dB—modular configuration power Fan speed 5150 RPM, temperature 104°F (40°C): 88.0 dB—modular configuration power |
Shock and vibration |
Designed and tested to meet the NEBS shock and vibration standards defined in GR-63-CORE (Issue 2, April 2002). |
For information about the regulatory, compliance, and safety standards to which the Cisco CRS Series system conforms, see Regulatory Compliance and Safety Information for the Cisco CRS Carrier Routing System .