- A.1 CPT 200 Shelf Specifications
- A.1.1 Bandwidth
- A.1.2 Cisco Transport Controller
- A.1.3 External LAN Interface for EMS
- A.1.4 TL1 Craft Interface
- A.1.5 Modem Interface
- A.1.6 Alarm Interface
- A.1.7 Passive Unit Remote Inventory
- A.1.8 BITS Interface
- A.1.9 System Timing
- A.1.10 System Power
- A.1.11 Fan Tray
- A.1.12 System Environmental Specifications
- A.1.13 Dimensions
- A.2 CPT 600 Shelf Specifications
- A.2.1 Bandwidth
- A.2.2 Cisco Transport Controller
- A.2.3 External LAN Interface for EMS
- A.2.4 TL1 Craft Interface
- A.2.5 Modem Interface
- A.2.6 Alarm Interface
- A.2.7 Passive Unit Remote Inventory
- A.2.8 BITS Interface
- A.2.9 System Timing
- A.2.10 System Power
- A.2.11 Fan Tray
- A.2.12 System Environmental Specifications
- A.2.13 Dimensions
Hardware Specifications
This appendix contains hardware and software specifications of the CPT 200, and CPT 600 shelf.
The following sections are included:
A.1 CPT 200 Shelf Specifications
This section provides specifications for shelf bandwidth; a list of topologies; Cisco Transport Controller (CTC) specifications; the LAN, Transaction Language One (TL1), modem, and alarm specifications; timing, power, and environmental specifications; and shelf dimensions.
A.1.1 Bandwidth
The CPT 200 has the following bandwidth specifications depending of the applications):
•Total bandwidth: 200 Gbps
•Data plane bandwidth: 100 Gbps per slot
A.1.2 Cisco Transport Controller
CTC, the CPT 200 craft interface software, has the following specifications:
•10/100BaseT Ethernet
•TNC/TNCE/TSC/TSCE card access: RJ-45 LAN connector on the controller front plate
A.1.3 External LAN Interface for EMS
The CPT 200 external LAN interface has the following specifications:
•10/100BaseT Ethernet located on the power module
A.1.4 TL1 Craft Interface
The CPT 200 TL1 craft interface has the following specifications:
•TNC/TNCE/TSC/TSCE access: EIA/TIA-232 DB-9 type connector
A.1.5 Modem Interface
The CPT 200 modem interface has the following specifications:
•Hardware flow control
•TNC/TNCE/TSC/TSCE: EIA/TIA-232 DB-9 type connector
A.1.6 Alarm Interface
The CPT 200 does not support alarm interface.
A.1.7 Passive Unit Remote Inventory
The CPT 200 provides 1 standard USB port located on the power module to retrieve the passive units inventory data.
A.1.8 BITS Interface
The CPT 200 building integrated timing supply (BITS) interface has the following specifications:
•1 DS-1 BITS inputs wire wrap for ANSI applications
•1 derived DS-1 outputs wire wrap for ANSI applications
•1 E1 BITS input DIN-1.0/2.3 for ETSI applications
•1 E1 BITS output DIN-1.0/2.3 for ETSI applications
A.1.9 System Timing
The CPT 200 for ANSI has the following system timing specifications:
•Stratum 3 per Telcordia GR-253-CORE
•Free running accuracy: +/- 4.6 ppm
•Holdover stability: 3.7 x 10-7 per day, including temperature (< 255 slips in first 24 hours)
•Reference: External BITS, line, internal
The CPT 200 for ETSI has the following system timing specifications:
•Stratum 3, per ITU-T G.813
•Free running accuracy: +/- 4.6 ppm
•Holdover stability: 3.7 exp -7 per day, including temperature (< 255 slips in first 24 hours)
•Reference: External BITS, line, internal
A.1.10 System Power
The CPT 200 has the following AC power specifications:
•Input Voltage: 100V - 240V AC (+/- 10%)
•Power consumption: Configuration dependent; 35 W (fan-tray and LCD)
•Power terminals standard 3 pole AC connector
•For an AC power supply, the fuse rating must not exceed 10A, 15A, or 20A depending on the standard in various countries. For North America, the branch circuit protection must be rated 20A.
•Total maximum power consumption of 350W with ancillaries, controllers and line cards
The CPT 200 has the following DC power specifications:
•Nominal Input Voltage: -48 VDC
•Power consumption: Configuration dependent; 35 W (fan-tray and LCD)
•Power requirements:
–Nominal: -48 VDC
–Input Voltage Range: -40.5 to -57.6 VDC
•Power terminals: DSUB 2 poles for ETSI applications and terminal block double pole for ANSI applications
•External fuse must not exceed 15A
•Total maximum power consumption of 450W with ancillaries, controllers and line cards
A.1.11 Fan Tray
Table A-1 lists power requirements for the fan-tray assembly.
|
|
|
|
---|---|---|---|
15454-M2-FTA |
35 |
1 |
120 |
15454-M2-FTA2 |
40 |
1 |
135 |
A.1.12 System Environmental Specifications
The CPT 200 for ANSI environment has the following specifications:
•Operating temperature: 23 to +131 degrees Farenheit (-5 to +55 degrees Celsius)
•Operating humidity: 5 to 95 percent, noncondensing
The CPT 200 for ETSI environment has the following specifications:
•Operating temperature: 23 to 131 degrees Fahrenheit (-5 to +55 degrees Celsius)
•Operating humidity: 5 to 95 percent, noncondensing
A.1.13 Dimensions
The CPT 200 shelf assembly has the following dimensions:
•Height: 3.5 inches (88.9 mm)
•Width: 19 or 23 inches (482.6 or 584.2 mm) with mounting ears attached
•Depth: 11.1 inches (281.94 mm)
•Weight:
–11.02 pounds (5 kg) with preinstalled air filter and no cards installed
–15.40 pounds (6.82 kg) with the power module, fan-tray assembly and air filter installed but with no cards.
A.2 CPT 600 Shelf Specifications
This section provides specifications for shelf bandwidth; a list of topologies; Cisco Transport Controller (CTC) specifications; the LAN, Transaction Language One (TL1), modem, and alarm specifications; timing, power, and environmental specifications; and CPT 600 shelf dimensions.
The CPT 600 shelf is compliant with the ETS 300-119-4 standard.
A.2.1 Bandwidth
The CPT 600 has the following bandwidth specifications (depending of the applications):
•Total bandwidth: 400 Gbps
•Data plane bandwidth: 100 Gbps per slot
A.2.2 Cisco Transport Controller
CTC, the CPT 600 craft interface software, has the following specifications:
•10/100BaseT Ethernet
•TNC/TNCE/TSC/TSCE card access: RJ-45 LAN connector on the controller front plate
•Shelf access: RJ-45 LAN Connector located on the ECU or ECU2
A.2.3 External LAN Interface for EMS
The CPT 600 external LAN interface has the following specification:
•10/100BaseT Ethernet located on the ECU or ECU2 and supports:
–10/100 Mbps full duplex
–Auto detection
A.2.4 TL1 Craft Interface
The CPT 600 TL1 craft interface has the following specifications:
•Speed: 9600 bps
•TNC/TNCE/TSC/TSCE access: EIA/TIA-232 DB-9 type connector
•An alternative RJ-45 LAN connector on TNC/TNCE/TSC/TSCE or ECU or ECU2
A.2.5 Modem Interface
The CPT 600 modem interface has the following specifications:
•Hardware flow control
•TNC/TNCE/TSC/TSCE: EIA/TIA-232 DB-9 type connector
A.2.6 Alarm Interface
The CPT 600 alarm interface has the following specifications:
•2 SCSI Connectors located on the ECU or ECU2
•Visual: Critical, Major, Minor, Remote
•Audible: Critical, Major, Minor, Remote
•Alarm inputs: Common 32-VDC output for all alarm-inputs, closed contact limited to 2 mA
•Control outputs: Open contact maximum 60 VDC, closed contact maximum 100 mA
A.2.7 Passive Unit Remote Inventory
The CPT 600 provide 12 standard USB ports located on the ECU or ECU2 to retrieve the inventory data from the passive units.
A.2.8 BITS Interface
The CPT 600 building integrated timing supply (BITS) interface has the following specifications:
•2 T1 BITS inputs wire wrap for ANSI applications
•2 derived T1 outputs wire wrap for ANSI applications
•2 E1 BITS input DIN-1.0/2.3 for ETSI applications
•2 E1 BITS output DIN-1.0/2.3 for ETSI applications
A.2.9 System Timing
The CPT 600 for ANSI has the following system timing specifications:
•Stratum 3 per Telcordia GR-253-CORE
•Free running accuracy: +/- 4.6 ppm
•Holdover stability: 3.7 x 10-7 per day, including temperature (< 255 slips in first 24 hours)
•Reference: External BITS, line, internal
The CPT 600 for ETSI has the following system timing specifications:
•Stratum 3, per ITU-T G.813
•Free running accuracy: +/- 4.6 ppm
•Holdover stability: 3.7 exp -7 per day, including temperature (< 255 slips in first 24 hours)
•Reference: External BITS, line, internal
A.2.10 System Power
The CPT 600 has the following AC power specifications:
•Input voltage: 100 V to 240 V AC (+/-10%).
•Power consumption: Configuration dependent; 130 W (fan-tray, LCD, and ECU or ECU2).
•Power terminals standard 3-pole AC connector.
•Fuse rating for an AC power supply must not exceed 10 A, 15 A, or 20 A depending on the standard in various countries. For North America, the branch circuit protection must be rated 20 A.
•Total maximum power consumption of 900 W with ancillaries, controllers, and line cards.
The CPT 600 has the following DC power specifications:
•Nominal Input Voltage: -48 VDC
•(15454-M6-DC and 15454-M6-DC20) Power consumption: Configuration dependent; 130 W (15454-M6-FTA Fan Tray, LCD, and ECU or ECU2).
•(15454-M6-DC and 15454-M6-DC20) Power consumption: Configuration dependent; 140 W (15454-M6-FTA2 Fan Tray, LCD, and ECU or ECU2).
•Power requirements:
–Nominal: -48 VDC
–Input Voltage Range: -40.5 to -57.6 VDC
•Power terminals: DSUB 3 poles for ETSI applications and terminal block double pole for ANSI applications
•External fuse must not exceed 40 A
•(15454-M6-DC only) Total maximum power consumption of 1350 W with ancillaries, controllers, and line cards.
•(15454-M6-DC20 only) Total maximum power consumption of 960 W with ancillaries, controllers and line cards.
A.2.11 Fan Tray
Table A-2 lists power requirements for the fan-tray assembly.
|
|
|
|
---|---|---|---|
15454-M6-FTA |
120 |
3 |
410 |
15454-M6-FTA2 |
130 |
3.5 |
445 |
A.2.12 System Environmental Specifications
The CPT 600 for ANSI environment has the following specifications:
•Operating temperature: 23 to +131 degrees Farenheit (-5 to +55 degrees Celsius)
•Operating humidity: 5 to 95 percent, noncondensing
The CPT 600 for ETSI environment has the following specifications:
•Operating temperature: 23 to 131 degrees Fahrenheit (-5 to +55 degrees Celsius)
•Operating humidity: 5 to 95 percent, noncondensing
A.2.13 Dimensions
The CPT 600 shelf assembly has the following dimensions:
•Height: 10.4 inches (264.16 mm)
•Width: 19 or 23 inches (482.6 or 584.2 mm) with mounting ears attached
•Depth: 11.1 inches (281.94 mm)
•Weight:
–23.55 pounds (10.680 kg) with preinstalled air filter and no cards installed
–40.12 pounds (18.2 kg) with all the ancillary units (2 DC power modules, ECU or ECU2, fan-tray assembly and air filter) installed but with no cards.