NTP-L48 Mounting Brackets on NCS 2015 Shelf for ANSI Rack Configuration
Purpose |
This procedure helps in mounting the brackets on the NCS 2015 shelf for ANSI rack configuration. The mounting brackets can be installed in the middle position of the chassis. |
Tools/Equipment |
|
Prerequisite Procedures |
|
Required/As Needed |
Required |
Onsite/Remote |
Onsite |
Security Level |
None |
Procedure
Step 1 |
Align the mounting bracket screw holes against the shelf screw holes. |
||||||||||||||||
Step 2 |
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m). |
||||||||||||||||
Step 3 |
Repeat steps 1 and 2 for the mounting bracket on the opposite side. The following figure shows the mounting of brackets for a 19-inch (482.6-mm) configuration.
The following figure shows the mounting of brackets for a 23-inch (584.2-mm) configuration.
The following figure shows the mounting of Z-brackets for a 23-inch (584.2-mm) configuration.
Stop. You have completed this procedure. |